Nidec & Control Technique Unidrive HS30 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy | ||||||
|---|---|---|---|---|---|---|---|
| C.Acc NV Media Card Write fail | Cause: Unable to access the NV Media Card. Remedy:
|
||||||
| C.by NV Media Card busy | Cause: An attempt has been made to access a file on NV Media Card, but the NV Media Card is already being accessed by an option module. No data is transferred. |
||||||
| C.cPr NV Media Card file/data is different to the one in the drive | Cause: A C.cPr trip is initiated if the parameters on the NV Media Card are different to the drive. |
||||||
| C.d.E NV Media Card data location already contains data | Cause: Attempt has been made to store data on a NV Media Card in a data block which already contains data. |
||||||
| C.dAt NV Media Card data not found | Cause: Attempt has been made to access non-existent file or block on the NV Media Card. |
||||||
| C.Err NV Media Card data structure error | Cause: Attempt has been made to access the NV Media Card but an error has been detected in the data structure on the card. Remedy:
|
||||||
| C.FuL NV Media Card full | Cause: There is not enough space left on the card. |
||||||
| C.OPt Option modules installed are different between source drive and destination drive | Cause: The parameter data or default difference data is being transferred from the NV Media Card to the drive, but the option module category is different between the source and destination drives. |
||||||
| C.Pr NV Media Card data blocks are not compatible with the drive derivative | Cause: Drive Derivative is different between the source and target drives. Remedy:
|
||||||
| C.rdo NV Media Card has the Read Only bit set | Cause: Attempt has been made to modify a read-only NV Media Card or a read-only data block. |
||||||
| C.rtg Voltage and/or current rating of the source and destination drives are different | Cause: The current and / or voltage ratings are different between source and destination drives. |
||||||
| C.SL Option module file transfer has failed | Cause: The C.SL trip is initiated if the transfer of an option module file to or from a module failed because the option module does not respond correctly. |
||||||
| C.tyP NV Media Card parameter set not compatible with current drive mode | Cause: The drive mode in the data block on the NV Media Card is different from the current drive mode. |
||||||
| cL.A1 Analog input 1 current loss | Cause: Current loss was detected in current mode on Analog input 1 (Terminal 2). |
||||||
| CL.bt Trip initiated from the Control Word | Cause: Initiated by setting bit 12 on the control word when the control word is enabled. Remedy:
|
||||||
| Cur.c Current calibration range | Cause: Current calibration range error. |
||||||
| Cur.O Current feedback offset error | Cause: Current offset is too large to be trimmed. |
||||||
| d.Ch Drive parameters are being changed | Cause: A user action or a file system write is active that is changing the drive parameters and the drive has been commanded to enable. |
||||||
| dEr.E Derivative file error | Cause: Derivative file error. Remedy:
|
||||||
| dEr.I Derivative product image error | Cause: Derivative product image error. Remedy:
|
||||||
| dESt Two or more parameters are writing to the same destination parameter | Cause: The dESt trip indicates that destination output parameters of two or more logic functions within the drive are writing to the same parameter. |
||||||
| dr.CF Drive configuration | Cause: Drive configuration error. Remedy:
|
||||||
| EEF Default parameters have been loaded | Cause: The EEF trip indicates that default parameters have been loaded. The exact cause/reason of the trip can be identified from the sub-trip number. Remedy:
|
||||||
| Et An External trip is initiated | Cause: The cause of the trip can be identified from the sub trip number displayed after the trip string (e.g., Sub-trip 1 = External Trip). Remedy:
|
||||||
| FAn.F Fan fail | Cause: Indicates the fan or fan circuitry has failed. |
||||||
| Fi.Ch File changed | Cause: A file has been changed. Remedy:
|
||||||
| FI.In Firmware Incompatibility | Cause: The user firmware is incompatible with the power firmware. |
