Schneider ATV610 Drives Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| NOA [No Warning stored] | Cause: No warning stored. |
| FRF [Fallback Frequency] | Cause: Reaction on event: Fallback frequency. |
| RLS [Speed Maintained] | Cause: Reaction on event: Speed maintained. |
| STT [Type of stop] | Cause: Reaction on event: Stop following [Type of stop] STT without triggering an error. |
| SRA [Ref Frequency Warning] | Cause: Frequency reference reached. |
| PEE [PID error Warning] | Cause: PID error warning. |
| PFA [PID Feedback Warn] | Cause: PID feedback warning. |
| TP3A [AI3 Th Warning] | Cause: AI3 Thermal warning. |
| TP4A [AI4 Th Warning] | Cause: AI4 Thermal warning. |
| TP5A [AI5 Th Warning] | Cause: AI5 Thermal warning. |
| AP1 [AI1 4-20 Warning] | Cause: AI1 4-20 mA loss warning. |
| AP3 [AI3 4-20 Warning] | Cause: AI3 4-20 mA loss warning. |
| AP4 [AI4 4-20 Warning] | Cause: AI4 4-20 mA loss warning. |
| AP5 [AI5 4-20 Warning] | Cause: AI5 4-20 mA loss warning. |
| FCTA [Fan Counter Warning] | Cause: Fan counter speed warning. |
| FFDA [Fan Feedback Warning] | Cause: Fan feedback warning. |
| BOA [BR Thermal Warning] | Cause: Braking resistor thermal warning. |
| EFA [Ext. Error Warning] | Cause: External error warning. |
| USA [Undervoltage Warning] | Cause: Undervoltage warning. |
| UPA [Preventive UnderV Active] | Cause: Controlled stop threshold is reached. |
| FTA [Mot Freq High Thd] | Cause: Motor frequency high threshold 1 reached. |
| FTAL [Mot Freq Low Thd] | Cause: Motor frequency low threshold 1 reached. |
| F2AL [Mot Freq Low Thd 2] | Cause: Motor frequency low threshold 2 reached. |
| FLA [High Speed Reached] | Cause: High speed reached warning. |
| RTAH [Ref Freq High Thd reached] | Cause: Reference frequency high threshold reached. |
| RTAL [Ref Freq Low Thd reached] | Cause: Reference frequency low threshold reached. |
| F2A [2nd Freq Thd Reached] | Cause: Motor frequency high threshold 2 reached. |
| CTA [Current Thd Reached] | Cause: Motor current high threshold reached. |
| CTAL [Low Current Reached] | Cause: Motor current low threshold reached. |
| ULA [Process Undld Warning] | Cause: Process underload warning. |
| OLA [Process Overload Warning] | Cause: Overload warning. |
| TAD [Dev Thermal reached] | Cause: Drive thermal threshold reached. |
| TSA [Motor Therm Thd reached] | Cause: Motor thermal threshold reached. |
| PFES [Pos. Following Warn] | Cause: Position following warning. |
| TS2A [Temp Sens AI2 Warn] | Cause: Temperature sensor AI2 warning (open circuit). |
| TS3A [Temp Sens AI3 Warn] | Cause: Temperature sensor AI3 warning (open circuit). |
| TS4A [Temp Sens AI4 Warn] | Cause: Temperature sensor AI4 warning (open circuit). |
| TS5A [Temp Sens AI5 Warn] | Cause: Temperature sensor AI5 warning (open circuit). |
| DCRW [DC Bus Ripple Warn] | Cause: DC Bus Ripple Warning. |
| AFFL [Fallback Channel] | Cause: Automatic fallback behavior activated after a fieldbus communication interruption. |
| CBF [Circuit Breaker Error] | Cause: The DC bus voltage level is incorrect compared to the circuit breaker logic control (start or stop pulse) after the configured timeout. Defect of the motor circuit breaker. Remedy:
|
| CFF [Incorrect Config] | Cause: At power on, the configuration is not correct. Option module changed or removed. Remedy:
|
| CFI [Invalid Configuration] | Cause: The configuration loaded in the device via the commissioning tool or fieldbus is inconsistent. Invalid parameter value. Remedy:
|
| CFI2 [Conf Transfer Error] | Cause: The configuration transfer to the device was not successful or interrupted. The configuration loaded is not compatible with the device. Remedy:
|
| CFI3 [Pre-settings Transfer Error] | Cause: The configuration transfer to the device was not successful or interrupted. Remedy:
|
| CNF [Fieldbus Com Interrupt] | Cause: Communication interruption on fieldbus module. Triggered when communication between the fieldbus module and the master (PLC) is interrupted. Remedy:
|
| CRF1 [Precharge Capacitor] | Cause: Charging circuit control detected error or charging resistor damaged. Supply Mains unstable or too low. Remedy:
|
| CSF [Channel Switch Error] | Cause: An invalid channel has been selected. This error may be triggered if the device has been switched to a configuration which implies an invalid channel. Remedy:
|
