Schneider ATV610 Drives

Fault Code and MeaningCause and Remedy
NOA

[No Warning stored]

Cause: No warning stored.
FRF

[Fallback Frequency]

Cause: Reaction on event: Fallback frequency.
RLS

[Speed Maintained]

Cause: Reaction on event: Speed maintained.
STT

[Type of stop]

Cause: Reaction on event: Stop following [Type of stop] STT without triggering an error.
SRA

[Ref Frequency Warning]

Cause: Frequency reference reached.
PEE

[PID error Warning]

Cause: PID error warning.
PFA

[PID Feedback Warn]

Cause: PID feedback warning.
TP3A

[AI3 Th Warning]

Cause: AI3 Thermal warning.
TP4A

[AI4 Th Warning]

Cause: AI4 Thermal warning.
TP5A

[AI5 Th Warning]

Cause: AI5 Thermal warning.
AP1

[AI1 4-20 Warning]

Cause: AI1 4-20 mA loss warning.
AP3

[AI3 4-20 Warning]

Cause: AI3 4-20 mA loss warning.
AP4

[AI4 4-20 Warning]

Cause: AI4 4-20 mA loss warning.
AP5

[AI5 4-20 Warning]

Cause: AI5 4-20 mA loss warning.
FCTA

[Fan Counter Warning]

Cause: Fan counter speed warning.
FFDA

[Fan Feedback Warning]

Cause: Fan feedback warning.
BOA

[BR Thermal Warning]

Cause: Braking resistor thermal warning.
EFA

[Ext. Error Warning]

Cause: External error warning.
USA

[Undervoltage Warning]

Cause: Undervoltage warning.
UPA

[Preventive UnderV Active]

Cause: Controlled stop threshold is reached.
FTA

[Mot Freq High Thd]

Cause: Motor frequency high threshold 1 reached.
FTAL

[Mot Freq Low Thd]

Cause: Motor frequency low threshold 1 reached.
F2AL

[Mot Freq Low Thd 2]

Cause: Motor frequency low threshold 2 reached.
FLA

[High Speed Reached]

Cause: High speed reached warning.
RTAH

[Ref Freq High Thd reached]

Cause: Reference frequency high threshold reached.
RTAL

[Ref Freq Low Thd reached]

Cause: Reference frequency low threshold reached.
F2A

[2nd Freq Thd Reached]

Cause: Motor frequency high threshold 2 reached.
CTA

[Current Thd Reached]

Cause: Motor current high threshold reached.
CTAL

[Low Current Reached]

Cause: Motor current low threshold reached.
ULA

[Process Undld Warning]

Cause: Process underload warning.
OLA

[Process Overload Warning]

Cause: Overload warning.
TAD

[Dev Thermal reached]

Cause: Drive thermal threshold reached.
TSA

[Motor Therm Thd reached]

Cause: Motor thermal threshold reached.
PFES

[Pos. Following Warn]

Cause: Position following warning.
TS2A

[Temp Sens AI2 Warn]

Cause: Temperature sensor AI2 warning (open circuit).
TS3A

[Temp Sens AI3 Warn]

Cause: Temperature sensor AI3 warning (open circuit).
TS4A

[Temp Sens AI4 Warn]

Cause: Temperature sensor AI4 warning (open circuit).
TS5A

[Temp Sens AI5 Warn]

Cause: Temperature sensor AI5 warning (open circuit).
DCRW

[DC Bus Ripple Warn]

Cause: DC Bus Ripple Warning.
AFFL

[Fallback Channel]

Cause: Automatic fallback behavior activated after a fieldbus communication interruption.
CBF
[Circuit Breaker Error]

Cause: The DC bus voltage level is incorrect compared to the circuit breaker logic control (start or stop pulse) after the configured timeout. Defect of the motor circuit breaker.



Remedy:

  • Verify the circuit breaker logic control (pulse time for start and stop).

  • Verify the mechanical state of the circuit breaker.