||||||
| HFxx trip Hardware faults | Cause: Internal drive hardware fault. Remedy:
|
||||||
| It.Ac Output current overload timed out (I²t) | Cause: The It.Ac trip indicates a motor thermal overload based on the output current and motor thermal time constant. The drive will trip on It.Ac when the accumulator gets to 100%. This can occur when there is excessive mechanical load. Remedy:
|
||||||
| It.br Braking resistor overload timed out (I²t) | Cause: Braking resistor overload has timed out. This can be caused by excessive braking resistor energy. |
||||||
| no.PS No power board | Cause: No communication between the power and control boards. |
||||||
| O.Ld1 Digital output overload | Cause: The total current drawn from 24 V user supply or from the digital output has exceeded the limit. |
||||||
| O.SPd Motor frequency has exceeded the over frequency threshold | Cause: Excessive motor speed (typically caused by mechanical load driving the motor). |
||||||
| Oh.br Braking IGBT over-temperature | Cause: Braking IGBT over-temperature. Detected by thermal model. |
||||||
| Oh.dc DC bus over temperature | Cause: DC bus component over temperature based on a software thermal model. |
||||||
| Oht.C Control stage over-temperature | Cause: Control stage over-temperature detected. |
||||||
| Oht.I Inverter over temperature based on thermal model | Cause: IGBT junction over-temperature has been detected based on a software thermal model. |
||||||
| Oht.P Power stage over temperature | Cause: This trip indicates that a power stage over-temperature has been detected. |
||||||
| OI.A1 Analog input 1 over-current | Cause: Current input on analog input 1 exceeds 24 mA. |
||||||
| OI.AC Instantaneous output over current detected | Cause: The instantaneous drive output current has exceeded the set limit. Remedy:
|
||||||
| OI.br Braking IGBT over current detected | Cause: Over current has been detected in braking IGBT or braking IGBT protection has been activated. Short circuit protection for the braking IGBT activated. Remedy:
|
||||||
| OI.SC Output phase short-circuit | Cause: Over-current detected on drive output when enabled. |
||||||
| OPt.d Option module does not acknowledge during drive mode changeover | Cause: Option module did not acknowledge notifying the drive that communications with the drive has been stopped during the drive mode changeover within the allocated time. |
||||||
| Out.P Output phase loss detected | Cause: Phase loss has been detected at the drive output. |
||||||
| OV DC bus voltage has exceeded the peak level or maximum continuous level | Cause: The OV trip indicates that the DC bus voltage has exceeded the maximum limit (exceeded for 15 seconds). Remedy:
|
||||||
| P.dAt Power system configuration data error | Cause: Power system configuration data error. Remedy:
|
||||||
| PAd Keypad has been removed | Cause: The PAd trip indicates that the drive is in keypad mode and the keypad has been disconnected from the drive. |
||||||
| Pb.bt Power board is in bootloader mode | Cause: Power board is in bootloader mode. |
||||||
| Pb.Er Communication has been lost / errors detected between power control | Cause: Communications loss between power and control. |
||||||
| Pb.HF Power board HF | Cause: Power processor hardware fault. Remedy:
|
||||||
| Pd.S Power down save error | Cause: Error has been detected in the power down save parameters saved in non-volatile memory. |
||||||
| PH.Lo Supply phase loss | Cause: The drive has detected an input phase loss or large supply imbalance. |
||||||
| PSU Internal power supply fault | Cause: One or more internal power supply rails are outside limits or overloaded. |
||||||
| r.ALL RAM allocation error | Cause: Option module derivative image has requested more parameter RAM than is allowed. |
||||||
| r.b.ht Hot rectifier/brake | Cause: Over-temperature detected on input rectifier or braking IGBT. |
||||||
| rS Measured resistance has exceeded the parameter range | Cause: The measured stator resistance during an autotune test has exceeded the maximum possible value of Stator Resistance. Remedy:
|
||||||
