Mitsubishi FR-CS80 Drive

Fault Code and MeaningCause and Remedy
HOLD
Operation panel lock

Cause: Operation lock is set. Operation other than STOP/RESET is invalid.


Remedy:

  • Press MODE for 2 seconds to release the lock.


LOCD
Parameter locked

Cause: Password function is active. Display and setting of parameters are restricted.


Remedy:

  • Enter the password in Pr.297 (Password lock/unlock) to unlock the password function before the operation.


Er1
Write disable error

Cause:
Parameter setting was attempted while Pr.77 is set to disable write, or overlapping ranges set for frequency jump/adjustable 5 points V/F. The PU and inverter may not be communicating normally.


Remedy:

  • Check the Pr.77 Parameter write selection setting.

  • Check the settings of Pr.31 to Pr.36 (frequency jump).

  • Check the settings of Pr.100 to Pr.105 (adjustable 3 points V/F).

  • Check the connection of the PU and the inverter.


Er2
Write error during operation

Cause: Parameter write was attempted while Pr.77 Parameter write selection = “0”.


Remedy:

  • Check that the inverter is stopped.

  • After stopping the operation, make parameter setting.

  • When setting Pr.77 = “2”, parameter write is enabled during operation.


Er3
Calibration error

Cause: Analog input bias and gain calibration values are set too close.


Remedy:

  • Check the settings of the calibration parameters C3, C4, C6, and C7 (calibration functions).


Er4
Mode designation error

Cause:
Parameter setting is attempted in the External or NET operation mode when Pr.77 = “1”, or when the command source is not at the operation panel.


Remedy:

  • Check that operation mode is PU operation mode.

  • Check that the Pr.551 PU mode operation command source selection setting is correct.

  • After setting the operation mode to the “PU operation mode”, set the parameter.

  • When Pr.77 = “2”, parameter write is enabled regardless of the operation mode.


Err.
(Error)

Cause: The RES signal is turned ON, or voltage at the input side of the inverter has dropped.


Remedy:

  • Turn OFF the RES signal.

  • Check the voltage on the input side of the inverter.


OLC (FR-LU08: OL)
Stall prevention (overcurrent)

Cause:
When the output current of the inverter increases, the stall prevention function is activated. This stops the increase (during accel) or decreases frequency (during constant speed/decel) to prevent an overcurrent trip.


Remedy:

  • Check that the Pr.0 Torque boost setting is not too large.

  • Check if Pr.7 Acceleration time and Pr.8 Deceleration time settings are too short.

  • Check that the load is not too heavy.

  • Check for any failures in peripheral devices.

  • Check that Pr.13 Starting frequency is not too large.

  • Check that Pr.22 Stall prevention operation level is appropriate.

  • Set a larger value in Pr.7 and Pr.8.

  • Reduce the load or try General-purpose magnetic flux vector control.


OLV (FR-LU08: oL)
Stall prevention (overvoltage)

Cause:
When the output voltage increases, the stall prevention function is activated. The regeneration avoidance function may be activated due to excessive regenerative power.


Remedy:

  • Check for sudden speed reduction.

  • Check if the regeneration avoidance function (Pr.882, Pr.883, etc.) is enabled.

  • Increase the deceleration time using Pr.8 Deceleration time.


TH
Electronic thermal O/L relay pre-alarm

Cause:
Appears if the cumulative value of the electronic thermal O/L relay reaches 85% of the preset level of Pr.9.


Remedy:

  • Check for large load or sudden acceleration.

  • Check that the Pr.9 setting is appropriate.

  • Reduce the load and frequency of operation.

  • Set an appropriate value in Pr.9.


PS
PU stop

Cause:
The motor is stopped using STOP/RESET under a mode other than PU operation mode (if Pr.75 is set to allow this), or by the emergency stop function.


Remedy:

  • Check if the motor is stopped by pressing STOP/RESET on the operation panel.

  • Turn OFF the start signal and switch the operation mode to the PU operation mode to reset.


UV
Undervoltage

Cause:
Power supply voltage of the inverter decreased to about 115 VAC (200V class) or 230 VAC (400V class) or below.


Remedy:

  • Check that the power supply voltage is appropriate.

  • Check if a high-capacity motor is driven.

  • Investigate the devices on the power supply line such as the power supply itself.


IH
Inrush current limit resistor overheat

Cause:
The inrush current limit resistor (PTC thermistor) is overheated due to frequent power ON/OFF cycling.