  • Verify the measured values of [DC bus voltage] (VBUS) and [Mains Voltage] (ULN) parameters.


CFF
[Incorrect Config]

Cause: At power on, the configuration is not correct. Option module changed or removed.



Remedy:

  • Verify that all option modules are inserted correctly into the option module slot.

  • Verify that there is no detected error on the option module.

  • Return to factory settings or retrieve the backup configuration if it is valid.


CFI
[Invalid Configuration]

Cause: The configuration loaded in the device via the commissioning tool or fieldbus is inconsistent. Invalid parameter value.



Remedy:

  • Verify the loaded configuration.

  • Load a valid configuration.


CFI2
[Conf Transfer Error]

Cause: The configuration transfer to the device was not successful or interrupted. The configuration loaded is not compatible with the device.



Remedy:

  • Verify the configuration loaded previously.

  • Load a compatible configuration.

  • Use PC software commissioning tool to transfer a compatible configuration.

  • Perform a factory setting.


CFI3
[Pre-settings Transfer Error]

Cause: The configuration transfer to the device was not successful or interrupted.



Remedy:

  • Contact your local Schneider Electric representative.


CNF
[Fieldbus Com Interrupt]

Cause: Communication interruption on fieldbus module. Triggered when communication between the fieldbus module and the master (PLC) is interrupted.



Remedy:

  • Verify the communication settings on the devices (Drive, PLC, switches, repeater…).

  • Check for duplicate communication addresses.

  • Verify the environment (electromagnetic compatibility).

  • Verify the fieldbus wiring (continuity, cable type, grounding, and shielding).

  • Verify the terminating resistor.

  • Verify the timeout setting.

  • Refer to the fieldbus user manual.

  • Replace the option module.


CRF1
[Precharge Capacitor]

Cause: Charging circuit control detected error or charging resistor damaged. Supply Mains unstable or too low.



Remedy:

  • Turn off the device and then turn on again.

  • Verify the setting of [DC Bus Source Type] (DCBS).

  • Verify the mains supply voltage and stability.

  • Verify the parameters of [Undervoltage handling] (USB) menu.

  • Contact your local Schneider Electric representative.


CSF
[Channel Switch Error]

Cause: An invalid channel has been selected. This error may be triggered if the device has been switched to a configuration which implies an invalid channel.



Remedy:

  • Verify the function parameters.


DCRE
[DC Bus Ripple Error]

Cause: Persistent ripple detected on the DC bus or DC bus capacitors damaged.



Remedy:

  • Turn off the device and then turn on again.

  • Verify the correct behavior of the input filter.

  • Verify the Supply Mains wirings.

  • Verify the internal connections.

  • Contact your local Schneider Electric representative.


EEF1
[Control Memory Error]

Cause: An error of the internal memory of the control electronics has been detected.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Turn off the device and then turn on again.

  • Return to factory settings.

  • Contact your local Schneider Electric representative.


EEF2
[Power Memory Error]

Cause: An error of the internal memory of the power board has been detected.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Turn off the device and then turn on again.

  • Return to factory settings.

  • Contact your local Schneider Electric representative.


EPF1
[External Error]

Cause: An external error has been triggered by an external device, depending on user (via digital input assigned to [Ext Error assign]). An external error has been triggered via Embedded Ethernet.



Remedy:

  • Remove the cause of the external error.

  • Verify the setting of [Ext Error assign] (ETF) parameter.

  • Perform a factory setting of the Ethernet configuration.


EPF2
[Fieldbus Error]

Cause: External detected error from fieldbus module. Event triggered by an external device, depending on user. The error is caused by the fieldbus or an application program.



Remedy:

  • Remove the cause of the external error.

  • Verify the external circuit in the system which has triggered the error message.

  • Verify the PLC program which has caused the error message.

  • Verify the communication parameters.

  • Monitor with the commissioning software [Fieldbus Error] (EPF2) parameter.


