F4
AC Undervoltage: There is an undervoltage on the power circuit (can only occur while the drive is active). |
Cause:
- Par 481 [UnderVolt Thresh] is set incorrectly.
- The incoming voltage to the power terminals is too low (missing phase, poor connection).
- The line fuses have tripped.
- AC input voltage dips or high disturbance.
- Fuse on overvoltage clipping board blown (frame D only).
Remedy:
- Set Par 481 [UnderVolt Thresh] correctly and reset drive via Par 1347.
- Verify AC input power level.
- Check all cable connections (contactor, choke, filter).
- Remove power, eliminate voltage dips, replace blown fuses.
- Check/replace fuses on overvoltage clipping board.
|
F5
Arm Overvoltage: There is an overvoltage on the armature circuit (125% of Par 175). |
Cause:
- Par 175 [Rated Motor Volt] is set too low.
- Drive not configured for field weakening, but motor reaches set speed only in field weakening mode.
Remedy:
- Set Par 175 [Rated Motor Volt] correctly.
- Check the value of Par 469 [Field Mode Sel] and set accordingly.
|
F2
Auxiliary Input: An auxiliary input interlock is open or a voltage (15…30V) is missing for digital input set to “Aux Fault”. |
Cause:
- Reference signal missing or interlock open.
Remedy:
- Check remote wiring.
- Note: Configure with Par 354 [Aux Inp Flt Cfg].
|
F64
Drive Overload: The rated drive current was exceeded by 150% for 1 minute. |
Cause:
- Excessive load on the drive.
Remedy:
- Reduce the drive current limits.
|
F132
Dsp Error: A non-resettable software error exists on the control board. |
Cause:
- Internal control board software failure.
Remedy:
- Cycle power to the drive.
- If the problem persists, replace the control board.
|
F100
EEPROM Error: Parameter values could not be saved or hardware config issue. |
Cause:
- Parameter values could not be saved.
- Control board replaced and DIP switch S15 set incorrectly.
- Major firmware revision upgrade (e.g., v2.xxx to v3.xxx).
Remedy:
- If control board is new, verify DIP switch S15 is set correctly.
- Reset the fault.
- If fault occurs again, cycle power to the drive.
- If problem persists, replace the control board.
|
F92
Encoder Error: An error was detected with the Encoder signal. |
Cause:
- Issues with encoder signal or configuration.
Remedy:
- Verify the encoder wiring.
- Verify encoder configuration in Par 652 and DIP switches S20/S21.
- Verify the encoder power supply.
|
F6
Fld Current Loss: The field current is too low (less than 50% of Par 468). |
Cause:
- Field current regulator is not enabled.
- Conductors in field circuit interrupted.
- Field fuses are currently open.
Remedy:
- Enable field current regulator via Par 497.
- Check motor field wiring and resistance.
- Check field fuses and replace as necessary.
|
F95
Fwd End Limit: An end limit for the forward direction has been reached. |
Cause:
- Assigned contacts open due to limit reach.
Remedy:
- If digital limits are in use, verify digital inputs are connected to normally closed contacts.
|
F97
Fwd Over Travel: A forward direction over travel signal has occurred. |
Cause:
- Digital input triggered for over travel.
Remedy:
- Verify digital input assignments (Pars 133…144).
|
F130
Hardware Fault: A non-resettable hardware error has occurred. |
Cause:
- Internal hardware failure.
Remedy:
- Cycle power to the drive.
- If the problem persists, replace the control board.
|
F8
Heatsink OvrTemp: The heatsink temperature is too high. |
Cause:
- Surrounding air temperature is too high.
- Drive cooling fans have failed (drives > 110 A).
- Fan fuses have failed.
- The heatsink is dirty.
Remedy:
- Lower the surrounding air temperature.
- Check fan fuses and fans; replace if necessary.
- Clean the heatsink.
|
F131
Interrupt Error: A non-resettable software error in the main application. |
Cause:
- Software execution error.
Remedy:
- Report this error to Rockwell Automation Technical Support.
|
F37
Inverting Fault: A digital input configured as “Invert Flt” has been removed. |
Cause:
Remedy:
- Check the status of the inverting fault device connected to the digital input.
|
F10
Main Contactor: Main or Dynamic Brake contactor failed to open/close in time. |
Cause:
- Contactor mechanical failure or timing issue (960ms).
- Digital input/output wiring issue.
- Wiring to digital input for contactor has opened.
Remedy:
- Check all contactor wiring and drive jumpers. Repair/replace contactor.
- Check digital input/relay output 1 wiring and configuration.
|
F7
Motor Overload: The selected motor overload current level has been exceeded. |
Cause:
- Load exceeds limits based on Par 376 [MtrOvrld Type].