| DCRE [DC Bus Ripple Error] | Cause: Persistent ripple detected on the DC bus or DC bus capacitors damaged. Remedy:
|
| EEF1 [Control Memory Error] | Cause: An error of the internal memory of the control electronics has been detected. Remedy:
|
| EEF2 [Power Memory Error] | Cause: An error of the internal memory of the power board has been detected. Remedy:
|
| EPF1 [External Error] | Cause: An external error has been triggered by an external device, depending on user (via digital input assigned to [Ext Error assign]). An external error has been triggered via Embedded Ethernet. Remedy:
|
| EPF2 [Fieldbus Error] | Cause: External detected error from fieldbus module. Event triggered by an external device, depending on user. The error is caused by the fieldbus or an application program. Remedy:
|
| FWER [Firmware Update Error] | Cause: Firmware update function has detected an error. Remedy:
|
| HCF [Boards Compatibility] | Cause: Hardware configuration error. The [Pairing password] (PPI) parameter has been enabled and an option module has been changed. Remedy:
|
| HFPF [High Flow Error] | Cause: The high flow monitoring function has detected an error. Remedy:
|
| ILF [Internal Link Error] | Cause: Communication interruption between option module and the device. Remedy:
|
| INF0 [Internal Error 0] (IPC) | Cause: Internal control electronics CPU error. Communication interruption between microprocessors of the control board. The power board rating is not valid. Remedy:
|
| INF1 [Internal Error 1] (Rating) | Cause: If a component is not compatible with the hardware configuration. The power board rating is not valid. Remedy:
|
| INF2 [Internal Error 2] (Soft) | Cause: The power board is incompatible with the control electronics software. The Power board was replaced by a spare part and is not set to the correct power rating. Remedy:
|
| INF3 [Internal Error 3] (Intern Comm) | Cause: Internal communication detected error. Verify the wiring on device control terminals (internal 10V supply for analog inputs overloaded). Remedy:
|
| INF4 [Internal Error 4] (Manufacturing) | Cause: Internal data inconsistent. Remedy:
|
| INF6 [Internal Error 6] (Option) | Cause: The option module installed in the device is not recognized. The removable control terminal modules are not present. The embedded Ethernet adapter is not recognized. The device firmware is not compatible. Option module corrupted. Remedy:
|
| INF7 [Internal Error 7] (Init) | Cause: Communication interruption with CPLD component of the control board. Remedy:
|
| INF8 [Internal Error 8] (Switching Supply) | Cause: The internal power supplies of the control electronics are monitored, if one is out of range the error is triggered. Remedy:
|
| INF9 [Internal Error 9] (Measure) | Cause: An error on the current circuit measurement has been detected. Remedy:
|
| INFA [Internal Error 10] (Mains) | Cause: The input stage is not operating correctly. The external 24 Vdc supply voltage is too high. Remedy:
|
| INFB [Internal Error 11] (Temperature) | Cause: Internal temperature sensors are monitored for short circuit or open circuit. The internal device thermal sensor is not operating correctly. Remedy:
|
| INFC [Internal Error 12] (Internal current supply) | Cause: The current sensor supply monitoring has detected a low level on the current sensor supply. Remedy:
|
| INFD [Internal Error 13] (Diff current) | Cause: Differential current deviation on parallel inverter bricks/power modules. Remedy:
|
| INFE Internal Error 14 (CPU) | Cause: Internal microprocessor detected error. Remedy:
|
| INFF Internal Error 15 (Flash) | Cause: Serial memory flash format error. Remedy:
|
| INFG Internal Error 16 (IO module – relay) | Cause: Option module error. Communication interruption of the output relays option module. Internal error of the output relays option module. Remedy:
|
| INFH Internal Error 17 (IO module – Standard) | Cause: Extension module error. Communication interruption with the extension module of digital & analog I/O. Internal error of the extension module of digital & analog I/O. Remedy:
|
| INFK Internal Error 20 (option interface PCBA) | Cause: Option module interface board error. Remedy:
|
| INFL Internal Error 21 (RTC) | Cause: Internal Real Time Clock error. Communication interruption between the Graphic Display Terminal and the device. Clock oscillator error. Remedy:
|
