INVT SPC Series Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OV1 Overvoltage during ACC | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OV2 Overvoltage during DEC | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OV3 Overvoltage during constant speed running | Cause: The input voltage is abnormal; There is large energy feedback; No braking components; Energy-consumption braking is not enabled. Remedy:
|
| OC1 Overcurrent during ACC | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| OC2 Overcurrent during DEC | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| OC3 Overcurrent during constant speed running | Cause: The acceleration or deceleration is too fast; The voltage of the grid is too low; The power of the inverter is too low; The load transients or is abnormal; There is to-ground short circuit or output phase loss; There is strong external interference; The overvoltage stall protection is not enabled. Remedy:
|
| UV Bus undervoltage fault | Cause: The voltage of the grid is too low; The overvoltage stall protection is not enabled. Remedy:
|
| OL1 Motor overload | Cause: The grid voltage is too low; The motor rated current is set incorrectly; The motor stall occurs or the load transient is too large. Remedy:
|
| OL2 Inverter overload | Cause: The ACC is too fast; The rotating motor is reset; The grid voltage is too low; The load is too heavy; The motor power is too small. Remedy:
|
| SPO Phase loss on output side | Cause: Phase loss output occurs to U, V, W (or the three phases of the load are seriously asymmetrical). Remedy:
|
| OH2 Inverter module overheat | Cause: Air duct jam or fan damage occurs; Ambient temperature is too high; The time of overload running is too long. Remedy:
|
| EF External fault | Cause: SI external faulty input terminal action. Remedy:
|
| CE RS485 communication fault | Cause: The baud rate setting is incorrect; A fault occurs to the communication wiring; The communication address is incorrect; There is strong interference to the communication. Remedy:
|
| ItE Current detection fault | Cause: The control board connector is in poor contact; Hall device is damaged; An exception occurs on the magnifying circuit. Remedy:
|
| tE Motor autotuning fault | Cause: The motor capacity does not match the inverter capacity; Motor parameters are not set correctly; The difference between the parameters obtained from autotuning and the standard ones is great; Autotuning timed out. Remedy:
|
| EEP EEPROM operation error | Cause: Error in reading or writing control parameters; The EEPROM is damaged. Remedy:
|
| END Running time reached | Cause: The actual running time of the inverter is longer than the internal set running time. Remedy:
|
| OL3 Electronic overload fault | Cause: The inverter reports overload pre-alarm according to the setting. Remedy:
|
| ETH1 To-ground short-circuit fault 1 | Cause: The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit. Remedy:
|
| ETH2 To-ground short-circuit fault 2 | Cause: The output of the inverter is short circuited to the ground; There is a fault in the current detection circuit. Remedy:
|
| dEu Speed deviation fault | Cause: The load is too heavy or stalled. Remedy:
|
| STo Mal-adjustment fault | Cause: SM control parameters are set incorrectly; Autotuned parameters are not accurate; The inverter is not connected to the motor. Remedy:
|
| LL Electronic underload fault | Cause: The inverter reports underload pre-alarm according to the setting. Remedy:
|
| A-LS Weak-light pre-alarm | Cause: The sunlight is weak or the PV module configuration is insufficient. Remedy:
|
| A-LL Underload pre-alarm | Cause: The pumping pool has no water. Remedy:
|
| A-tF Full-water pre-alarm | Cause: The pumping pool is full. Remedy:
|
| A-tL Empty-water pre-alarm | Cause: The pumping pool has no water. Remedy:
|