FWER
[Firmware Update Error]

Cause: Firmware update function has detected an error.



Remedy:

  • Contact your local Schneider Electric representative.


HCF
[Boards Compatibility]

Cause: Hardware configuration error. The [Pairing password] (PPI) parameter has been enabled and an option module has been changed.



Remedy:

  • Refit the original option module.

  • Confirm the configuration by entering the [Pairing password] (PPI) if the module was changed deliberately.


HFPF
[High Flow Error]

Cause: The high flow monitoring function has detected an error.



Remedy:

  • Verify that the system works in its flow capabilities.

  • Verify that there is no pipe burst at the outlet of the system.

  • Verify the settings of the monitoring function.


ILF
[Internal Link Error]

Cause: Communication interruption between option module and the device.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Verify the connections.

  • Replace the option module.

  • Contact your local Schneider Electric representative.


INF0
[Internal Error 0] (IPC)

Cause: Internal control electronics CPU error. Communication interruption between microprocessors of the control board. The power board rating is not valid.



Remedy:

  • Turn off the device and then turn on again.

  • Contact your local Schneider Electric representative.


INF1
[Internal Error 1] (Rating)

Cause: If a component is not compatible with the hardware configuration. The power board rating is not valid.



Remedy:

  • Contact your local Schneider Electric representative.


INF2
[Internal Error 2] (Soft)

Cause: The power board is incompatible with the control electronics software. The Power board was replaced by a spare part and is not set to the correct power rating.



Remedy:

  • Turn off the device and then turn on again.

  • Contact your local Schneider Electric representative.


INF3
[Internal Error 3] (Intern Comm)

Cause: Internal communication detected error. Verify the wiring on device control terminals (internal 10V supply for analog inputs overloaded).



Remedy:

  • Contact your local Schneider Electric representative.


INF4
[Internal Error 4] (Manufacturing)

Cause: Internal data inconsistent.



Remedy:

  • Contact your local Schneider Electric representative.


INF6
[Internal Error 6] (Option)

Cause: The option module installed in the device is not recognized. The removable control terminal modules are not present. The embedded Ethernet adapter is not recognized. The device firmware is not compatible. Option module corrupted.



Remedy:

  • Verify the catalog number and compatibility of the option module.

  • Plug the removable control terminal modules after the device has been switched off.

  • Update the device firmware.

  • Contact your local Schneider Electric representative.


INF7
[Internal Error 7] (Init)

Cause: Communication interruption with CPLD component of the control board.



Remedy:

  • Contact your local Schneider Electric representative.


INF8
[Internal Error 8] (Switching Supply)

Cause: The internal power supplies of the control electronics are monitored, if one is out of range the error is triggered.



Remedy:

  • Contact your local Schneider Electric representative.


INF9
[Internal Error 9] (Measure)

Cause: An error on the current circuit measurement has been detected.



Remedy:

  • Contact your local Schneider Electric representative.


INFA
[Internal Error 10] (Mains)

Cause: The input stage is not operating correctly. The external 24 Vdc supply voltage is too high.



Remedy:

  • Verify the external 24 Vdc supply.

  • Contact your local Schneider Electric representative.


INFB
[Internal Error 11] (Temperature)

Cause: Internal temperature sensors are monitored for short circuit or open circuit. The internal device thermal sensor is not operating correctly.



Remedy:

  • Contact your local Schneider Electric representative.


INFC
[Internal Error 12] (Internal current supply)

Cause: The current sensor supply monitoring has detected a low level on the current sensor supply.



Remedy:

  • Contact your local Schneider Electric representative.


INFD
[Internal Error 13] (Diff current)

Cause: Differential current deviation on parallel inverter bricks/power modules.



Remedy:

  • Verify connections between inverter brick/power module outputs and device output terminals.


INFE

Internal Error 14 (CPU)

Cause:

Internal microprocessor detected error.