Remedy:
- Reduce the motor load, current limits, and/or ramp times.
|
F16
Motor Over Temp: Motor exceeded temperature rating (via thermistor). |
Cause:
- No thermistor/resistor between terminals 78 and 79.
- Broken cable to thermistor.
- Load cycle too extreme.
- High surrounding temperature.
- Fan failure (external or internal effect too low).
Remedy:
- Check thermistor connections and cables.
- Reduce the load.
- Reduce surrounding air temperature.
- Replace motor fan or fit external fan.
|
F0
No Fault / Info: Information only or HIM display issue. |
Cause:
- If on HIM: SA-SB terminal on frame B/C incorrectly configured or control power issue.
Remedy:
- Informational only.
- For Frame B/C: Verify terminal SA-SB configuration for control circuit input power.
|
F89
Open SCR: An open SCR fault condition has been detected. |
Cause:
- Open SCR detected during diagnostic test.
Remedy:
- Verify correct values in Pars 217 and 218.
- Replace the failed SCR devices.
|
F13
Overcurrent: An overcurrent occurred in the motor circuit. |
Cause:
- Short-circuit or ground fault at output.
- Current regulator not properly fine-tuned.
- Par 584 [OverCurrent Thr] value too low.
Remedy:
- Verify armature circuit wiring.
- Tune the Current Regulator (see manual).
- Increase the value of Par 584 accordingly.
|
F25
Overspeed: Speed feedback indicated speed > Par 585 [Overspeed Val]. |
Cause:
- Excessive load or overhauling conditions.
- Threshold too low.
Remedy:
- Remove excessive load or overhauling conditions.
- Increase value of Par 585 [Overspeed Val].
|
F48
Params Defaulted: User parameters reset to default values. |
Cause:
- System reset or corruption.
Remedy:
|
F71…75
Port 1…5 Adapter: The communication card has a fault. |
Cause:
- Communication card error.
Remedy:
- Check the DPI device event queue and fault information for the device.
|
F81…85
Port 1…5 DPI Loss: The DPI port stopped communicating. |
Cause:
- Disconnected cable or adapter.
- Intentional disconnect without masking bit.
Remedy:
- Check HIM connection and wiring.
- Replace wiring, port expander, or control board if required.
- If intentional, set appropriate bit in Par 591 [Logic Mask] to “0”.
|
F3
Power Failure: Fault in 24V control board supply or incoming voltage low. |
Cause:
- Problem with external I/O wiring (short circuit).
- Blown fuses (F1, F2, F3) on switching power supply or pulse transformer.
- AC input voltage too low or poor connections.
Remedy:
- Check I/O wiring for shorts/shielding issues.
- Check and replace fuses F1, F2, F3 as necessary.
- Verify AC input power level and connections.
|
F93
Resolver Error: An error was detected with the resolver signal. |
Cause:
- Signal loss or configuration error.
Remedy:
- Verify resolver wiring.
- Verify resolver configuration in Pars 423, 424, and 425.
- Verify resolver power supply.
|
F96
Rev End Limit: Reverse end limit reached. |
Cause:
- Contacts open due to limit reach.
Remedy:
- If digital limits used, verify digital inputs connected to normally closed contacts.
|
F98
Rev Over Travel: Reverse direction over travel signal occurred. |
Cause:
Remedy:
- Verify digital input assignments.
|
F90
Shorted SCR: Shorted SCR fault condition detected. |
Cause:
Remedy:
- Replace failed SCR device or devices.
|
F91
Spd Fdbk Loss: Speed feedback lost or inconsistent with armature voltage. |
Cause:
- Feedback signal conductors interrupted.
- Encoder/resolver channels missing (no power).
- Motor voltage incorrect.
- Ramp rate too fast for load.
- Field Weakening set incorrectly.
- Encoder/resolver config incorrect.
Remedy:
- Check feedback device wiring and power supply.
- Verify Par 175 and tune motor.
- Reduce load or ramp rate.
- Verify Par 456 [Fld Weaken Ratio].
- Verify encoder/resolver DIP switches and params (Par 652, 426).
|
F20
SSC Error: Valid fiber packet not received within time period. |
Cause:
- Fiber-optic connection issue.
- Damaged cables.
Remedy:
- Verify fiber-optic connections are secure.
- Check cables for damage; replace if necessary.
- If persists, replace Fiber-optic Interface circuit board.
|
F62
STune Aborted: Speed regulator auto tuning stopped manually. |
Cause:
- User stopped the process.
Remedy:
|
F59
STune CurLimit: Auto tuning current limit too high or speed zero levels high. |
Cause:
- Par 1048 [Autotune Cur Lim] too high.
- Par 107/108 set too high.
Remedy:
- Decrease value of Par 1048 and repeat tune.
- Set Pars 107 and 108 to default values.
|
F60
STune FrictionLo: Friction value attained during tune is zero or too low. |
Cause:
- Control precision limit issue.
