Schneider ATV600 Drives Fault Codes:
| Error Code and Meaning | Cause, Remedy and Clearing |
|---|---|
| NOA [No Warning stored] | No warning stored |
| FRF [Fallback Frequency] | Reaction on event: Fallback frequency |
| RLS [Speed Maintained] | Reaction on event: Speed maintained |
| STT [Type of stop] | Reaction on event: Stop following [Type of stop] STT without triggering an error |
| SRA [Ref Frequency Warning] | Frequency reference reached |
| LCA1 [Life Cycle Warn 1] | Life cycle warning 1 |
| LCA2 [Life Cycle Warn 2] | Life cycle warning 2 |
| DRYA [Dry Run Warning] | Dry run warning |
| LFA [Low Flow Warning] | Low flow warning |
| HFPA [High Flow Warning] | High flow warning |
| IPPA [InPress Warning] | Inlet pressure monitoring warning |
| OPLA [Low OutPres Warn] | Low outlet pressure warning |
| OPHA [High OutPres Warn] | High outlet pressure warning |
| PCPA [PumpCycle warning] | Pumpcycle monitoring warning |
| JAMA [Anti-Jam Warning] | Anti-jam warning |
| PLFA [Pump Low Flow] | Pump low flow warning |
| LPA [LowPres Warning] | Low pressure warning |
| FSA [Flow Limit activated] | Flow limitation function is active |
| PEE [PID error Warning] | PID error warning |
| PFA [PID Feedback Warn] | PID feedback warning |
| PFAH [PID High Fdbck Warn] | PID feedback high threshold reached |
| PFAL [PID Low Fdbck Warn] | PID feedback low threshold reached |
| PISH [Regulation Warning] | PID feedback monitoring warning |
| TP2A [AI2 Th Warning] | AI2 Thermal warning |
| TP3A [AI3 Th Warning] | AI3 Thermal warning |
| TP4A [AI4 Th Warning] | AI4 Thermal warning |
| TP5A [AI5 Th Warning] | AI5 Thermal warning |
| AP1 [AI1 4-20 Warning] | AI1 4-20 mA loss warning |
| AP2 [AI2 4-20 Warning] | AI2 4-20 mA loss warning |
| AP3 [AI3 4-20 Warning] | AI3 4-20 mA loss warning |
| AP4 [AI4 4-20 Warning] | AI4 4-20 mA loss warning |
| AP5 [AI5 4-20 Warning] | AI5 4-20 mA loss warning |
| THA [Device Therm Warn] | Drive overheating warning |
| TJA [IGBT Thermal Warning] | IGBT thermal state warning |
| FCTA [Fan Counter Warning] | Fan counter speed warning |
| FFDA [Fan Feedback Warning] | Fan feedback warning |
| EFA [Ext. Error Warning] | External error warning |
| USA [Undervoltage Warning] | Undervoltage warning |
| UPA [Preventive UnderV Active] | Controlled stop threshold is reached |
| ERN [Forced Run] | Drive in forced run |
| FTA [Mot Freq High Thd] | Motor frequency high threshold 1 reached |
| FTAL [Mot Freq Low Thd] | Motor frequency low threshold 1 reached |
| F2AL [Mot Freq Low Thd 2] | Motor frequency low threshold 2 reached |
| FLA [High Speed Reached] | High speed reached warning |
| RTAH [Ref Freq High Thd reached] | Reference frequency high threshold reached |
| RTAL [Ref Freq Low Thd reached] | Reference frequency low threshold reached |
| F2A [2nd Freq Thd Reached] | Motor frequency high threshold 2 reached |
| CTA [Current Thd Reached] | Motor current high threshold reached |
| CTAL [Low Current Reached] | Motor current low threshold reached |
| TTHA [High Torque Warning] | High torque threshold reached |
| TTLA [Low Torque Warning] | Low torque threshold reached |
| ULA [Process Undld Warning] | Process underload warning |
| OLA [Process Overload Warning] | Overload warning |
| TAD [Dev Thermal reached] | Drive thermal threshold reached |
| TSA [Motor Therm Thd reached] | Motor thermal threshold reached |
| PTHA [Power High Threshold] | Power high threshold reached |
| PTHL [Power Low Threshold] | Power low threshold reached |
| CAS1 [Cust Warning 1] | Customer warning 1 active |
| CAS2 [Cust Warning 2] | Customer warning 2 active |
| CAS3 [Cust Warning 3] | Customer warning 3 active |
| CAS4 [Cust Warning 4] | Customer warning 4 active |
| CAS5 [Cust Warning 5] | Customer warning 5 active |
| URA [AFE Mains Undervoltage] | AFE mains undervoltage |
| POWD [Power Cons Warning] | Power consumption warning |
| OPSA [Switch OutPres Warn] | Outlet pressure high switch warning |
| MPCA [MP Capacity Warn] | Multipump available capacity warning |
| MPLA [Lead Pump Warn] | Lead pump not available warning |
| LCHA [High Level Warning] | High level warning |
| LCLA [Low Level Warning] | Low level warning |
| LCWA [Level Switch Warning] | Level switch warning |
| IWA [MonitorCircuit A Warn] | Monitoring circuit A warning |
| IWB [MonitorCircuit B Warn] | Monitoring circuit B warning |
| IWC [MonitorCircuit C Warn] | Monitoring circuit C warning |
| IWD [MonitorCircuit D Warn] | Monitoring circuit D warning |
| CWA [CabinetCircuit A Warn] | Cabinet circuit A warning |
| CWB [CabinetCircuit B Warn] | Cabinet circuit B warning |
| CWC [CabinetCircuit C Warn] | Cabinet circuit C warning |
| TWA [MotorWinding A Warn] | Motor winding A warning |
| TWB [MotorWinding B Warn] | Motor winding B warning |
| TWC [MotorBearing A Warn] | Motor bearing A warning |
| TWD [MotorBearing B Warn] | Motor bearing B warning |
| CBW [Circuit Breaker Warn] | Circuit breaker warning |
| P24C [Cab I/O 24V Warn] | Cabinet I/O 24V missing warning |
| CLIM [AFE Motor Limitation] | AFE motor limitation |
| CLIG [AFE Generator Limitation] | AFE regen limitation |
| THSA [AFE Sensor thermal state] | AFE thermal state warning |