Remedy:


  • Verify that the error code can be cleared.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFF

Internal Error 15 (Flash)

Cause:

Serial memory flash format error.



Remedy:


  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFG

Internal Error 16 (IO module – relay)

Cause:

Option module error.

Communication interruption of the output relays option module.

Internal error of the output relays option module.



Remedy:


  • Verify that the option module is correctly connected to the control electronics.

  • Replace the option module.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFH

Internal Error 17 (IO module – Standard)

Cause:

Extension module error.

Communication interruption with the extension module of digital & analog I/O.

Internal error of the extension module of digital & analog I/O.



Remedy:


  • Verify that the option module is correctly connected to the control electronics.

  • Replace the option module.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFK

Internal Error 20 (option interface PCBA)

Cause:

Option module interface board error.



Remedy:


  • Replace the option module.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFL

Internal Error 21 (RTC)

Cause:

Internal Real Time Clock error.

Communication interruption between the Graphic Display Terminal and the device.

Clock oscillator error.



Remedy:


  • Replace the Graphic Display Terminal.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFM

Internal Error 22 (Embedded Ethernet)

Cause:

An error on the embedded Ethernet adapter has been detected.

Instability of external 24 Vdc supply.



Remedy:


  • Verify the connection to the Ethernet port.

  • Verify the external 24 Vdc supply voltage stability.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFP

Internal Error 25 (Incompatibility CB & SW)

Cause:

Incompatibility between the control board hardware version and firmware version.



Remedy:


  • Update the firmware package.

  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFR

Internal Error 27 (Diagnostics CPLD)

Cause:

Diagnostics in CPLD have detected an error.



Remedy:


  • Contact your local Schneider Electric representative.

  • (Requires power reset).


INFU

Internal Error 30 (Rectifier)

Cause:

An error on the rectifier brick has been detected or an [Input Phase Loss] (PHF) error has been triggered when the DC bus is charged.



Remedy:


  • Turn off the device and then turn on again.

  • If [Input Phase Loss] (PHF) error code replaces [Internal Error 30] (INFU), refer to the instructions of [Input Phase Loss] (PHF) error.

  • (Requires power reset).


LCF

Input Contactor

Cause:

Sequences allowed in the time window.



Remedy:


  • Verify the wiring between the Supply Mains, the contactor/breaker and device.

  • Verify that the Supply Mains is present upstream of the contactor/breaker.

  • Verify the input contactor/breaker and its wiring.

  • Verify the [Mains V. time out] (LCT) timeout setting.

  • Verify the input contactor/breaker configuration.


LFF1

AI1 4-20 mA loss

Cause:

Loss of the 4-20 mA on analog input AI1. This error is triggered when the analog input current is below the minimum threshold value.



Remedy:


  • Verify the connection on the analog inputs.

  • Verify the setting of [AI1 4-20mA loss] (LFL1) parameter.


LFF2

AI2 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI2. This error is triggered when the analog input current is below the minimum threshold value.



Remedy:


  • Verify the connection on the analog inputs.

  • Verify the setting of [AI2 4-20mA loss] (LFL2) parameter.


LFF3

AI3 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI3. This error is triggered when the analog input current is below the minimum threshold value.



Remedy:


  • Verify the connection on the analog inputs.

  • Verify the setting of [AI3 4-20mA loss] (LFL3) parameter.


LFF4

AI4 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI4. This error is triggered when the analog input current is below the minimum threshold value.



Remedy:


  • Verify the connection on the analog inputs.

  • Verify the setting of [AI4 4-20mA loss] (LFL4) parameter.


LFF5

AI5 4-20 mA loss

Cause:

Loss of the 4-20 mA on analog input AI5. This error is triggered when the analog input current is below the minimum threshold value.



Remedy:


  • Verify the connection on the analog inputs.

  • Verify the setting of [AI5 4-20mA loss] (LFL5) parameter.


MPLF

Lead Pump Error

Cause:

The selected lead pump is not available while in run.