Remedy:
- Decrease value of Par 1048 [Autotune Cur Lim] and repeat.
|
F58
STune LoadHi: Loading torque too high at zero speed. |
Cause:
- Load torque too high.
- Par 107/108 set too high.
Remedy:
- Decrease load torque and repeat.
- Set Pars 107 and 108 to defaults.
|
F56
STune Overspeed: Measured motor speed too high during tuning. |
Cause:
- Current limit excessive for load.
Remedy:
- Decrease value of Par 1048 [Autotune Cur Lim] and repeat.
|
F57
STune Stalled: Drive stalled during speed regulator tuning. |
Cause:
- Current limit too low to move motor.
Remedy:
- Increase value of Par 1048 [Autotune Cur Lim] and repeat.
|
F61
STune Timeout: Auto tuning did not complete within 15 minutes. |
Cause:
- Par 1048 too low.
- Max speed parameters (Par 45, 3, 4) set incorrectly for test.
Remedy:
- Verify value of Par 1048.
- Set max speed parameters appropriately (must reach 33%).
- Repeat tuning procedure.
|
F70
Sustained Curr: Motor CEMF too high or current bridge change failed. |
Cause:
- Motor CEMF too high or line voltage too low.
- Current bridge change command not completed within 1 second.
Remedy:
- Check line voltage and frequency.
- Check motor brushes and connections.
- Check main and DB contactor connections.
- Verify no overhauling loads present.
|
F94
TorqPrv Spd Band: Speed deviation exceeded level in Par 1105. |
Cause:
- Speed loop tuning not correct.
- Drive operating under current limit.
- Accel/Decel rates too fast.
- Brake not releasing.
- Motor field not reaching rated value.
- Drive undersized.
Remedy:
- Increase Par 434 or Par 433.
- Raise current limit (Par 7).
- Reduce accel/decel rates.
- Check brake wiring/operation.
- Check motor field wiring/config.
- Reduce the load.
|
F99
Travel Lim Cflct: Travel limits are in conflict (Forward and Reverse active simultaneously). |
Cause:
- Digital limits: Both inputs off simultaneously (e.g., loss of common power).
- Software limits: Bits in Par 1101 set incorrectly simultaneously.
Remedy:
- Verify wiring of digital limit switches (normally closed).
- Check state of fwd/rev travel limit bits in Par 1101.
|
Arm Overvoltage Type 1 |
Cause: There is a possible overvoltage on the armature circuit or Par 175 [Rated Motor Volt] is set too low for the application.
Remedy: See the “Arm Overvoltage” fault description in the manual (page 222) for more information.
|
Auxiliary Input Type 1 |
Cause: An auxiliary input interlock is open or a voltage (15…30V) or reference signal is missing for the digital input set to 14 “Aux Fault”.
Remedy: See the “Auxiliary Input” fault description in the manual (page 222) for more information.
|
BipolarCflct Type 2 |
Cause: Par 1322 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of these digital input functions is configured: “Fwd/Reverse,” “Run Forward,” “Run Reverse,” “Jog Forward,” “Jog Reverse,” “Rev Dec Limit,” or “Rev End Limit.”
Remedy: Check parameter configurations and ensure digital input functions match the Direction Mode setting.
|
BrakeSlipped Type 1 & 2 |
Cause: The encoder movement has exceeded the level in Par 1110 [Brk Slip Count] after the brake was set.
- Type 1: The brake slip maneuver is controlling the drive (drive is active).
- Type 2: The brake slip maneuver is finished (drive is stopped).
Remedy: Cycle power to the drive to reset.
|
CntactrCflct Type 2 |
Cause: Contactor input functions are in conflict.
- When [ContactorControl] is “None”, relay outputs/digital inputs cannot be set to “Contactor” or “ContactorDB”.
- When [ContactorControl] is “AC Cntcr” or “DC Cntcr”, one relay output and one digital input must be set to “Contactor”.
- When [ContactorControl] is “AC Cntcr+DB” or “DC Cntcr+DB”, relays and inputs must be set to “Contactor” and “ContactorDB” respectively.
Remedy: Program the parameter selections so that they match the relay output and/or digital input terminal block wiring correctly.
|
DigInCflctA Type 2 |
Cause: Digital input functions are in conflict. Combinations of the following settings cause an alarm:
- Acc2/Dec2 vs Accel 2, Decel 2
- Jog 1/2 vs Jog Fwd, Jog Rev
- Fwd/Rev vs Jog Fwd, Jog Rev
Remedy: Check digital input assignments and remove conflicting combinations.
|
DigInCflctB Type 2 |
Cause: One of these digital input conflicts exists:
- A digital Start input has been configured without a Stop input.
- None of the digital inputs are configured for “Enable”.
- Other digital input functions are in conflict (e.g., Run vs Run Fwd/Rev, Jog vs Run).