| THJA [AFE IGBT thermal state] | AFE IGBT thermal warning |
| FFCA [Cabinet Fan Fdbck Warn] | Cabinet fan feedback warning |
| FCCA [Cabinet Fan Counter Warn] | Cabinet fan counter warning |
| CHA [Cabinet Overheat Warn] | Cabinet overheat warning |
| CMIJ [CMI Jumper Warn] | CMI jumper warning |
| FCBA [AFE Fan Counter Warn] | AFE fan counter warning |
| FFBA [AFE Fan Fdbck Warn] | AFE fan feedback warning |
| MPDA [M/P Device Warn] | Multipump device warning |
| TS2A [Temp Sens AI2 Warn] | Temperature sensor AI2 warning (open circuit) |
| TS3A [Temp Sens AI3 Warn] | Temperature sensor AI3 warning (open circuit) |
| TS4A [Temp Sens AI4 Warn] | Temperature sensor AI4 warning (open circuit) |
| TS5A [Temp Sens AI5 Warn] | Temperature sensor AI5 warning (open circuit) |
| DCRW [DC Bus Ripple Warn] | DC Bus Ripple Warning |
| INWM [Ethernet Internal Warning] | Ethernet Internal Warning |
| VCA [VxCtrl Warning] | Vortex control warning |
| COPA [Cooling Pump Warn] | Cooling pump warning resulting from the detection of an error during pump operation or resulting from [Pump Diagnostics] CPT- (related to ATV9L0). |
| MOA [Module Overheat] | Module overheating warning resulting from the ambient temperature monitoring |
| AFFL [Fallback Channel] | Automatic fallback behavior activated after a fieldbus communication interruption |
| LKON [ON Lock Warning] | ON lock warning resulting from an external device not ready. |
| INFM [Internal Error 22] | Internal error 22 (Embedded Ethernet) |
| SLF1 [Modbus Com Inter.] | Modbus communication interruption warning |
| ACF1 [AFE DC-Caps Error] | Probable Cause: AFE DC-capacitors error: DC-capacitors overcurrent. – Low mains voltage for too long. – Mains voltage is on a low limit, the modulation rate of the AFE increases to help protect the DC link capacitors. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ACF2 [AFE Current Control Error] | Probable Cause: Mains voltage interruption. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ACF3 [AFE Line Filter Error] | Probable Cause: Mains voltage drops during generator operation. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| AFLF [Adv. Function Lock] | Probable Cause: [LevelCtrl Strategy] is set to [Energy Optimized] and a run order is given. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ASF [Angle error] | Probable Cause: This error is triggered during the phase-shift angle measurement if the motor phase is disconnected or if the motor inductance is too high. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CbF [Circuit Breaker Error] | Probable Cause: The DC bus voltage level is not correct compared to the circuit breaker logic control (start or stop pulse) after the configured timeout [Mains V. time out]. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| CFA [CabinetCircuit A Error] | Probable Cause: The monitoring function has detected an error. The digital input assigned to [CabinetCircuit A Assign] is active when the detected error duration is longer than [CabinetCircuit A Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CFb [CabinetCircuit B Error] | Probable Cause: The monitoring function has detected an error. The digital input assigned to [CabinetCircuit B Assign] is active when the detected error duration is longer than [CabinetCircuit B Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CFC [CabinetCircuit C Error] | Probable Cause: The monitoring function has detected an error. The digital input assigned to [CabinetCircuit C Assign] is active when the detected error duration is longer than [CabinetCircuit C Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CFF [Incorrect Configuration] | Probable Cause: – Option module changed or removed. – Control board replaced by a control board configured on a drive with a different rating. – The current configuration is inconsistent. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| CFI [Invalid Configuration] | Probable Cause: Invalid configuration. The configuration loaded in the drive via the commissioning tool or fieldbus is inconsistent. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| CFI2 [Conf Transfer Error] | Probable Cause: – The configuration transfer to the drive was not successful or interrupted. – The configuration loaded is not compatible with the drive. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| CFI3 [Pre-settings Transfer Error] | Probable Cause: The configuration transfer to the drive was not successful or interrupted. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| CHF [Cabinet Overheat Error] | Probable Cause: The cabinet thermal switch is at active state, the cabinet fan(s) has been switched on but there is no fan feedback. If the enclosure thermo switch opens in case of over temperature, this error is triggered. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CnF [Fieldbus Com Interrupt] | Probable Cause: Communication interruption on fieldbus module. Triggered when communication between fieldbus module and master (PLC) is interrupted. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CoF [CANopen Com Interrupt] | Probable Cause: Communication interruption on the CANopen fieldbus. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| COPF [Cooling Pump Error] | Probable Cause: Cooling pump is not working. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| CrF1 [Precharge Capacitor] | Probable Cause: – Charging circuit control detected error or charging resistor damaged. – Supply mains too low. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Extended Fault Reset] parameter after the cause has been removed. |
