Yaskawa L1000A Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| boL Braking Transistor Overload | Cause: The wrong braking resistor is installed (transistor reached overload level). Remedy:
|
| bUS Option Communication Error | Cause: Connection lost after initial communication, No signal from PLC, Faulty wiring, Noise, or Damaged option card. Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Communication data not received (Time set in H5-09), Faulty wiring, or Noise interference. Remedy:
|
| CF Control Fault | Cause: Torque limit reached continuously for 3 seconds (OLV Control), Improper motor parameters, or Load inertia too big. Remedy:
|
| CoF Current Offset Fault | Cause: Current sensor damaged or residual induction current in motor (e.g., during sudden deceleration). Remedy:
|
| CPF00 or CPF01 Control Circuit Error | Cause: Self-diagnostic error in control circuit or Connector on operator is damaged. Remedy:
|
| CPF02 A/D Conversion Error | Cause: Control circuit is damaged (A/D conversion error). Remedy:
|
| CPF03 Control Board Connection Error | Cause: Connection error between control board and drive, or Noise interference. Remedy:
|
| CPF06 EEPROM Memory Data Error | Cause: Error in EEPROM control circuit, or power lost while saving parameters. Remedy:
|
| CPF07 or CPF08 Terminal Board Connection Error | Cause: Faulty connection between terminal board and control board. Remedy:
|
| CPF11 to CPF14 CPF16 to CPF21 Control Circuit Error | Cause: Hardware is damaged (RAM/ROM/CPU errors). Remedy:
|
| CPF22 Hybrid IC Failure | Cause: Hybrid IC failure on the power board. Remedy:
|
| CPF23 Control Board Connection Error | Cause: Hardware is damaged (Connection error). Remedy:
|
| CPF24 Drive Unit Signal Fault | Cause: Hardware damaged (Drive capacity cannot be detected correctly). Remedy:
|
| CPF25 Terminal Board not Connected | Cause: Terminal board is not connected correctly. Remedy:
|
| CPF26 to CPF34 Control Circuit Error (CPU Error) | Cause: Hardware is damaged. Remedy:
|
| CPF35 A/D Conversion Error | Cause: A/D conversion damaged or Control circuit damaged. Remedy:
|
| dEv Speed Deviation | Cause: Load too heavy, Accel/decel too short, Load locked, Parameters F1-10/F1-11 set incorrectly, or Brake not applied. Remedy:
|
| dv1 Encoder Z Pulse Fault | Cause: Encoder not connected, wired improperly, or damaged. Remedy:
|
| dv2 Z Pulse Noise Fault Detection | Cause: Noise interference on encoder cable, Wiring improper, or Hardware damaged. Remedy:
|
| dv3 Inversion Detection | Cause: Encoder offset (E5-11) not set, External force moved load, Noise interference, or Phase order incorrect. Remedy:
|
| dv4 Inversion Prevention Detection | Cause: Encoder offset not set properly (E5-11), Noise interference, or Disconnected encoder. Remedy:
|
| dv6 Overacceleration Detection | Cause: Encoder offset (E5-11) incorrect, Noise, Incorrect motor data, or Acceleration too fast. Remedy:
|
| dv7 Rotor Polarity Detection Timeover | Cause: Battery low, Cable disconnected, Motor winding damaged, or Terminal loose. Remedy:
|
| dv8 PM Rotor Position Estimation Error | Cause: Motor characteristics changed, Initial Pole Search parameters incorrect, Brake released during search. Remedy:
|
| EF0 Option Card External Fault | Cause: External fault received from PLC, or PLC program problem. Remedy:
|
| EF3 to EF8 External Fault (Input Terminals S3 to S8) | Cause: External device tripped alarm, Wiring incorrect, or Incorrect multi-function input setting. Remedy:
|
| Err EEPROM Write Error | Cause: Noise corrupted data while writing to EEPROM, or Hardware problem. Remedy:
|
| FrL Speed Reference Missing | Cause: Parameter d1-18 set incorrectly, or no speed selected at start. Remedy:
|
| GF Ground Fault | Cause: Motor insulation damaged, Motor cable short circuit, Leakage current too high, or Hardware problem. Remedy:
|
| LF Output Phase Loss | Cause: Output cable disconnected, Motor winding damaged, Terminal loose, or Single-phase motor used. Remedy:
|
| LF2 Output Current Imbalance | Cause: Phase loss on output side, Loose terminals, Output circuit damaged, or Motor impedance uneven. Remedy:
