bLF Brake sequence |
Cause:
- Brake release current not reached.
- Brake engage frequency bEn = nO (not adjusted) when brake logic bLC is assigned.
Remedy:
- Check the drive/motor connection.
- Check the motor windings.
- Check the Ibr setting in the FUn- menu (see page 60).
- Carry out the recommended adjustment of bEn (see pages 59 and 60).
|
CrF Capacitor load circuit |
Cause:
Load relay control fault or charging resistor damaged.
Remedy:
|
EEF EEPROM fault |
Cause:
Internal memory fault.
Remedy:
- Check the environment (electromagnetic compatibility).
- Replace the drive.
|
InF Internal fault |
Cause:
- Short-circuit on the 10 V power supply.
- Internal fault.
Remedy:
- Check the circuits connected to the 10 V.
- Check the wiring of inputs AI1 and AI2 and the connection to the RJ45 connector.
- Check the environment (electromagnetic compatibility).
- Replace the drive.
|
OCF Overcurrent |
Cause:
- Incorrect parameters in the SEt- and drC- menus.
- Inertia or load too high.
- Mechanical blockage.
Remedy:
- Check the SEt- and drC- parameters.
- Check the size of the motor/drive/load.
- Check the state of the mechanism.
|
SCF Motor short-circuit |
Cause:
- Short-circuit or earthing at the drive output.
- Significant earth leakage current at the drive output when several motors are connected in parallel.
Remedy:
- Check the cables connecting the drive to the motor, and the motor insulation.
- Reduce the switching frequency.
- Connect chokes in series with the motor.
|
SOF Overspeed |
Cause:
- Instability.
- Driving load too high.
Remedy:
- Check the motor, gain and stability parameters.
- Add a braking resistor.
- Check the size of the motor/drive/load.
|
tnF Auto-tuning fault |
Cause:
- Special motor or motor whose power is not suitable for the drive.
- Motor not connected to the drive.
Remedy:
- Use the L or the P ratio (see Uft page 24).
- Check the presence of the motor during auto-tuning.
- If a downstream contactor is being used, close it during auto-tuning.
|
COF CAnopen fault |
Cause:
Interruption in communication on the CANopen bus.
Remedy:
- Check the communication bus.
- Please refer to the product-specific documentation.
|
EPF External fault |
Cause:
According to user.
Remedy:
|
LFF Loss of 4-20mA |
Cause:
Loss of the 4-20 mA reference on input AI3.
Remedy:
- Check the connection on input AI3.
|
ObF Overvoltage during deceleration |
Cause:
Braking too sudden or driving load.
Remedy:
- Increase the deceleration time.
- Install a braking resistor if necessary.
- Activate the brA function (page 44) if it is compatible with the application.
|
OHF Drive overheated |
Cause:
Drive temperature too high.
Remedy:
- Check the motor load, the drive ventilation and the environment. Wait for the drive to cool down before restarting.
|
OLF Motor overload |
Cause:
- Triggered by excessive motor current.
- Incorrect value of parameter rSC.
Remedy:
- Check the ItH setting (motor thermal protection) (page 20), check the motor load. Wait for the drive to cool down before restarting.
- Measure rSC again (page 24).
|
OPF Motor phase loss |
Cause:
- Loss of one phase at drive output.
- Downstream contactor open.
- Motor not connected or motor power too low.
- Instantaneous instability in the motor current.
Remedy:
- Check the connections from the drive to the motor.
- If a downstream contactor is being used, set OPL to OAC (FLt- menu page 67).
- Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active (OPL = YES). To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive, deactivate motor phase loss detection (OPL = no).
- Check and optimize the UFr, UnS and nCr parameters and perform auto-tuning with tUn.
|
OSF Overvoltage |
Cause:
- Line voltage too high.
- Disturbed line supply.
Remedy:
|
PHF Line phase failure |
Cause:
- Drive incorrectly supplied or a fuse blown.
- Failure of one phase.
- 3-phase ATV31 used on a single phase line supply.
- Unbalanced load.
- This protection only operates with the drive on load.
Remedy:
- Check the power connection and the fuses.
- Reset.
- Use a 3-phase line supply.
- Disable the fault by setting IPL = nO (FLt- menu page 67).
|
SLF Modbus fault |
Cause:
- Interruption in communication on the Modbus bus.
- Remote terminal enabled (LCC = YES page 40) and terminal disconnected.
Remedy:
- Check the communication bus.
- Please refer to the product-specific documentation.
- Check the link with the remote terminal.
|
CFF Configuration fault |
Cause:
The current configuration is inconsistent.
Remedy:
- Return to factory settings or call up the backup configuration, if it is valid. See the FCS parameter in the I-O-, drC-, CtL- or FUn- menu.
|
CFI Configuration fault via serial link |
Cause:
Invalid configuration. The configuration loaded in the drive via the serial link is inconsistent.
Remedy:
- Check the configuration loaded previously.
- Load a consistent configuration.
|
USF Undervoltage |
Cause:
- Line supply too low.
- Transient voltage dip.
- Damaged load resistor.
Remedy:
- Check the voltage and the voltage parameter. USF trip threshold:
- ATV31….M2: 160V
- ATV31….M3X: 160V
- ATV31….N4: 300V
- ATV31….S6X: 430V
- Replace the drive.
|