| INFM Internal Error 22 (Embedded Ethernet) | Cause: An error on the embedded Ethernet adapter has been detected. Instability of external 24 Vdc supply. Remedy:
|
| INFP Internal Error 25 (Incompatibility CB & SW) | Cause: Incompatibility between the control board hardware version and firmware version. Remedy:
|
| INFR Internal Error 27 (Diagnostics CPLD) | Cause: Diagnostics in CPLD have detected an error. Remedy:
|
| INFU Internal Error 30 (Rectifier) | Cause: An error on the rectifier brick has been detected or an [Input Phase Loss] (PHF) error has been triggered when the DC bus is charged. Remedy:
|
| LCF Input Contactor | Cause: Sequences allowed in the time window. Remedy:
|
| LFF1 AI1 4-20 mA loss | Cause: Loss of the 4-20 mA on analog input AI1. This error is triggered when the analog input current is below the minimum threshold value. Remedy:
|
| LFF2 AI2 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI2. This error is triggered when the analog input current is below the minimum threshold value. Remedy:
|
| LFF3 AI3 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI3. This error is triggered when the analog input current is below the minimum threshold value. Remedy:
|
| LFF4 AI4 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI4. This error is triggered when the analog input current is below the minimum threshold value. Remedy:
|
| LFF5 AI5 4-20 mA loss | Cause: Loss of the 4-20 mA on analog input AI5. This error is triggered when the analog input current is below the minimum threshold value. Remedy:
|
| MPLF Lead Pump Error | Cause: The selected lead pump is not available while in run. Remedy:
|
| OBF DC Bus Overvoltage | Cause: The DC bus voltage is too high. Deceleration time too short or driving load too high. Mains voltage too high. Braking unit option cannot convert the “braking energy” into heat. Remedy:
|
| OCF Overcurrent | Cause: Overcurrent limitation is reached. Inertia or load too high. Mechanical locking. Motor autotuned values does not match with the motor connected. Remedy:
|
| OHF Device Overheating | Cause: Device temperature too high. Ambient temperature too high. Reduced air flow due to blocked air at the inlet or outlet. One of the fans does not work properly. Remedy:
|
| OLC Process Overload | Cause: Process overload. Mechanical root cause in the application. Changed load cycle situation of the application. Remedy:
|
| OLF Motor Overload | Cause: This error is triggered when an excessive motor current has been detected. The [Motor Overload] (OLF) threshold is set to 118 % of the [Motor Therm State] (THR). Remedy:
|
| OPF1 Single output phase loss | Cause: Loss of one phase at device output. Remedy:
|
| OPF2 Output Phase Loss | Cause: Loss of three phases at device output. Motor not connected or motor power too low. Output contactor opened. Instantaneous instability in the motor current. Remedy:
|
| OSF Supply Mains Overvoltage | Cause: This error is triggered when the device is not running, and the DC bus voltage exceeds the maximum value allowed by the device. Supply Mains voltage too high. Remedy:
|
| PFMF PID Feedback Error | Cause: The PID feedback error was out of the allowed range around the set point during the time window. Remedy:
|
| PGLF Program Loading Error | Cause: Verify that the error code can be cleared. Remedy:
|
| PGRF Program Running Error | Cause: Verify that the error code can be cleared. Remedy:
|
| PHF Input Phase Loss | Cause: Device incorrectly supplied or a tripped fused. One phase is unavailable. 3-phase device used on a single-phase Supply Mains. Unbalanced load. Remedy:
|
| SCF1 [Motor short circuit] | Cause: The monitoring function of the device has detected a short circuit between the phase outputs or a phase to the ground. Remedy:
Clearing: This detected error requires a power reset. |
| SCF3 [Ground Short Circuit] | Cause: • Significant ground leakage current at the device output. • Short circuit or grounding at the inverter output. • Short circuit on a motor with long cable. • Insulation error in the motor or in the cable. • High resistance at the motor connection. Remedy:
Clearing: This detected error requires a power reset. |