Remedy: Configure a Stop input, ensure Enable is configured, and resolve function conflicts.
|
DigInCflctC Type 2 |
Cause: Multiple physical inputs have been configured to the same input function. Duplicate configurations are not allowed for:
- Forward/Reverse, Run Reverse, Run Forward
- Jog Forward, Jog Reverse, Speed Select (1, 2, 3)
- Acc2 / Dec2, Accel 2, Decel 2, Run
Remedy: Remove duplicate input configurations.
|
FB Cfg Cflct Type 2 |
Cause: Feedback configuration conflict has occurred:
- [Fdbk Device Type] is not “Armature” but [Spd Loss Flt Cfg] is “Alarm” and [SpdReg FB Bypass] is “Disabled”.
- [Fdbk Device Type] is “Resolver” but other parameters are selecting a resolver signal incorrectly.
- [Fdbk Device Type] is “Encoder” but other parameters are selecting an encoder signal incorrectly.
Remedy: Correct the [Fdbk Device Type] or the associated source selection parameters (Pars 429, 430, 786, 1021, 1204, 1284).
|
FldCfg Cflct Type 2 |
Cause: The selected operating mode of the field controller is in conflict with another setting, or a permanent magnet motor is incorrectly configured.
- Conflict between Field Mode Sel (Weakened/External) and Feedback Device (Armature).
- Conflict between Field Mode Sel and Speed Loss Fault Config.
- Conflict between Field Mode Sel (Base Speed) and Field Reg Enable (Disabled).
- Conflict between Field Mode Sel and Force Min Field settings.
Remedy: Review parameters 469, 414, 478, 497, 498, and Digital Inx Sel for consistency.
|
Fld Current Loss Type 1 |
Cause: The field current is too low.
Remedy: See the “Fld Current Loss” fault description in the manual (page 222) for more information.
|
Motor Overload Type 1 |
Cause: The selected motor overload current level has been exceeded.
Remedy: See the “Motor Overload” fault description in the manual (page 223) for more information.
|
Motor Over Temp Type 1 |
Cause: The motor has exceeded its temperature rating (as signaled by the thermistor connected to drive terminals 78 and 79).
Remedy: See the “Motor Over Temp” fault description in the manual (page 223) for more information.
|
Ref Cflct Type 2 |
Cause: Reference Conflict:
- Multiple drive reference inputs are set to the same value (Pars 70, 75, 80, 1323-1327, 1021, 430, 1375).
- Both [Resolver Pos Sel] and [Resolver Spd Sel] are non-zero.
- Multiple source parameters (PID Source, Line Spd Source, Ref Spd Source) contain the same value.
Remedy: Change the parameter selections so that unique sources are defined for the reference inputs.
|
Open SCR Type 1 |
Cause: An open SCR condition has been detected (Par 213 bit 0 set and Par 216 set to “Alarm”).
Remedy: See the “Open SCR” fault description in the manual (page 89) for more information.
|
Spd Fdbk Err Type 1 |
Cause: With Par 478 [Spd Loss Flt Cfg] set to 1 “Alarm”, an error condition associated with the selected speed feedback device (analog tachometer, encoder, or resolver) was detected.
Remedy: Check the speed feedback device connections and operation.
|
Spd Fdbk Loss Type 1 |
Cause: Par 478 set to “Alarm”. The speed feedback device indicates a value less than 5% of Max Feedback Spd, but the measured armature voltage is greater than the value of Par 455 [Spd FB Loss Lvl].
Remedy: See the “Spd Fdbk Loss” fault description in the manual (page 225) for more information.
|
Start At PowerUp Type 1 |
Cause: Par 1344 [Start At Powerup] is enabled.
Remedy: The drive can start at any time after power-up and the specified delay (Par 1345). Disable Par 1344 if this behavior is not desired.
|
Torq Prov Cflct Type 2 |
Cause: Par 1100 [Torq Prove Cfg] is enabled, but a conflict exists:
- Operating non-regenerative drive (negative current required).
- Direction Mode set to “Rev Disable”.
- Feedback Device set to “Armature Voltage” or “DC Tach” (with Encoderless=0).
- Speed Loop or Field configurations incorrect (e.g., SpdReg FB Bypass enabled).
- Digital Input “Lift Stop” missing or TP Enable bit 0 is 0.
- Alpha Test On or TstGen Output connected.
Remedy: Check Par 1100, 1322, 414, 458, 457, 166, 58, 467, 498, 245, and 241 settings. Ensure relay outputs are not defined as “TP Brake Cmd” if not intended.
|
TP Encls Config Type 2 |
Cause: The drive has been configured to enable Encoderless TorqProve, but an application conflict exists.
Remedy: You must read and understand the “Attention” on page 309 relating to the use of TorqProve with no encoder before you can continue.
|