Hitachi WL200 Drive

Fault Code and MeaningCause and Remedy
E01

Over-current event while at constant speed

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. Setting in dual-voltage motor is wrong.



Remedy:

Check for short circuits, unlock the motor shaft, or reduce load. Press Stop/Reset key.
E02

Over-current event during deceleration

Cause:

Excessive current detected during deceleration. (Similar conditions to E01).



Remedy:

Check deceleration time parameters. Press Stop/Reset key.
E03

Over-current event during acceleration

Cause:

Excessive current detected during acceleration. (Similar conditions to E01).



Remedy:

Check acceleration time parameters. Press Stop/Reset key.
E04

Over-current event during other conditions

Cause:

Excessive current detected during conditions other than constant speed, accel, or decel.



Remedy:

Check motor and load conditions. Press Stop/Reset key.
E05

Overload protection

Cause:

When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.



Remedy:

Reduce motor load. Press Stop/Reset key.
E06

Braking resistor overload protection

Cause:

When the BRD operation rate exceeds the setting of “b090”, this protective function shuts off the inverter output and displays the error code.



Remedy:

Check braking usage and “b090” setting. Press Stop/Reset key.
E07

Over-voltage protection

Cause:

When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.



Remedy:

Check input voltage and deceleration times. Press Stop/Reset key.
E08

EEPROM error

Cause:

When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Reset by cycling power. If error persists, perform initialization.
E09

Under-voltage error

Cause:

A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque.



Remedy:

Check input power source. Press Stop/Reset key.
E10

Current detection error

Cause:

If an error occurs in the internal current detection system, the inverter will shut off its output and display the error code.



Remedy:

Press Stop/Reset key. If error persists, contact support.
E11

CPU error

Cause:

A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.



Remedy:

Press Stop/Reset key.
E12

External trip

Cause:

A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.



Remedy:

Remove the external trip signal. Press Stop/Reset key.
E13

USP (Unattended Start Protection)

Cause:

When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present.



Remedy:

Clear the Run signal. Press Stop/Reset key.
E14

Ground fault

Cause:

The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Check motor/cable for ground faults. Reset by cycling power.
E15

Input over-voltage

Cause:

The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state.



Remedy:

Check input voltage. After the fault is cleared, the inverter can enter Run Mode again.
E19

Inverter thermal detection system error

Cause:

When the thermal sensor in the inverter module is not connected.



Remedy:

Press Stop/Reset key.
E21

Inverter thermal trip

Cause:

When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips.



Remedy:

Allow inverter to cool. Check cooling fans/ventilation. Press Stop/Reset key.
E22

CPU communication error

Cause:

When communication between two CPU fails, inverter trips and displays the error code.



Remedy:

Press Stop/Reset key.
E25

Main circuit error

Cause:

The inverter will trip if the power supply establishment is not recognized because of a malfunction due to noise or damage to the main circuit element.



Remedy:

Check power supply and for electrical noise. Press Stop/Reset key.
E30

Driver error

Cause:

An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Reset by cycling power.
E35

Thermistor

Cause:

When a thermistor is connected to terminals [5] and [L] and the inverter has sensed the temperature is too high.



Remedy:

Check thermistor temperature. Press Stop/Reset key.
E36

Braking error

Cause:

When “01” has been specified for the Brake Control Enable (b120), the inverter will trip if it cannot receive the braking confirmation signal within the Brake Wait Time.



Remedy:

Check brake signal wiring and timing. Press Stop/Reset key.
E37

Safe Stop

Cause:

Safe stop signal is given.



Remedy:

Check Safe Stop input. Press Stop/Reset key.
E38

Low-speed overload protection

Cause:

If overload occurs during the motor operation at a very low speed, the inverter will detect the overload and shut off the inverter output.



Remedy:

Reduce load at low speeds. Press Stop/Reset key.
E40

Operator connection

Cause:

When the connection between inverter and operator keypad failed.



Remedy:

Check keypad connection. Press Stop/Reset key.
E41

Modbus communication error

Cause:

When “trip” is selected (C076=00) as a behavior in case of communication error, inverter trips when timeout happens.



Remedy:

Check Modbus communication lines. Press Stop/Reset key.
E43

EzSQ invalid instruction

Cause:

The program stored in inverter memory has been destroyed, or the PRG terminal was turned on without a program downloaded to the inverter.



Remedy:

Check or reload EzSQ program. Press Stop/Reset key.
E44

EzSQ nesting count error

Cause:

Subroutines, if-statement, or for-next loop are nested in more than eight layers.



Remedy:

Correct EzSQ program structure. Press Stop/Reset key.
E45

EzSQ instruction error

Cause:

Inverter found the command which cannot be executed.



Remedy:

Correct EzSQ program command. Press Stop/Reset key.
E50 to E59

EzSQ user trip (0 to 9)

Cause:

When user-defined trip happens, inverter trips and displays the error code.



Remedy:

Check user program logic. Press Stop/Reset key.
E60 to E69

Option error

Cause:

The inverter detects errors in the option board mounted in the optional slot. For details, refer to the instruction manual for the mounted option board.



Remedy:

Refer to Option Board manual. Press Stop/Reset key.
H001

Frequency upper limit warning

Cause:

Frequency upper limit (A061) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H002

Frequency lower limit warning

Cause:

Frequency lower limit (A062) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H005

Multi-speed freq warning

Cause:

Output Frequency setting (F001) or Multi-speed freq. 0 (A020) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H015

Frequency setting warning

Cause:

Output Frequency setting (F001) or Multi-speed freq. 0 (A020) > Frequency upper limit (A061).



Remedy:

Correct parameter settings.
H025

Frequency lower limit conflict

Cause:

Frequency lower limit (A062) > Output Frequency setting (F001) or Multi-speed freq. 0 (A020).



Remedy:

Correct parameter settings.
H031

Start frequency conflict

Cause:

Start frequency (A082) > Frequency upper limit (A061).



Remedy:

Correct parameter settings.
Rotating Display

Reset

Cause:

RS input is ON or STOP/RESET key is pressed.



Remedy:

Release key or RS input.
—-

Under-voltage (Indication)

Cause:

If input voltage is under the allowed level, inverter shuts off output and waits with this indication.



Remedy:

Restore input voltage to allowed level.
0000

Waiting to restart

Cause:

This indication is displayed after tripping before restarting.



Remedy:

Wait for restart.
Blinking

Communication error

Cause:

Communication between inverter and digital operator fails.



Remedy:

Check connection between inverter and operator.