Remedy:


  • Verify the state of the corresponding drive digital input for the pump availability information (for example [Pump 1 Ready Assign] MPI1 for the pump 1).


OBF

DC Bus Overvoltage

Cause:

The DC bus voltage is too high.

Deceleration time too short or driving load too high.

Mains voltage too high.

Braking unit option cannot convert the “braking energy” into heat.



Remedy:


  • Increase the deceleration time.

  • Configure the [Dec.Ramp Adapt] (BRA) function if it is compatible with the application.

  • Verify the Mains voltage.

  • Verify the braking circuit capability if present.


OCF

Overcurrent

Cause:

Overcurrent limitation is reached.

Inertia or load too high.

Mechanical locking.

Motor autotuned values does not match with the motor connected.



Remedy:


  • Verify the motor parameters.

  • Verify the size of the motor/drive/load.

  • Verify the state of the mechanism.

  • Decrease [Current Limitation] (CLI).

  • Increase the switching frequency.

  • Proceed to the motor autotuning.


OHF

Device Overheating

Cause:

Device temperature too high.

Ambient temperature too high.

Reduced air flow due to blocked air at the inlet or outlet.

One of the fans does not work properly.



Remedy:


  • Verify the drive ventilation and the ambient temperature.

  • Clean the heat sink.

  • Clean the inlet filter.

  • Verify the air flow.

  • Verify the fans.

  • Verify the motor load according to the environmental conditions.

  • Verify the external 48V power supply function (if applicable).

  • Wait for the drive to cool down before restarting.


OLC

Process Overload

Cause:

Process overload.

Mechanical root cause in the application.

Changed load cycle situation of the application.



Remedy:


  • Verify and remove the cause of the overload.

  • Verify the parameters of the [Process overload] (OLD–) function.


OLF

Motor Overload

Cause:

This error is triggered when an excessive motor current has been detected.

The [Motor Overload] (OLF) threshold is set to 118 % of the [Motor Therm State] (THR).



Remedy:


  • Verify the setting of the motor thermal monitoring.

  • Verify the motor load. Wait for the motor to cool down before restarting.

  • Verify the setting of the following parameters: [Motor Th Current] (ITH), [Motor Thermal Mode] (THT), [Motor Therm Thd] (TTD), [MotorTemp ErrorResp] (OLL).

  • Verify the parameter [OutPhaseLoss Delay] (ODT) value.


OPF1

Single output phase loss

Cause:

Loss of one phase at device output.



Remedy:


  • Verify the wiring from the device to the motor.


OPF2

Output Phase Loss

Cause:

Loss of three phases at device output.

Motor not connected or motor power too low.

Output contactor opened.

Instantaneous instability in the motor current.



Remedy:


  • Verify the wiring from the device to the motor, including the tightening of the connections.

  • If an output contactor is being used, set [OutPhaseLoss Assign] (OPL) to [No Error Triggered] (OAC).

  • If the device is connected to a low-power motor or not connected to a motor: Deactivate motor phase loss detection [OutPhaseLoss Assign] (OPL) = [Function Inactive] (NO).

  • Verify and optimize the following parameters: [IR compensation] (UFR), [Nom Motor Voltage] (UNS) and [Nom Motor Current] (NCR) and perform [Autotuning] (TUN).


OSF

Supply Mains Overvoltage

Cause:

This error is triggered when the device is not running, and the DC bus voltage exceeds the maximum value allowed by the device.

Supply Mains voltage too high.



Remedy:


  • Verify the Mains voltage.


PFMF

PID Feedback Error

Cause:

The PID feedback error was out of the allowed range around the set point during the time window.



Remedy:


  • Check for mechanical breakdown of pipes.

  • Check for water leakage.

  • Check for open discharge valve.

  • Check for fire hydrant opened.

  • Verify the settings of the monitoring function.


PGLF

Program Loading Error

Cause:

Verify that the error code can be cleared.