|
| oC Overcurrent | Cause: The motor has been damaged due to overheating or the motor insulation is damaged. Remedy:
Cause: One of the motor cables has shorted out or there is a grounding problem. Remedy:
Cause: The drive is damaged. Remedy:
Cause: The load is too heavy. Remedy:
Cause: Accel/decel ramp is too fast. Remedy:
|
| oFA00 Option Card Connection Error (CN5-A) | Cause: The option card installed into port CN5-A is incompatible with the drive. Remedy:
Cause: A PG option card is connected to option port CN5-A. Remedy:
|
| oFA01 Option Card Fault (CN5-A) | Cause: The option board connection to port CN5-A is faulty. Remedy:
|
| oFA05, oFA06, oFA10-oFA17, oFA30-oFA43 Option card error at CN5-A | Cause: Option card or hardware is damaged. Remedy:
|
| oFb00 Option Card Fault (CN5-B) | Cause: The option card installed into port CN5-B is incompatible with the drive. Remedy:
Cause: A communication option card has been installed in option port CN5-B. Remedy:
|
| oFb01 Option Card Fault (CN5-B) Not Connected | Cause: The option board connection to port CN5-B is faulty. Remedy:
|
| oFb02 Option Card Fault (CN5-B) Duplicate | Cause: An option card of the same type is already installed in option port CN5-A. Remedy:
|
| oFb03 to oFb17 Option card error at CN5-B | Cause: Option card or hardware is damaged. Remedy:
|
| oFC00 Option Card Connection Error (CN5-C) | Cause: The option card installed into port CN5-C is incompatible with the drive. Remedy:
Cause: A communication option card has been installed in option port CN5-C. Remedy:
|
| oFC01 Option Card Fault (CN5-C) | Cause: The option board connection to port CN5-C is faulty. Remedy:
|
| oFC02 Option Card Fault (CN5-C) Duplicate | Cause: Three PG option boards are installed. Remedy:
|
| oFC50 Encoder Option AD Conversion Error | Cause: The PG option card is damaged. Remedy:
|
| oFC51 Encoder Option Analog Circuit Error | Cause: The PG option card is damaged. Remedy:
|
| oFC52 Encoder Communication Timeout | Cause: Encoder cable wiring is wrong or disconnected. Remedy:
Cause: Parameters for Encoder Selection (F1-50) are set to the wrong values. Remedy:
|
| oFC53 Encoder Communication Data Error | Cause: Encoder cable wiring is wrong or disconnected. Remedy:
|
| oFC54 Encoder Error | Cause: Power supply to encoder is wired incorrectly. Remedy:
Cause: The power supply circuit of the PG option card is damaged. Remedy:
|
| oH Heatsink Overheat (Pre-alarm) | Cause: Surrounding temperature is too high. Remedy:
Cause: Load is too heavy. Remedy:
Cause: Internal cooling fan is stopped. Remedy:
|
| oH1 Heatsink Overheat (Fault) | Cause: Surrounding temperature is too high. Remedy:
Cause: Load is too heavy. Remedy:
|
| oH3 Motor Overheat Alarm (PTC) | Cause: Motor thermostat wiring is faulty. Remedy:
Cause: Motor has overheated. Remedy:
|
| oH4 Motor Overheat Fault (PTC) | Cause: Motor thermostat wiring is faulty. Remedy:
Cause: Motor has overheated. Remedy:
|
| oL1 Motor Overload | Cause: Load is too heavy. Remedy:
Cause: Cycle times are too short during acceleration/deceleration. Remedy:
Cause: Output voltage is too high. Remedy:
Cause: The wrong motor rated current is set to E2-01. Remedy:
|
| oL2 Drive Overload | Cause: Load is too heavy. Remedy:
Cause: Accel/decel ramp is too short. Remedy:
Cause: Drive capacity is too small. Remedy:
|
| oL3 Overtorque Detection 1 | Cause: Parameter settings are not appropriate for the load. Remedy:
Cause: Fault on the machine side (e.g., machine is locked up). Remedy:
|
| oL4 Overtorque Detection 2 | Cause: Parameter settings are not appropriate for the load. Remedy:
|
| oPr External Operator Connection Fault | Cause: External operator is not properly connected to the drive. Remedy:
|
| oS Overspeed | Cause: Overshoot is occurring. Remedy:
Cause: Inappropriate parameter settings. Remedy:
|
| ov DC Bus Overvoltage | Cause: Deceleration ramp is too short and regenerative energy is flowing back. Remedy:
Cause: Surge voltage entering from drive input power. Remedy:
Cause: Ground fault in the output circuit. Remedy:
