Danfoss VACON 20 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Overcurrent | Cause: Frequency converter has detected too high a current (>4*In) in the motor cable:
Remedy:
|
| 2 Overvoltage | Cause: The DC-link voltage has exceeded the internal safety limit:
Remedy: Increase the deceleration time (Par.4.3 or Par.4.6). |
| 3 Earth fault | Cause: Current measurement has detected extra leakage current at start:
Remedy: Check motor cables and motor. |
| 8 System fault | Cause:
Remedy: Reset the fault and restart. If the fault re-occurs, contact the distributor near to you. NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault History menu under Id xxx! |
| 9 Under voltage | Cause: The DC-link voltage has gone below the internal safety limit:
Remedy: In case of temporary supply voltage break reset the fault and restart the frequency converter. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact the distributor near to you. |
| 10 Input phase fault | Cause: Input phase is missing. Remedy: Check supply voltage, fuses and cable. |
| 11 Output phase fault | Cause: Current measurement has detected that there is no current in one motor phase. Remedy: Check motor cable and motor. |
| 13 Frequency converter under temperature | Cause: Heat sink temperature is under -10 °C. Remedy: Check the ambient temperature. |
| 14 Frequency converter over temperature | Cause: Heat sink is overheated. Remedy:
|
| 15 Motor stalled | Cause: Motor stall protection has tripped. Remedy: Check that the motor is able to rotate freely. |
| 16 Motor over temperature | Cause: Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded. Remedy: Decrease the motor load. If no motor overload exists, check the temperature model parameters. |
| 17 Motor underload | Cause: Motor underload protection has tripped. Remedy: Check motor and load, e.g. for broken belts or dry pumps. |
| 22 EEPROM checksum fault | Cause: Parameter save fault:
Remedy: Contact the distributor near to you. NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault History menu under Id xxx! |
| 25 Microcontroller watchdog fault | Cause:
Remedy: Reset the fault and restart. If the fault re-occurs, contact the distributor near to you. |
| 27 Back EMF protection | Cause: Drive has detected that the magnetized motor is running in start situation.
Remedy: Make sure that there is no rotating PM-motor when the start command is given. |
| 29 Thermistor fault | Cause: The thermistor input of option board has detected increase of the motor temperature. Remedy: Check motor cooling and loading. Check thermistor connection (If thermistor input of the option board is not in use it has to be short circuited). |
| 34 Internal bus communication | Cause: Ambient interference or defective hardware. Remedy: If the fault re-occurs, contact the distributor near to you. |
| 35 Application fault | Cause: Application is not working properly. Remedy: Contact the distributor near to you. NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault History menu under Id xxx! |
| 41 IGBT Overtemperature | Cause: Overtemperature alarm is issued when the IGBT switch temperature exceeds 110 °C. Remedy: Check loading. Check motor size. Make identification run. |
| 50 Analog input select 20% – 100% (selected signal range 4 to 20 mA or 2 to 10 V) | Cause: Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V.
Remedy: Check the current loop circuitry. |
| 51 External fault | Cause: Digital input fault. Digital input has been programmed as external fault input and this input is active. Remedy: Remove the external device fault. |
| 52 Door Panel fault | Cause: Control place is keypad, but door panel has been disconnected. Remedy: Check the connection between optional board and API. If connection is correct, contact the nearest Vacon distributor. |
| 53 Fieldbus fault | Cause: The data connection between the fieldbus Master and the fieldbus of the drive has broken. Remedy: Check installation. If installation is correct, contact the nearest Vacon distributor. |
| 54 Slot fault | Cause: The connection between optional board and API has been broken. Remedy: Check board and slot. Contact the nearest Vacon distributor. |
| 55 Wrong run fault (FWD/REV conflict) | Cause: Run forward and backward are high at the same time. Remedy: Check I/O control signal 1 and I/O control signal 2. |
| 57 Identification fault | Cause: Identification run has failed. Remedy: Run command was removed before completion of identification run. Motor is not connected to frequency converter. There is load on motor shaft. |
| 63 Quick Stop | Cause: Quick Stop activated. Remedy: The drive has been stopped with Quick Stop digital input or Quick Stop command by fieldbus. |
| 111 Temperature fault | Cause: Over low or over high temperature. Remedy: Check temperature signal from OPTBH board. |