Remedy:


  • Contact your local Schneider Electric representative.


PGRF

Program Running Error

Cause:

Verify that the error code can be cleared.



Remedy:


  • Contact your local Schneider Electric representative.

  • (Requires power reset).


PHF

Input Phase Loss

Cause:

Device incorrectly supplied or a tripped fused.

One phase is unavailable.

3-phase device used on a single-phase Supply Mains.

Unbalanced load.



Remedy:


  • Verify the wiring from the device to the motor, including the tightening of the connections.

  • Verify the fuses and the power connection.

  • Use a 3-phase Supply Mains.


SCF1
[Motor short circuit]

Cause:

The monitoring function of the device has detected a short circuit between the phase outputs or a phase to the ground.



Remedy:


  • Verify the cables connecting the device to the motor, and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.


Clearing: This detected error requires a power reset.
SCF3
[Ground Short Circuit]

Cause:

• Significant ground leakage current at the device output.

• Short circuit or grounding at the inverter output.

• Short circuit on a motor with long cable.

• Insulation error in the motor or in the cable.

• High resistance at the motor connection.



Remedy:


  • Verify the cables connecting the device to the motor, and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.

  • In case of long motor cables, verify the setting of [Ground Fault Activation] GRFL.

  • Contact your local Schneider Electric representative.


Clearing: This detected error requires a power reset.
SCF4
[IGBT Short Circuit]

Cause:

Power component detected error.

At product power-on, the IGBTs are tested for short circuit. Thereby an error (short circuit or interruption) has been detected on at least one IGBT. The time to check each transistor is between 1 and 10 μs.



Remedy:


  • Verify the setting of [Output Short Circuit Test] STRT parameter.

  • Contact your local Schneider Electric representative.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
SCF5
[Motor Short Circuit]

Cause:

Short-circuit at device output.



Remedy:


  • Verify the cables connecting the device to the motor, and the motor’s insulation.

  • Contact your local Schneider Electric representative.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
SLF1
[Modbus Com Interruption]

Cause:

Communication interruption on the Modbus port if the command and/or reference value is given by Modbus.



Remedy:


  • Verify the Modbus communication wiring.

  • Verify the Modbus communication parameter settings.

  • Verify the timeout.

  • Refer to the Modbus user manual.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
SLF3
[HMI Com Interruption]

Cause:

Communication interruption with the Graphic display terminal.

This error is triggered when the command or reference value are given using the Graphic Display Terminal and if the communication is interrupted during more than 2 seconds.



Remedy:


  • Verify the Graphic display terminal connection.

  • Verify that the cable length does not exceed 10 m.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
SOF
[Motor Overspeed]

Cause:

A too high-speed has been detected, based on the speed feedback or on the estimated speed, depending on the settings.

• Instability or driving load too high.

• If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command.

• The overspeed threshold (corresponding to 110 % of [Max Frequency] TFR) has been reached.



Remedy:


  • Verify the motor parameter settings.

  • Verify the size of the motor/drive/load.

  • Add a braking resistor if necessary.

  • Verify and close the contacts between the motor and the drive before applying a RUN command.

  • Verify the consistency between [Max Frequency] TFR and [High Speed] HSP.


Clearing: Can be cleared manually with the [Fault Reset Assign] RSF parameter after its cause has been removed.
STF
[Motor Stall Error]

Cause:

The stall monitoring function has detected an error. The [Motor Stall Error] STF is triggered on the following conditions:

• The output frequency is smaller than the stalling frequency [Stall Frequency] STP3.

• The output current is higher than the stalling current [Stall Current] STP2.

• For a duration longer than the stalling time [Stall Max Time] STP1.



Remedy:


  • Search for a mechanical blocking of the motor.

  • Search for a possible cause of motor overload.

  • Verify the settings of the monitoring function.


Clearing: Can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF.
T2CF
[AI2 Thermal Sensor Error]

Cause:

The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI2:

• Open circuit, or

• Short circuit.