Cause: Drive input power voltage is too high. Remedy:
|
| PF Input Phase Loss | Cause: There is phase loss in the drive input power. Remedy:
Cause: There is loose wiring in the drive input power terminals. Remedy:
Cause: The main circuit capacitors are worn. Remedy:
|
| PF5 Rescue Operation Power Supply Error | Cause: During Rescue Operation, DC bus voltage dropped too low. Remedy:
|
| PGo Encoder Disconnected (Control Mode with Encoder) | Cause: Encoder cable disconnected, wrong wiring, no power, or motor brake not released. Remedy:
|
| PGoH Encoder Disconnected (detected when using an encoder) | Cause: Encoder cable is not connected properly. Remedy:
|
| rF Braking Resistor Fault | Cause: Resistance of braking resistor is too low, proper option not installed, or wiring issue with regenerative unit. Remedy:
|
| rr Dynamic Braking Transistor Fault | Cause: The built-in dynamic braking transistor or control circuit is damaged. Remedy:
|
| SC IGBT Short Circuit | Cause: IGBT fault, short circuit/ground fault, or drive damage. Remedy:
|
| SCF Safety Circuit Fault | Cause: The safety circuit is damaged. Remedy:
|
| SE1 Motor Contactor Response Error | Cause: Problem with motor contactor or auxiliary switch. Remedy:
|
| SE2 Starting Current Error | Cause: The motor contactor is open (current lower than 25% of no-load current at start). Remedy:
|
| SE3 Output Current Error | Cause: The motor contactor opened during operation. Remedy:
|
| SE4 Brake Feedback Error | Cause: Feedback contact defective, wiring incorrect, brake control circuit fail, or contactor open. Remedy:
|
| SvE Position Lock Error | Cause: Torque limit too low, excessive load torque, or noise interference. Remedy:
|
| STo Motor Pull Out or Step Out Detection | Cause: Wrong motor code, load too heavy, or accel/decel ramp too short. Remedy:
|
| UL3 Undertorque Detection 1 | Cause: Parameter settings inappropriate or fault on machine side. Remedy:
|
| UL4 Undertorque Detection 2 | Cause: Parameter settings inappropriate or fault on machine side. Remedy:
|
| Uv1 DC Bus Undervoltage | Cause: Input phase loss, loose terminals, voltage problem, power interrupt, worn capacitors, or soft-charge relay damage. Remedy:
|
| Uv2 Control Power Supply Voltage Fault | Cause: Control power supply wiring damaged or internal circuitry damaged. Remedy:
|
| Uv3 Soft-Charge Bypass Circuit Fault | Cause: The relay or contactor on the soft-charge bypass circuit is damaged. Remedy:
|
| voF Output Voltage Detection Error | Cause: Hardware is damaged. Remedy:
|
| AEr Communication Option Node ID Setting Error (CANopen) | Cause: Option card node address is outside the acceptable setting range. Remedy:
|
| bb Baseblock | Cause: Drive output interrupted as indicated by an external baseblock signal (entered via multi-function input terminals S3 to S8). Remedy:
|
| boL Braking Transistor Overload | Cause: The braking transistor in the drive has been overloaded (proper braking resistor not installed). Remedy:
|
| bUS Option Communication Error | Cause: Connection broken, master controller stopped, option card damaged, or data error due to noise. Remedy:
|
| CALL Serial Communication Stand By | Cause: Communication has not yet been established. Could be faulty wiring, programming error on master side, or damaged circuitry. Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Control data was not received correctly for two seconds (noise, incompatible protocol, or hardware problem). Remedy:
|
| CrST Cannot Reset | Cause: A fault reset command was entered while the Up/Down command was still present. Remedy:
|
| dEv Speed Deviation (using PG option card) | Cause: Deviation between speed reference and feedback is greater than setting in F1-10 for longer than time in F1-11. Remedy:
|
| EF Up/Down Command Error | Cause: Both forward run and reverse run closed simultaneously for over 0.5 s. Remedy:
|
| EF0 Option Card External Fault | Cause: An external fault condition is present (received from PLC). Remedy:
|
| EF3 External fault (input terminal S3) | Cause: External fault at multi-function input terminal S3. Remedy:
|
| EF4 External fault (input terminal S4) | Cause: External fault at multi-function input terminal S4. Remedy:
|
| EF5 External fault (input terminal S5) | Cause: External fault at multi-function input terminal S5. Remedy:
|
| EF6 External fault (input terminal S6) | Cause: External fault at multi-function input terminal S6. Remedy:
|
| EF7 External fault (input terminal S7) | Cause: External fault at multi-function input terminal S7. Remedy:
|
| EF8 External fault (input terminal S8) | Cause: External fault at multi-function input terminal S8. Remedy:
|
| Hbb Safe Disable Circuit Fault Signal | Cause: Both Safe Disable Input channels are open (H1 and H2). Remedy:
|
| HbbF Safe Disable Circuit Fault Signal (One Channel) | Cause: One Safe Disable channel is open while the other is closed. Remedy:
|
| HCA High Current Alarm | Cause: Drive current exceeded overcurrent warning level (150% of rated current). Load too heavy or ramp too short. Remedy:
|
| LT-1 Cooling Fan Maintenance Time | Cause: The cooling fan has reached 90% of its expected performance life. Remedy:
|
| LT-2 Capacitor Maintenance Time | Cause: The main circuit and control circuit capacitors have reached 90% of their expected performance life. Remedy:
|
| LT-3 Soft Charge Bypass Relay Maintenance Time | Cause: The DC bus soft charge relay has reached 90% of expected performance life. Remedy:
|
| LT-4 IGBT Maintenance Time (90%) | Cause: IGBTs have reached 90% of their expected performance life. Remedy:
|
| oH Heatsink Overheat | Cause: Heatsink temperature exceeded pre-alarm level (L8-02). Surrounding temp too high, fan stopped, or airflow restricted. Remedy:
|
| oH3 Motor Overheat Alarm (PTC thermistor input) | Cause: Motor overheat signal to A1/A2 exceeded alarm level, wiring fault, or machine locked up. Remedy:
|
| oL3 Overtorque Detection 1 | Cause: Drive output current/torque greater than L6-02 for time set in L6-03. Remedy:
|
| oL4 Overtorque Detection 2 | Cause: Drive output current/torque greater than L6-05 for time set in L6-06. Remedy:
|
| oS Overspeed (Control Mode with Encoder) | Cause: Motor speed feedback exceeded the F1-08 setting. Remedy:
|
| ov DC Bus Overvoltage | Cause: DC bus voltage exceeded trip point (Surge voltage, short-circuit, or noise). Remedy:
|
| PASS MEMOBUS/Modbus Communication Test Mode Complete | Cause: MEMOBUS/Modbus test has finished normally. Remedy:
|
| PGo Encoder Disconnected | Cause: No encoder signal received for time longer than F1-14 setting. Cable disconnected, wiring wrong, or insufficient power. Remedy:
|
| PGoH Encoder Disconnected (detected when using encoder) | Cause: Encoder cable has become disconnected. Remedy:
|
| SE MEMOBUS/Modbus Self Test Failed | Cause: A digital input set to 67H was closed while the drive was running. Remedy:
|
| TrPC IGBT Maintenance Time (90%) | Cause: IGBTs have reached 90% of their expected performance life. Remedy:
|
| UL3 Undertorque Detection 1 | Cause: Drive output current/torque less than L6-02 for longer than L6-03 time. Remedy:
|
| UL4 Undertorque Detection 2 | Cause: Drive output current/torque less than L6-05 for longer than L6-06 time. Remedy:
|
| Uv Undervoltage | Cause: DC bus voltage dropped below level specified in L2-05. Phase loss, loose wiring, or internal circuitry worn. Remedy:
|
| voF Output Voltage Detection Error | Cause: Hardware is damaged. Remedy:
|
| oPE01 Drive Capacity Setting Fault | Cause: The drive model selection (o2-04) and the actual capacity of the drive are not the same. Remedy:
|
| oPE02 Parameter Range Setting Error | Cause: Parameters were set outside the possible setting range. Remedy:
|
| oPE03 Multi-function Digital Input Selection Error | Cause: A contradictory setting is assigned to multi-function contact inputs H1-03 to H1-08 (e.g., same function assigned twice, or specific Brake Feedback conflicts). Remedy:
|
| oPE04 Terminal Board Mismatch Error | Cause: The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match. Remedy:
|
