CrF1 Precharge |
Cause: Charging relay control fault or charging resistor damaged.
Remedy:
- Turn the drive off and then back on again.
- Check the connections.
- Check the stability of the main supply.
- Contact your local Schneider Electric representative.
|
InF1 Unknown drive rating |
Cause: The power card is different from the card stored.
Remedy:
- Contact your local Schneider Electric representative.
|
InF2 Unknown or incompatible power board |
Cause: The power card is incompatible with the control card.
Remedy:
- Contact your local Schneider Electric representative.
|
InF3 Internal serial link |
Cause: Communication interruption between the internal cards.
Remedy:
- Contact your local Schneider Electric representative.
|
InF4 Invalid industrialization zone |
Cause: Inconsistent internal data.
Remedy:
- Contact your local Schneider Electric representative.
|
InF9 Current measurement circuit |
Cause: Current measurement is not correct due to hardware circuit.
Remedy:
- Contact your local Schneider Electric representative.
|
—- Problem of application Firmware |
Cause: Invalid application firmware update using the Multi-Loader tool.
Remedy:
- Flash again the application firmware of the product.
|
InFb Internal thermal sensor detected fault |
Cause:
- The drive temperature sensor is not operating correctly.
- The drive is in short circuit or open.
Remedy:
- Contact your local Schneider Electric representative.
|
InFE Internal CPU |
Cause: Internal microprocessor.
Remedy:
- Turn the drive off and then back on again.
- Contact local Schneider Electric representative.
|
OCF Overcurrent |
Cause:
- Parameters in the Motor control menu (drC) are not correct.
- Inertia or load too high.
- Mechanical locking.
Remedy:
- Check the parameters.
- Check the size of the motor/drive/load.
- Check the state of the mechanism.
- Connect line chokes.
- Reduce the Switching frequency (SFr).
- Check the ground connection of drive, motor cable and motor insulation.
|
SCF1 Motor or Ground short circuit |
Cause:
- Short-circuit or grounding at the drive output.
- Ground fault during running status.
- Commutation of motors during running status.
- Significant current leakage to ground if several motors are connected in parallel.
Remedy:
- Check the cables connecting the drive to the motor, and the motor insulation.
- Connect motor chokes.
|
SCF3 Ground short circuit |
Cause: See SCF1.
Remedy:
|
SCF4 IGBT short circuit |
Cause: Internal power component short circuit detected at power-on.
Remedy:
- Contact your local Schneider Electric representative.
|
SOF Overspeed |
Cause:
- Instability.
- Overspeed associated with the inertia of the application.
Remedy:
- Check the motor.
- Overspeed is 10% more than Maximum frequency (tFr), so adjust this parameter if necessary.
- Add a braking resistor.
- Check the size of the motor/drive/load.
- Check parameters of the speed loop (gain and stability).
|
tnF Auto-tuning |
Cause:
- Motor not connected to the drive.
- One motor phase loss.
- Special motor.
- Motor is rotating (being driven by the load, for example).
Remedy:
- Check that the motor/drive are compatible.
- Check that the motor is present during auto-tuning.
- If an output contactor is being used, close it during auto-tuning.
- Check that the motor is completely stopped.
|
LFF1 AI current lost fault |
Cause: Detection if AI1 is current, scaling > 3 mA, and input < 2 mA.
Remedy:
- Check the terminal connection.
|
ObF Overbraking |
Cause: Braking too sudden or driving load too high.
Remedy:
- Increase the deceleration time.
- Install a module unit with a braking resistor if necessary.
- Check the line supply voltage.
|
OHF Drive overheat |
Cause: Drive temperature too high.
Remedy:
- Check the motor load, drive ventilation, and ambient temperature.
- Wait for the drive to cool down before restarting.
|
OLC Process overload |
Cause: Process overload.
Remedy:
- Check the process and the parameters of the drive to be in phase.
|
OLF Motor overload |
Cause: Triggered by excessive motor current.