Remedy:

  • Check that power ON/OFF is not repeated frequently.

  • Check that the inrush current limit circuit is not damaged.

  • Configure a circuit where frequent power ON/OFF is not repeated.

  • If problem persists, contact your sales representative.


ED

Emergency drive in operation

Cause:

Emergency drive operation is performed by turning ON the X84 signal.



Remedy:

The display is cleared when the emergency drive operation ends.
E.OC1

Overcurrent trip during acceleration

Cause:

  • Check for sudden speed acceleration.

  • Check if the downward acceleration time is too long in a lift application.

  • Check for output short-circuit.

  • Check that the Pr.3 Base frequency setting is not 60 Hz when the motor rated frequency is 50 Hz.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.

  • Check that the regenerative driving is not performed frequently.


Remedy:

  • Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)

  • If “E.OC1” always appears at start, disconnect the motor once and restart the inverter. If it still appears, contact your sales representative.

  • Check the wiring to make sure that output short circuit does not occur.

  • Set 50 Hz in Pr.3 Base frequency.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.

  • Set the base voltage in Pr.19 Base frequency voltage.


E.OC2

Overcurrent trip during constant speed

Cause:

  • Check for sudden load change.

  • Check for output short-circuit.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.


Remedy:

  • Keep the load stable.

  • Check the wiring to make sure that output short circuit does not occur.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.


E.OC3

Overcurrent trip during deceleration or stop

Cause:

  • Check for sudden speed reduction.

  • Check for output short-circuit.

  • Check for too fast operation of the motor’s mechanical brake.

  • Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.


Remedy:

  • Set the deceleration time longer.

  • Check the wiring to make sure that output short circuit does not occur.

  • Check the mechanical brake operation.

  • Lower the stall prevention operation level. Activate the fast-response current limit operation.


E.OV1

Regenerative overvoltage trip during acceleration

Cause:

  • Check for too slow acceleration. (e.g. during downward acceleration in vertical lift load)

  • Check that the Pr.22 Stall prevention operation level is not set to the no load current or lower.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.


Remedy:

  • Set the acceleration time shorter.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Set a value larger than the no load current in Pr.22.


E.OV2

Regenerative overvoltage trip during constant speed

Cause:

  • Check for sudden load change.

  • Check that the Pr.22 Stall prevention operation level is not set to the no load current or lower.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.

  • Check that acceleration/deceleration time is not too short.


Remedy:

  • Keep the load stable.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Use a brake unit or the power regeneration common converter (FR-CV) as required.

  • Set a value larger than the no load current in Pr.22.

  • Set the acceleration/deceleration time longer.


E.OV3

Regenerative overvoltage trip during deceleration or stop

Cause:

  • Check for sudden speed reduction.

  • Check if the stall prevention operation is frequently activated in an application with a large load inertia.


Remedy:

  • Set the deceleration time longer. (Set the deceleration time which matches the moment of inertia of the load.)

  • Make the brake cycle longer.

  • Use the regeneration avoidance function (Pr.882, Pr.883, Pr.885, Pr.886).

  • Use the brake unit or power regeneration common converter (FR-CV) as required.

  • Enable the increased magnetic excitation deceleration.


E.THT

Inverter overload trip (electronic thermal O/L relay function)

Cause:

  • Check that acceleration/deceleration time is not too short.

  • Check that torque boost setting is not too large (small).

  • Check that load pattern selection setting is appropriate for the load pattern of the machine.

  • Check that the motor is not used under overload.


Remedy:

  • Set the acceleration/deceleration time longer.

  • Adjust the torque boost setting.

  • Set the load pattern selection setting according to the load pattern of the using machine.

  • Reduce the load.


E.THM

Motor overload trip (electronic thermal O/L relay function)

Cause:

  • Check if the motor is not used under overload.

  • Check that the setting of Pr.71 Applied motor for motor selection is correct.

  • Check that the stall prevention operation setting is correct.


Remedy:

  • Reduce the load.

  • For a constant-torque motor, set the constant-torque motor in Pr.71 Applied motor.

  • Set the stall prevention operation level accordingly.


E.FIN

Heatsink overheat

Cause:

  • Check for too high surrounding air temperature.

  • Check for heat sink clogging.

  • Check that the cooling system is not stopped.


Remedy:

  • Set the surrounding air temperature to within the specifications.

  • Clean the heatsink.