| SCL Control word watchdog has timed out | Cause: The control word has been enabled and has timed out. Remedy:
|
||||||
| SL.dF Option module in option slot 1 has changed | Cause: Option slot 1 on the drive is a different type to that installed when parameters were last saved on the drive. Remedy:
|
||||||
| SL.Er Option module in option slot 1 has detected a fault | Cause: Option module in option slot 1 on the drive has detected an error. Remedy:
|
||||||
| SL.HF Option module 1 hardware fault | Cause: Option slot 1 on the drive has indicated a hardware fault. Remedy:
|
||||||
| SL.nF Option module in option slot 1 has been removed | Cause: The option module in option slot 1 on the drive has been removed since the last power up. Remedy:
|
||||||
| SL.tO Option module watchdog function service error | Cause: The option module installed in Slot 1 has started the option watchdog function and then failed to service the watchdog correctly. Remedy:
|
||||||
| So.St Soft start relay failed to close, soft start monitor failed | Cause: Soft start relay in the drive failed to close or the soft start monitoring circuit has failed. Remedy:
|
||||||
| St.HF Hardware trip has occurred during last power down | Cause: Hardware trip (HF01 – HF19) has occurred and the drive has been power cycled. Remedy:
|
||||||
| Sto No Safe Torque Off board installed | Cause: Safe Torque Off board not installed correctly. Remedy:
|
||||||
| th Motor thermistor over-temperature | Cause: The motor thermistor connected to terminal 14 (digital input 5) on the control connections has indicated a motor over temperature. Remedy:
|
||||||
| th.br Brake resistor over temperature | Cause: The th.br trip is initiated if the hardware based braking resistor thermal monitoring is connected and the resistor overheats. Remedy:
|
||||||
| tH.Fb Internal thermistor has failed | Cause: Internal thermistor has failed. Remedy:
|
||||||
| thS Motor thermistor short circuit | Cause: The motor thermistor connected to terminal 14 (digital input 5) on the control connections, is short circuit or low impedance (<50 Ω). Remedy:
|
||||||
| tun.S Autotune test stopped before completion | Cause: The drive was prevented from completing an autotune test, because either the drive enable or the drive run signals were removed. Remedy:
|
||||||
| tun.1 Autotune 1 | Cause: The drive has tripped during a rotating autotune. The cause of the trip can be identified from the sub-trip number.
Remedy:
|
||||||
| tun.3 Autotune 3 | Cause: RFC-A mode only. The drive has tripped during a rotating auto-tune or mechanical load measurement.
Remedy:
|
||||||
| U.OI User OI ac | Cause: The U.OI trip is initiated if the output current of the drive exceeds the trip level set by User Over Current Trip Level. Remedy:
|
||||||
| U.S User Save error / not completed | Cause: The U.S trip indicates that an error has been detected in the user save parameters saved in non-volatile memory. Remedy:
|
||||||
| UP.uS User Program trip | Cause: This trip can be initiated from within an onboard user program. Remedy:
|
||||||
| UPrG User Program | Cause: An error has been detected in the onboard user program image. Remedy:
|
||||||
| br.res Brake resistor overload | Cause: Braking Resistor Thermal Accumulator in the drive has reached 75.0 % of the value at which the drive will trip. Remedy:
|
||||||
| OV.Ld Motor Protection Accumulator warning | Cause: Motor Protection Accumulator in the drive has reached 75.0 % of the value at which the drive will trip and the load on the drive is >100 %. Remedy:
|
||||||
| d.OV.Ld Drive over temperature | Cause: Percentage Of Drive Thermal Trip Level in the drive is greater than 90 %. Remedy:
|
||||||
| tuning Autotune in progress | Cause: The autotune procedure has been initialized and an autotune in progress. Remedy:
|
||||||
| LS Limit switch active | Cause: Indicates that a limit switch is active and that is causing the motor to be stopped. Remedy:
|
||||||
| Lo.AC Low voltage mode | Cause: Drive is operating in Low Voltage Mode. Remedy:
|
||||||
| I.AC.Lt Current limit active | Cause: Drive output current has reached the limit. Remedy:
|
||||||
| 24.LoSt 24V backup not present | Cause: 24V backup supply is missing. Remedy:
|