Remedy:
- Check the setting of the motor thermal protection, check the motor load.
|
OPF1 1 output phase loss |
Cause: Loss of one phase at drive output.
Remedy:
- Check the connections from the drive to the motor.
- In case of using downstream contactor, check the right connection, cable and contactor.
|
OPF2 3 output phase loss |
Cause: Motor not connected, low power, contactor open, or instability.
Remedy:
- Check connections.
- Test on a low-power motor (set OPL = YES).
- To check without motor, deactivate OPL (= no).
- Check parameters: UFr, UnS, nCr, and perform Auto-tuning.
|
OSF Main overvoltage |
Cause: Line voltage too high or disturbed line supply.
Remedy:
- Check and adjust the line voltage.
- If intermittent, set Relay R1 to FLt and connect to upstream protection.
|
PHF Input phase loss |
Cause: Incorrect supply, blown fuse, phase failure, or unbalanced load.
Remedy:
- Check the power connection and the fuses.
- Use a 3-phase line supply.
- Disable the fault by setting IPL = no.
|
SCF5 Load short circuit |
Cause: Short-circuit at drive output or during run/DC injection.
Remedy:
- Check the cables connecting the drive to the motor, and the motor’s insulation.
|
SLF1 Modbus communication |
Cause: Interruption in communication on the Modbus network.
Remedy:
- Check connections of communication bus.
- Check time-out (ttO).
- Refer to the Modbus user manual.
|
SLF2 SoMove communication |
Cause: Communication interruption with SoMove.
Remedy:
- Check the SoMove connecting cable.
- Check the time-out.
|
SLF3 HMI communication |
Cause: Communication interruption with the external display terminal.
Remedy:
- Check the terminal connection.
|
SPIF PI Feedback detected fault |
Cause: PID feedback below lower limit.
Remedy:
- Check the PID function feedback.
- Check supervision threshold (LPI) and time delay (tPI).
|
ULF Process underload fault |
Cause: Process underload or motor current below threshold (LUL) for time (ULt).
Remedy:
- Check the process and the parameters of the drive to be in phase.
|
tJF IGBT overheat |
Cause: Drive overheated (IGBT temp too high).
Remedy:
- Check load size.
- Reduce Switching frequency (SFr).
- Wait for the drive to cool.
|
EPF1 External detected fault |
Cause: Event triggered by an external device.
Remedy:
- Check the device which caused the trip and reset.
|
CFF Incorrect configuration |
Cause: HMI block replaced with different rating or inconsistent parameters.
Remedy:
- Return to factory settings or retrieve valid backup.
- Contact Schneider Electric if fault remains.
|
CFI Invalid configuration |
Cause: Configuration loaded is inconsistent or upload interrupted.
Remedy:
- Check configuration loaded previously.
- Load a compatible configuration.
|
CFI2 Download invalid configuration |
Cause: Interruption of download operation (Loader/SoMove).
Remedy:
- Check connection.
- Restart download or restore factory setting.
|
USF Undervoltage |
Cause: Line supply too low or transient dip.
Remedy:
- Check voltage and Undervoltage Phase Loss Menu (USb) parameters.
|
InIt On initializing itself |
Description:
- Micro controller initializing.
- Communication configuration search.
|
Com.E Communication error (Flashing) |
Description:
- 50ms time-out error.
- Shown after 220 retry attempts.
|
A-17 Key alarm (Flashing) |
Description:
- Key pressed > 10s.
- Membrane switch disconnected.
- Keypad woken up while key pressed.
|
cLr Confirm Fault reset (Flashing) |
Description:
- Appears if STOP key is pressed when there is a keypad fault.
|
dEU.E Drive mismatch (Flashing) |
Description:
- Drive type (brand) did not match with keypad type.
|
rOM.E ROM abnormality (Flashing) |
Description:
- Keypad ROM abnormality detected by checksum.
|
rAM.E RAM abnormality (Flashing) |
Description:
- Keypad RAM abnormality detected.
|
CPU.E The other defect (Flashing) |
Description:
- The other detected fault.
|