  • If the problem still persists after taking the above measure, contact your sales representative.


E.UVT

Undervoltage

Cause:

  • Check if a high-capacity motor is driven.


Remedy:

  • Check the devices on the power supply line such as the power supply itself.

  • If the problem still persists after taking the above measure, contact your sales representative.


E.ILF

Input phase loss

Cause:

  • Check if a high-capacity motor is driven.

  • Check that phase-to-phase voltage of the three-phase power input is not largely unbalanced.


Remedy:

  • Wire the cables properly.

  • Check the Pr.872 setting.


E.OLT
Stall prevention stop

Cause: Output frequency has fallen to 1 Hz by stall prevention operation and remains for 3 seconds. Check if the motor is not used under overload.

Remedy:

  • Reduce the load.

  • Change the Pr.22 setting.

  • Check that stall prevention (overcurrent) warning (OLC) or stall prevention (overvoltage) warning (OLV) countermeasure is taken.


E.GF
Output side earth (ground) fault overcurrent

Cause: Earth (ground) fault overcurrent flows due to an earth fault on the inverter’s output side. Check for a ground fault in the motor and connection cable.

Remedy:

  • Remedy the earth (ground) fault portion.

  • Check the Pr.249 setting.


E.LF
Output phase loss

Cause: One of the three phases (U, V, W) on the inverter’s output side is lost. Check wiring and that motor capacity is not smaller than inverter.

Remedy:

  • Wire the cables properly.

  • Check the Pr.251 setting.


E.OHT
External thermal relay operation

Cause: External or internal thermal relay switches ON (contacts open). Check for motor overheating. Check Pr.178 to Pr.182 settings.

Remedy:

  • Reduce the load and operation duty.

  • Even if relay contacts reset automatically, the inverter will not restart unless reset manually.


E.PE6
Internal storage device fault

Cause: Writing data failed due to power-OFF or data fault during parameter operations. Check if power was turned OFF during operations.

Remedy:

  • Check power supply and devices.

  • If due to power-OFF: Check Pr.890. If “7” or smaller, perform All parameter clear and reset.

  • If due to other reasons: Contact sales representative.


E.PE / E.PE2
Parameter storage device fault (Corrupt Memory)

Cause: A fault occurred in the stored parameters (EEPROM failure). Check for too many parameter write times.

Remedy:

  • Contact your sales representative.

  • If writing frequently for communication, set “1” in Pr.342 to enable RAM write.


E.PUE
PU disconnection

Cause: Communication between inverter and PU is suspended/disconnected. Check that PU is connected properly and Check Pr.75.

Remedy:

  • Connect the PU securely.


E.RET
Retry count excess

Cause: Operation cannot be resumed properly within the number of retries set in Pr.67. Find the cause of the fault occurrence.

Remedy:

  • Eliminate the cause of the fault preceding this fault indication.


E.CPU / E.5
CPU fault

Cause: Communication fault of the built-in CPU. Check for devices producing excess electrical noises around the inverter.

Remedy:

  • Take measures against noises if there are devices producing excess electrical noises.

  • Contact your sales representative.


E.CDO
Abnormal output current detection

Cause: Output current exceeds Pr.150 level. Check settings of Pr.150, Pr.151, and Pr.167.

Remedy:

  • Adjust the parameter settings (Pr.150, Pr.151, Pr.167) or load conditions.


E.IOH
Inrush current limit circuit fault

Cause: Resistor of inrush current limit circuit is overheated or faulty. Check that frequent power ON/OFF is not repeated.

Remedy:

  • Configure a circuit where frequent power ON/OFF is not repeated.

  • If problem persists, contact sales representative.


E.ICF
Input monitoring fault

Cause: Input signal does not turn ON/OFF within time set in Pr.242. Check for input signal loss or device failure.

Remedy:

  • Set the Pr.242 setting larger.

  • Check connection of input devices.


E.LCI
4 mA input fault

Cause: Analog input current is 2 mA or less. Check for break in wiring or Pr.778 setting.

Remedy:

  • Check the wiring for the analog current input.

  • Set the Pr.778 setting larger.


E.E10
Inverter output fault

Cause: Fault on inverter output side while Pr.631 is active. Check for ground fault in motor/cable.

Remedy:

  • Remedy the earth (ground) fault portion.

  • Check the Pr.631 setting.


E.0
No fault history

Cause: Appears when no fault records are stored.

Remedy:

  • None required (System Normal).