INVT GD20-UL Series Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUt1 [1] Inverter unit U phase protection | Cause: The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper. Remedy:
|
| OUt2 [2] Inverter unit V phase protection | Cause: The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper. Remedy:
|
| OUt3 [3] Inverter unit W phase protection | Cause: The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper. Remedy:
|
| OC1 [4] Overcurrent during acceleration | Cause: The acceleration is too fast; Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference; Overvoltage stall protection not open. Remedy:
|
| OC2 [5] Overcurrent during deceleration | Cause: The deceleration is too fast; Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference; Overvoltage stall protection not open. Remedy:
|
| OC3 [6] Overcurrent during constant speed running | Cause: Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference. Remedy:
|
| OV1 [7] Overvoltage during acceleration | Cause: Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open. Remedy:
|
| OV2 [8] Overvoltage during deceleration | Cause: Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open. Remedy:
|
| OV3 [9] Overvoltage during constant speed running | Cause: Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open. Remedy:
|
| UV [10] Bus undervoltage | Cause: The voltage of the power supply is too low; The overvoltage stall protection is not open. Remedy:
|
| OL1 [11] Motor overload | Cause: Power supply voltage too low; Motor rated current setting incorrect; Motor stall or load transients too strong. Remedy:
|
| OL2 [12] VFD overload | Cause: Acceleration too fast; Resetting rotating motor; Power supply voltage too low; Load too heavy; Close loop vector control reverse direction/long low-speed operation. Remedy:
|
| SPI [13] Phase loss on input side | Cause: Phase loss or fluctuation of input R,S,T. Remedy:
|
| SPO [14] Phase loss on output side | Cause: U,V,W phase loss input (or serious asymmetrical three phase of the load). Remedy:
|
| OH1 [15] Rectifier module overheat | Cause: Air duct jam or fan damage; Ambient temperature is too high; The time of overload running is too long. Remedy:
|
| OH2 [16] Inverter module overheat | Cause: Air duct jam or fan damage; Ambient temperature is too high; The time of overload running is too long. Remedy:
|
| EF [17] External fault | Cause: SI external fault input terminals action. Remedy:
|
| CE [18] 485 communication fault | Cause: Baud rate setting incorrect; Fault in communication wiring; Communication address wrong; Strong interference. Remedy:
|
| ItE [19] Current detection fault | Cause: Control panel connector poor contact; Exception on the magnifying circuit. Remedy:
|
| tE [20] Motor autotuning fault | Cause: Motor capacity not compatible with VFD; Rated parameter of motor not set correctly; Offset parameters huge; Autotune overtime. Remedy:
|
| EEP [21] EEPROM operation fault | Cause: Error of controlling the write and read of parameters; Damage to EEPROM. Remedy:
|
| PIDE [22] PID feedback offline fault | Cause: PID feedback offline; PID feedback source disappear. Remedy:
|
| bCE [23] Braking unit fault | Cause: Braking circuit fault or damage to braking pipes; External braking resistor not sufficient. Remedy:
|
| END [24] Running time reached | Cause: The actual running time of the VFD is above the internal setting running time. Remedy:
|
| OL3 [25] Electronic overload | Cause: The VFD will report overload pre-alarm according to the set value. Remedy:
|
| PCE [26] Keypad communication error | Cause: Keypad not in good connection or offline; Keypad cable too long or strong interference; Keypad/Main board circuit fault. Remedy:
|
| UPE [27] Parameter upload error | Cause: Keypad not in good connection or offline; Keypad cable too long or strong interference; Communication circuit fault. Remedy:
|
| DNE [28] Parameter download error | Cause: Keypad not in good connection or offline; Keypad cable too long/interference; Data storage error in keypad. Remedy:
|
| ETH1 [32] To-ground short-circuit fault 1 | Cause: Output of VFD is short circuited with ground; Fault in current detection circuit; Great difference between motor power setting and VFD power. Remedy:
|
| ETH2 [33] To-ground short-circuit fault 2 | Cause: Output of VFD is short circuited with ground; Fault in current detection circuit; Great difference between motor power setting and VFD power. Remedy:
|
| dEu [34] Speed deviation fault | Cause: Load is too heavy, or stall occurred. Remedy:
|
| STo [35] Mal-adjustment fault | Cause: Control parameters of synchronous motor are set improperly; Autotuning parameter inaccurate; VFD not connected to motor. Remedy:
|
| LL [36] Electronic underload fault | Cause: The VFD will report the underload pre-alarm according to the set value. Remedy:
|
| PoFF System power off | Cause: System power off or low DC voltage. Remedy:
|