| CrF3 [AFE contactor fdbk error] | Probable Cause: AFE mains contactor feedback signal does not match with the internal AFE mains contactor command. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| CSF [Channel Switch Error] | Probable Cause: Switch to an invalid channel. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| DCrE [DC Bus Ripple Error] | Probable Cause: Persistent ripple observed on the DC bus or DC bus capacitors damaged. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| drYF [Dry Run Error] | Probable Cause: The dry run monitoring function has detected an error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| EEF1 [EEPROM Control] | Probable Cause: An error of the internal memory of the control block has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| EEF2 [EEPROM Power] | Probable Cause: An error of the internal memory of the power board has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| EPF1 [External Error] | Probable Cause: – Event triggered by an external device. – External error triggered via Embedded Ethernet. – Error caused by external circuit. – Ethernet configuration file is corrupted. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| EPF2 [Fieldbus Error] | Probable Cause: Event triggered by an external device, depending on user. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| EtHF [Embd Eth Com Interrupt] | Probable Cause: Communication interruption on the Ethernet IP ModbusTCP bus. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| FCF1 [Out Contact Closed Error] | Probable Cause: The output contactor remains closed although the opening conditions have been met. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| FCF2 [Out Contact Opened Error] | Probable Cause: The output contactor remains opened although the closing conditions have been met. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| Fdr1 [FDR 1 Error] | Probable Cause: – Embedded Ethernet FDR error. – Communication interruption between drive and PLC. – Configuration file incompatible/invalid. – Drive rating not consistent. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| Fdr2 [FDR 2 Error] | Probable Cause: – Ethernet fieldbus module FDR error. – Communication interruption between drive and PLC. – Configuration file incompatible/corrupted. – Drive rating not consistent. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| FFdF [Fan Feedback Error] | Probable Cause: Fan speed too low. [Fan Feedback Warning] has been active for a time longer than 10 minutes. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| FWEr [Firmware Update Error] | Probable Cause: Firmware update function has detected an error. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| HCF [Boards Compatibility] | Probable Cause: Hardware configuration error. The [Pairing password] parameter has been enabled and an option module has been changed. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| HFPF [High Flow Error] | Probable Cause: The high flow monitoring function has detected an error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IdLF [Egy Saving Exit Error] | Probable Cause: The drive is not turned on even though [Egy Saving Timeout] has elapsed. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IFA [MonitorCircuit A Error] | Probable Cause: The digital input assigned to [MonitorCircuit A Assign] is active for longer than [MonitorCircuit A Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IFb [MonitorCircuit B Error] | Probable Cause: The digital input assigned to [MonitorCircuit B Assign] is active for longer than [MonitorCircuit B Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IFC [MonitorCircuit C Error] | Probable Cause: The digital input assigned to [MonitorCircuit C Assign] is active for longer than [MonitorCircuit C Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IFd [MonitorCircuit D Error] | Probable Cause: The digital input assigned to [MonitorCircuit D Assign] is active for longer than [MonitorCircuit D Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| iHF [Input Overheating] | Probable Cause: The AFE brick temperature is too high. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ILF [Internal Link Error] | Probable Cause: Communication interruption between option module and the drive. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF0 [Internal Error 0] | Probable Cause: – Communication interruption between microprocessors of the control board. – The power board rating is not valid. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF1 [Internal Error 1] | Probable Cause: The power board rating is not valid. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF2 [Internal Error 2] | Probable Cause: The power board is incompatible with the control block software. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF3 [Internal Error 3] | Probable Cause: Internal communication detected error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF4 [Internal Error 4] | Probable Cause: Internal data inconsistent. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF6 [Internal Error 6] | Probable Cause: – The option module installed in the drive is not recognized. – The removable control terminal modules are not present or recognized. – The embedded Ethernet adapter is not recognized. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF7 [Internal Error 7] | Probable Cause: Communication interruption with CPLD component of Control board. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF8 [Internal Error 8] | Probable Cause: The internal power switching supply is not correct. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InF9 [Internal Error 9] | Probable Cause: An error on the current circuit measurement has been detected. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| InFA [Internal Error 10] | Probable Cause: The input stage is not operating correctly. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFb [Internal Error 11] | Probable Cause: The internal drive thermal sensor is not operating correctly. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| InFC [Internal Error 12] | Probable Cause: Internal current supply error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFd [Internal Error 13] | Probable Cause: Differential current deviation. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Extended Fault Reset] parameter after the cause has been removed. |
| InFE [Internal Error 14] | Probable Cause: Internal microprocessor detected error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFF [Internal Error 15] | Probable Cause: Serial memory flash format error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFG [Internal Error 16] | Probable Cause: Communication interruption or internal error of output relays option module. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFH [Internal Error 17] | Probable Cause: Communication interruption with the Extension module of digital & analog I/O or internal error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFk [Internal Error 20] | Probable Cause: Option module interface board error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFl [Internal Error 21] | Probable Cause: Internal Real Time Clock error or keypad communication error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFM [Internal Error 22] | Probable Cause: An error on the embedded Ethernet adapter has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFn [Internal Error 23] | Probable Cause: A communication interruption between the control block and AFE or BU bricks has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFP [Internal Error 25] | Probable Cause: Incompatibility between Control Board hardware version and firmware version. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFr [Internal Error 27] | Probable Cause: Diagnostics in CPLD have detected an error. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFS [Internal Error 28] | Probable Cause: An error on the AFE brick has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFt [Internal Error 29] | Probable Cause: An error on the power unit / inverter brick has been detected. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFU [Internal Error 30] | Probable Cause: An error on the rectifier brick has been detected or an [Input phase loss] PHF error has been triggered when the DC bus is charged. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| InFV [Internal Error 31] | Probable Cause: An error on the brick architecture has been detected (brick unavailable). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| IPPF [Inlet Pressure Error] | Probable Cause: The inlet pressure monitoring function has detected an error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| JAMF [Anti Jam Error] | Probable Cause: The Anti-Jam monitoring function has exceeded the maximum number of sequences allowed in the time window. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LCF [Input Contactor] | Probable Cause: The drive is not switched on even though [Mains V. time out ] LCt timeout has elapsed. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LCHF [High Level Error] | Probable Cause: The maximum level switch is active during filling process. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LCLF [Low Level Error] | Probable Cause: The minimum level switch is active during emptying process. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LFF1 [AI1 4-20mA loss] | Probable Cause: Loss of the 4-20 mA on analog input AI1. This error is triggered when the measured current is below 2 mA. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LFF2 [AI2 4-20mA loss] | Probable Cause: Loss of the 4-20 mA on analog input AI2. This error is triggered when the measured current is below 2 mA. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LFF3 [AI3 4-20mA loss] | Probable Cause: Loss of the 4-20 mA on analog input AI3. This error is triggered when the measured current is below 2 mA. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LFF4 [AI4 4-20mA loss] | Probable Cause: Loss of the 4-20 mA on analog input AI4. This error is triggered when the measured current is below 2mA. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LFF5 [AI5 4-20mA loss] | Probable Cause: Loss of the 4-20 mA on analog input AI5. This error is triggered when the measured current is below 2 mA. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| LKON [ON Lock Error] | Probable Cause: External device not ready. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| MdLF [MultiDrive Link Error] | Probable Cause: – The communication has been interrupted while running. – The function has detected an inconsistency in the system configuration. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| MFF [Mains Freq Out Of Range] | Probable Cause: [Mains Frequency] FRC on the AFE brick is out of range. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| MOF [Module Overheat] | Probable Cause: Cabinet temperature too high. [Module Overheat] MOA warning has been active for a time longer than 10 minutes. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| MPDF [M/P Device Error] | Probable Cause: A device on the MultiDrive Link architecture is missing. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| MPLF [Lead Pump Error] | Probable Cause: The selected lead pump is not available while in run. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ObF [DC Bus Overvoltage] | Probable Cause: – Deceleration time too short or driving load too high. – Supply mains voltage too high. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ObF2 [AFE Bus unbalancing] | Probable Cause: – AFE DC bus unbalancing. – Supply mains voltage too high. – Total generative power too high. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OCF [Overcurrent] | Probable Cause: – Parameters in the [Motor data] menu are not correct. – Inertia or load too high. – Mechanical locking. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| OHF [Drive Overheating] | Probable Cause: Drive temperature too high. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OLC [Process Overload] | Probable Cause: Process overload. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OLF [Motor Overload] | Probable Cause: Triggered by excessive motor current. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OPF1 [Single Output Phase Loss] | Probable Cause: Loss of one phase at drive output. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OPF2 [Output Phase Loss] | Probable Cause: – Motor not connected or motor power too low. – Output contactor opened. – Instantaneous instability in the motor current. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OPHF [Out Pressure High] | Probable Cause: The outlet pressure monitoring function has detected a high-pressure error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OPLF [Out Pressure Low] | Probable Cause: The outlet pressure monitoring function has detected a low-pressure error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| OSF [Supply Mains Overvoltage] | Probable Cause: – Supply mains voltage too high. – Disturbed supply mains. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| P24C [Cab I/O 24V Error] | Probable Cause: The input DI58 is used to monitor the 24V on input terminal. – DI58 cabinet I/O input is not wired to the internal terminal X231. – DI58 is used by another cabinet I/O function. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| PCPF [PumpCycle Start Error] | Probable Cause: The Pumpcycle monitoring function has exceeded the maximum number of start sequences allowed in the time window. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| PFMF [PID Feedback Error] | Probable Cause: The PID feedback error was out of the allowed range around the set point during the time window. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| PGLF [Program Loading Error] | Probable Cause: Verify that the error code can be cleared. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| PGrF [Program Running Error] | Probable Cause: Verify that the error code can be cleared. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| PHF [Input phase loss] | Probable Cause: – Drive incorrectly supplied or a tripped fused. – One phase is unavailable. – 3-phase Drive used on a single-phase supply mains. – Unbalanced load. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| PLFF [Pump Low Flow Error] | Probable Cause: The pump low flow monitoring function has detected an error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SAFF [Safety Function Error] | Probable Cause: – Debounce time exceeded. – Internal hardware error. – STOA and STOB have a different status (high/low) for more than 1 second. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| SCF1 [Motor short circuit] | Probable Cause: Short-circuit or grounding at the drive output. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Extended Fault Reset] HRFC parameter after the cause has been removed. |
