Omron 3G3MX2-V1 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Overcurrent protection (Constant speed) | Cause: The inverter output current exceeded approximately 200% of the rated output current during constant speed operation. Possible causes include rapid load fluctuation, output short-circuit, or ground fault. Remedy:
|
| E02 Overcurrent protection (Deceleration) | Cause: The inverter output current exceeded approximately 200% of the rated output current during deceleration. Remedy:
|
| E03 Overcurrent protection (Acceleration) | Cause: The inverter output current exceeded approximately 200% of the rated output current during acceleration. Remedy:
|
| E04 Overcurrent protection (Others) | Cause: Overcurrent detected during other states (e.g., DC injection braking power too high). Remedy:
|
| E05 Overload protection | Cause: The internal electronic thermal function detected a motor overload. Remedy:
|
| E06 Braking resistor overload protection | Cause: The usage rate of the regenerative braking circuit exceeded the value set in b090. Remedy:
|
| E07 Overvoltage protection | Cause: Extremely high DC voltage between P/+2 and N/- (approx 400 VDC for 200-V class or 800 VDC for 400-V class). Caused by regenerative energy or increased incoming voltage. Remedy:
|
| E08 EEPROM error | Cause: Error in the built-in EEPROM due to external noise or abnormal temperature rise. Remedy:
|
| E09 Undervoltage | Cause: Incoming voltage dropped below specified level, causing DC voltage to drop (approx 173 VDC for 200-V class or 345 VDC for 400-V class). Remedy:
|
| E10 Current detector error | Cause: An error occurred in the current detector. Remedy:
|
| E11 CPU error | Cause: Malfunction or error in the built-in CPU. Remedy:
|
| E12 External trip | Cause: The multi-function input terminal allocated to the External trip (12: EXT) function turned ON. Remedy:
|
| E13 USP error | Cause: The power supply was turned on while the RUN signal was ON (only when USP function is selected). Remedy:
|
| E14 Grounding protection | Cause: A ground fault was detected between the inverter output unit and the motor when power was turned on. Remedy:
|
| E15 Incoming overvoltage protection | Cause: Incoming voltage remained in an overload state for 100 seconds (DC voltage approx 390 VDC for 200-V class or 780 VDC for 400-V class). Remedy:
|
| E21 Abnormal temperature | Cause: The temperature in the main circuit exceeded the specified value due to high ambient temperature or improper installation. Remedy:
|
| E22 CPU communication error | Cause: Malfunction or error in the built-in CPU during communications. Remedy:
|
| E25 Main circuit error | Cause: An error occurred in the main circuit board. Remedy:
|
| E30 Driver error | Cause: Momentary overcurrent (350% of rated), abnormal temperature in main element, or voltage drop detected by driver IC. Remedy:
|
| E35 Thermistor error | Cause: Abnormal temperature detected from external thermistor resistance value. Remedy:
|
| E36 Brake error | Cause: Inverter cannot recognize ON/OFF status of brake within Brake Error Detection Time (b124). Remedy:
|
| E37 Emergency shutoff | Cause: The safety input terminals GS1/GS2 are active. Remedy:
|
| E38 Overload protection (Low speed) | Cause: Overload detected in extremely low speed range (0.2 Hz or lower). Remedy:
|
| E40 Digital Operator connection failure | Cause: Error or disconnection communicating with external Digital Operator. Remedy:
|
| E41 Modbus communication error | Cause: Timeout occurs when Operation Selection on Communication Error (C076) is set to 00. Remedy:
|
| E43 – E45 DriveProgramming error | Cause: Program error in DriveProgramming. Remedy:
|
| E50 – E59 User trip | Cause: User trip initiated by DriveProgramming. Remedy:
|
| E60 – E68 Option error | Cause: Error received from the mounted option unit (e.g., EtherCAT or CompoNet fatal fault). Remedy:
|
| E69 Option timeout | Cause: Timeout in communications between the inverter and the option unit. Remedy:
|
| E80 Encoder disconnection | Cause: The encoder wiring is disconnected, or motor rotation speed detected is lower than Starting Frequency for the set duration. Remedy:
|
| E81 Overspeed | Cause: Motor rotation speed exceeds Maximum Frequency × Overspeed Error Detection Level. Remedy:
|
| E83 Position control range trip | Cause: Current position is out of the range set in Position Limit Setting (P072, P073) during simple position control. Remedy:
|