| SCF4 [IGBT Short Circuit] | Cause: Power component detected error. At product power-on, the IGBTs are tested for short circuit. Thereby an error (short circuit or interruption) has been detected on at least one IGBT. The time to check each transistor is between 1 and 10 μs. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| SCF5 [Motor Short Circuit] | Cause: Short-circuit at device output. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| SLF1 [Modbus Com Interruption] | Cause: Communication interruption on the Modbus port if the command and/or reference value is given by Modbus. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| SLF3 [HMI Com Interruption] | Cause: Communication interruption with the Graphic display terminal. This error is triggered when the command or reference value are given using the Graphic Display Terminal and if the communication is interrupted during more than 2 seconds. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| SOF [Motor Overspeed] | Cause: A too high-speed has been detected, based on the speed feedback or on the estimated speed, depending on the settings. • Instability or driving load too high. • If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command. • The overspeed threshold (corresponding to 110 % of [Max Frequency] TFR) has been reached. Remedy:
Clearing: Can be cleared manually with the [Fault Reset Assign] RSF parameter after its cause has been removed. |
| STF [Motor Stall Error] | Cause: The stall monitoring function has detected an error. The [Motor Stall Error] STF is triggered on the following conditions: • The output frequency is smaller than the stalling frequency [Stall Frequency] STP3. • The output current is higher than the stalling current [Stall Current] STP2. • For a duration longer than the stalling time [Stall Max Time] STP1. Remedy:
Clearing: Can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF. |
| T2CF [AI2 Thermal Sensor Error] | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI2: • Open circuit, or • Short circuit. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| T3CF [AI3 Thermal Sensor Error] | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI3: • Open circuit, or • Short circuit. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| T4CF [AI4 Thermal Sensor Error] | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI4: • Open circuit, or • Short circuit. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| T5CF [AI5 Thermal Sensor Error] | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI5: • Open circuit, or • Short circuit. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TH2F [AI2 Th Level Error] | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI2. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TH3F [AI3 Th Level Error] | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI3. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TH4F [AI4 Th Level Error] | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI4. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TH5F [AI5 Th Level Error] | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI5. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TJF [IGBT Overheating] | Cause: The thermal junction monitoring function helps to prevent the IGBT from junction over temperature. • Device power stage overheating. • On AFE drives: the thermal model of the AFE IGBT thermal monitoring has detected an overheat. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| TNF [Autotuning Error] | Cause: An error has been triggered during a motor autotune. • Special motor or motor whose power is not suitable for the drive. • Motor not connected to the drive. • Motor not stopped. • For a tune in rotation, the motor has been stopped prematurely. • The configuration of the drive (including the configuration of the tune in rotation) does not fit the use of tune in rotation with your application. • The motor cannot operate correctly during a tune in rotation. • Autotuning with long motor cables. Remedy:
Clearing: This detected error can be cleared manually with the [Fault Reset Assign] RSF. |
| ULF [Process Underload] | Cause: Process underload. • Mechanical root cause in the application. • Changed load cycle situation of the application. Remedy:
Clearing: Can be cleared with [Auto Fault Reset] ATR or manually with [Fault Reset Assign] RSF. |
| USF [Supply Mains UnderV] | Cause: Supply mains undervoltage. The measured DC bus voltage is lower than the rated voltage of the Supply Mains [Mains voltage] URES configured: • Supply Mains power too weak. Remedy:
Clearing: This detected error is cleared as soon as its cause has been removed. |