| SCF3 [Ground Short Circuit] | Probable Cause: Significant ground leakage current at the drive output if several motors are connected in parallel. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| SCF4 [IGBT Short Circuit] | Probable Cause: Power component detected error (short circuit or interruption detected on at least one IGBT). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SCF5 [Motor Short Circuit] | Probable Cause: Short-circuit at drive output. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SCF6 [AFE ShortCircuit error] | Probable Cause: AFE rectifier IGBT short-circuit. AFE over current due to power factor correction systems in the grid. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| SLF1 [Modbus Com Interruption] | Probable Cause: Communication interruption on the Modbus port. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SLF2 [PC Com Interruption] | Probable Cause: Communication interruption with the commissioning software. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SLF3 [HMI Com Interruption] | Probable Cause: Communication interruption with the Graphic display terminal. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SoF [Motor Overspeed] | Probable Cause: – Instability or driving load too high. – Downstream contactor not closed before Run command. – Overspeed threshold (110% of Max frequency) reached. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| SPFC [Security Files Corrupt] | Probable Cause: Security files corrupted or missing. Remedy:
Clearing the Error Code: This detected error requires a power reset. |
| StF [Motor Stall Error] | Probable Cause: The stall monitoring function has detected an error. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| t2CF [AI2 Thermal Sensor Error] | Probable Cause: The thermal sensor monitoring function has detected a thermal sensor error on analog input AI2 (Open or Short circuit). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| t3CF [AI3 Thermal Sensor Error] | Probable Cause: The thermal sensor monitoring function has detected an error on analog input AI3 (Open or Short circuit). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| t4CF [AI4 Thermal Sensor Error] | Probable Cause: The thermal sensor monitoring function has detected an error on analog input AI4 (Open or Short circuit). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| t5CF [AI5 Thermal Sensor Error] | Probable Cause: The thermal sensor monitoring function has detected an error on analog input AI5 (Open or Short circuit). Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tFA [MotorWinding A Error] | Probable Cause: The digital input assigned to [MotorWinding A Assign] is active for longer than [MotorWinding A Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tFB [MotorWinding B Error] | Probable Cause: The digital input assigned to [MotorWinding B Assign] is active for longer than [MotorWinding B Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tFC [MotorBearing A Error] | Probable Cause: The digital input assigned to [MotorBearing A Assign] is active for longer than [MotorBearing A Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tFD [MotorBearing B Error] | Probable Cause: The digital input assigned to [MotorBearing B Assign] is active for longer than [MotorBearing B Delay]. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tH2F [AI2 Th Level Error] | Probable Cause: The thermal sensor monitoring function has detected a high temperature error on analog input AI2. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tH3F [AI3 Th Level Error] | Probable Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI3. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tH4F [AI4 Th Level Error] | Probable Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI4. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tH5F [AI5 Th Level Error] | Probable Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI5. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tJF [IGBT Overheating] | Probable Cause: Drive power stage overheating. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tJF2 [AFE IGBT over-heat error] | Probable Cause: Rectifier IGBT power stage overheating. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| tnF [Autotuning Error] | Probable Cause: – Special motor or motor whose power is not suitable for the drive. – Motor not connected to the drive. – Motor not stopped. Remedy:
Clearing the Error Code: This detected error can be cleared manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| ULF [Process Underload] | Probable Cause: Process underload. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |
| UrF [AFE Mains Undervoltage] | Probable Cause: – Too low DC-Bus voltage due to mains undervoltage. – AFE overload. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| USF [Supply Mains UnderV] | Probable Cause: – Supply mains too low. – Transient voltage dips. Remedy:
Clearing the Error Code: This detected error is cleared as soon as its cause has been removed. |
| VCF [VxCtrl Error] | Probable Cause: Invalid power reference curve or warning still present after the error delay [Error Delay] VCFd. Remedy:
Clearing the Error Code: This detected error can be cleared with the [Auto Fault Reset] or manually with the [Fault Reset Assign] parameter after its cause has been removed. |