Remedy:


  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI2 Type] AI2T parameter.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
T3CF
[AI3 Thermal Sensor Error]

Cause:

The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI3:

• Open circuit, or

• Short circuit.



Remedy:


  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI3 Type] AI3T parameter.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
T4CF
[AI4 Thermal Sensor Error]

Cause:

The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI4:

• Open circuit, or

• Short circuit.



Remedy:


  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI4 Type] AI4T parameter.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
T5CF
[AI5 Thermal Sensor Error]

Cause:

The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI5:

• Open circuit, or

• Short circuit.



Remedy:


  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI5 Type] AI5T parameter.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TH2F
[AI2 Th Level Error]

Cause:

The thermal sensor monitoring function has detected a high temperature on analog input AI2.



Remedy:


  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TH3F
[AI3 Th Level Error]

Cause:

The thermal sensor monitoring function has detected a high temperature on analog input AI3.



Remedy:


  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TH4F
[AI4 Th Level Error]

Cause:

The thermal sensor monitoring function has detected a high temperature on analog input AI4.



Remedy:


  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TH5F
[AI5 Th Level Error]

Cause:

The thermal sensor monitoring function has detected a high temperature on analog input AI5.



Remedy:


  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TJF
[IGBT Overheating]

Cause:

The thermal junction monitoring function helps to prevent the IGBT from junction over temperature.

• Device power stage overheating.

• On AFE drives: the thermal model of the AFE IGBT thermal monitoring has detected an overheat.



Remedy:


  • Verify the size of the load/motor/device according to environment conditions.

  • Verify the device ventilation and the ambient temperature.

  • Reduce the switching frequency.

  • Verify the external 48V power supply function (if applicable).


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
TNF
[Autotuning Error]

Cause:

An error has been triggered during a motor autotune.

• Special motor or motor whose power is not suitable for the drive.

• Motor not connected to the drive.

• Motor not stopped.

• For a tune in rotation, the motor has been stopped prematurely.

• The configuration of the drive (including the configuration of the tune in rotation) does not fit the use of tune in rotation with your application.

• The motor cannot operate correctly during a tune in rotation.

• Autotuning with long motor cables.



Remedy:


  • Verify that the motor/device are compatible.

  • Verify that the motor is connected to the device during autotuning.

  • If an output contactor is being used, verify that it is closed during autotuning.

  • Verify that the motor is present and stopped during autotuning.

  • In case of reluctance motor, reduce [PSI Align Curr Max] MCR.

  • In case of error detected during a tune in rotation:

    • Verify the run order remain active all along the tune in rotation.

    • Increase [Acceleration] ACC and [Deceleration] DEC. They must not be set to value close to 0 s.

    • If [Nb Of Repetitions] TNBR is different from 1, decrease [2nd Id max current] IDH2.

    • If [Nb Of Repetitions] TNBR is different from 1, increase [2nd Id min current] IDL2.

    • If possible, remove the load of the motor.

    • Set back [Rotation Tune Freq] TLFR to [Nominal Motor Freq] FRS.



  • If the error continues to be triggered, decrease [Rotation Tune Freq] TLFR.

  • If possible, decrease [Nb Of Repetitions] TNBR.


Clearing: This detected error can be cleared manually with the [Fault Reset Assign] RSF.
ULF
[Process Underload]

Cause:

Process underload.

• Mechanical root cause in the application.

• Changed load cycle situation of the application.



Remedy:


  • Verify and remove the cause of the underload.

  • Verify the parameters of the [Process underload] ULD– function.


Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF.
USF
[Supply Mains UnderV]

Cause:

Supply mains undervoltage. The measured DC bus voltage is lower than the rated voltage of the Supply Mains [Mains voltage] URES configured:

• Supply Mains power too weak.



Remedy:


  • Verify the RMS input voltage and the parameters of [Undervoltage Resp] USB.


Clearing: This detected error is cleared as soon as its cause has been removed.