| oPE05 Reference Source Selection Error | Cause: Speed reference/Up-Down command is assigned to an option card (b1-01/02 = 3) but no card is connected, or Digital card input data length (F3-03) is incorrect for BCD special (F3-01=6). Remedy:
|
| oPE06 Control Mode Selection Error | Cause: A control mode has been selected that requires a PG option card to be installed, but no option card is installed (A1-02 = 3 or 7). Remedy:
|
| oPE07 Multi-function Analog Input Selection Error | Cause: At least two analog input terminals are set to the same function (i.e., parameters H3-02 and H3-10 have the same setting). Remedy:
|
| oPE08 Parameter Selection Error | Cause: Attempted to use a function not valid for the selected control mode, or n2-02 > n2-03 in Open Loop Vector, or b1-14=1 (Switch phase order) while using a PG option card. Remedy:
|
| oPE10 V/f Pattern Setting Error | Cause: The V/f pattern frequency settings are incorrect (Logic required: E1-04 ≥ E1-06 ≥ E1-07 ≥ E1-09 ≥ E1-11). Remedy:
|
| oPE16 Energy Savings Constants Error | Cause: Energy saving coefficients are out of the allowable range. Remedy:
|
| oPE18 Parameter Setting Error, Online Tuning Parameter Setting Error | Cause: Load cell conflicts (S3-29 = S3-30), Dwell 2 speed logic errors, or Open Loop Vector Online Tuning parameters (E2-02, E2-06, E2-03) are set incorrectly. Remedy:
|
| oPE20 PG-F3 Setting Error | Cause: The encoder signal frequency is too high. With the entered resolution (F1-01) and max output frequency (E1-04), the calculation exceeds 50 kHz (PG-F3) or 20 kHz (PG-E3). Remedy:
|
| oPE21 Elevator Parameter Setting Fault | Cause: Elevator parameters are not set correctly (DC Injection time < Brake Close delay, Decel/Stop distances set lower than minimums, or S5-10 and S5-01 enabled simultaneously). Remedy:
|
| End1 Excessive V/f Setting | Cause: The torque reference exceeded 20% during Auto-Tuning OR the results from Auto-Tuning the no-load current exceeded 80%. Remedy:
|
| End2 Motor Iron-Core Saturation Coefficient | Cause: Motor data entered during Auto-Tuning was incorrect OR results are outside the parameter setting range. Remedy:
|
| End3 Rated Current Setting Alarm | Cause: The correct current rating printed on the nameplate was not entered into T1-04. Remedy:
|
| End4 Adjusted Slip Calculation Error | Cause: The slip that was calculated is outside the allowable range. Remedy:
|
| End5 Resistance Tuning Error | Cause: The resistance value that was calculated is outside the allowable range. Remedy:
|
| End6 Leakage Inductance Alarm | Cause: A1-02 setting error OR the leakage inductance value calculated is outside the allowable range. Remedy:
|
| End7 No-Load Current Alarm | Cause: The entered no-load current value was outside the allowable range OR Auto-Tuning results were less than 5% of the motor rated current. Remedy:
|
| End8 Rescue Operation Speed Warning | Cause: High frequency injection calculations for the battery power supply were below 10 Hz. Remedy:
|
| End9 Rescue Operation Rotor Pole Position Search Warning | Cause: While operating from the backup battery, pole diversion exceeded 40 degrees. Remedy:
|
| End10 Rescue Operation Rotor Polarity Detection Warning | Cause: While operating from the backup battery, the Id value between poles was less than 5%. Remedy:
|
| Er-01 Motor Data Error | Cause: Motor data entered incorrect, capacity mismatch, or base freq/speed mismatch. Remedy:
|
| Er-02 Alarm | Cause: An alarm was triggered during Auto-Tuning. Remedy:
|
| Er-03 STOP Button Input | Cause: Auto-Tuning canceled by pressing STOP button. Remedy:
|
| Er-04 Line-to-Line Resistance Error | Cause: Motor data incorrect, result out of range, or cable fault. Remedy:
|
| Er-05 No-Load Current Error | Cause: Motor data incorrect, result out of range, or load too high during tuning. Remedy:
|
| Er-08 Rated Slip Error | Cause: Data incorrect, calculation timed out, or load too high. Remedy:
|
| Er-09 Acceleration Error | Cause: Motor did not accelerate (ramp too short), torque limit too low, or load too high. Remedy:
|
| Er-10 Motor Direction Error | Cause: Encoder lines not connected properly, Motor/PG direction opposite, or load pulled motor. Remedy:
|
| Er-11 Motor Speed Fault | Cause: Torque reference is too high. Remedy:
|
| Er-12 Current Detection Error | Cause: Phase missing, current too high/low, or signal error. Remedy:
|
| Er-13 Leakage Inductance Error | Cause: Unable to complete tuning within 300 seconds. Remedy:
|
| Er-18 Induction Voltage Error | Cause: Induced voltage constant outside allowable range. Remedy:
|
| Er-19 Inductance Error | Cause: Induced voltage constant attempted to set value to E5-08 or E5-09 outside range. Remedy:
|
| Er-20 Stator Resistance Error | Cause: Attempted to set E5-06 outside allowable range. Remedy:
|
| Er-21 Z Pulse Correction Error | Cause: Motor coasting, wiring issue, encoder direction/pulses wrong, encoder damaged, or PG-E3 error. Remedy:
|
| Er-22 Initial Rotor Pole Search Error | Cause: Parameters outside range or pole diversion exceeded 20 degrees. Remedy:
|
| Er-23 Non-rotating Encoder Offset Tuning Warning | Cause: Pole diversion exceeded 15 degrees three times. Remedy:
|
| Er-24 Auto-Tuning Error for PG-E3 Encoder Characteristics | Cause: Signal lines disconnected, electrical interference, or unsupported software version. Remedy:
|
| CoPy Writing Parameter Settings (flashing) | Cause: Parameters are being written to the drive. Remedy: Not an error. |
| CPEr Control Mode Mismatch | Cause: Control mode of the parameters to be loaded onto the drive and the control mode already set to the drive don’t match. Remedy: Check the control mode for the parameters that are to be loaded onto the drive and the control mode set to the drive those parameters will be written to. Set the same control mode using parameter A1-02 and try again. |
| CPyE Error Writing Data | Cause: Failed writing parameters. Remedy: Try writing parameters again. |
| CSEr Copy Unit Error | Cause: Hardware fault. Remedy: Replace the operator or the USB Copy Unit. |
| dFPS Drive Model Mismatch | Cause:
Remedy: Check the model number of the drive from which the parameters were copied and the model of the drive to which you are attempting to write the parameters. Make sure the two drives are the same model and have the same software version. |
| ECE Copy Error | Cause: Attempted to read data from the encoder during undervoltage. Remedy: Make sure there is no undervoltage fault or alarm, then try reading the data again. |
| ECS Checksum Error | Cause: Checksum error occurred when attempting to read data from the encoder. Remedy: Try copying the data again. |
| EdE Write Impossible | Cause: Drive settings do not permit writing to the encoder (F1-51 = 0), or there was a CPF24 while attempting to write to the encoder. Remedy: Set the drive to allow encoder to be written to (F1-51 = 1) and try writing the data again. |
| EiF Write Data Error | Cause: Communication error occurred while attempting to write to the encoder. Remedy: Make sure communications are normal and try writing to the encoder again. |
| End Task Complete | Cause: Finished reading, writing, or verifying parameters. Remedy: Not an error. |
| EPE ID Mismatch | Cause: Attempted to acquire machine data from an encoder that does not have any machine data written to it yet. Remedy: Try again after writing machine data to the encoder. |
| ErE Data Error | Cause: Attempted to write data to the encoder during undervoltage. Remedy: Make sure there is no undervoltage fault or alarm and try again. |
| EvE Verify Error | Cause: Drive parameters and the data saved to the encoder do not match. Remedy: Use the Verify Menu to check parameter settings and try again. |
| iFEr Communication Error | Cause:
Remedy:
|
| ndAT Model, Voltage Class, Capacity Mismatch | Cause:
Remedy:
|
| rdEr Error Reading Data | Cause: Failed while attempting to read parameter settings from the drive. Remedy: Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read parameters from the drive. |
| rEAd Reading Parameter Settings (flashing) | Cause: Displayed while the parameter settings are being read onto the USB Copy Unit. Remedy: Not an error. |
| vAEr Voltage Class, Capacity Mismatch | Cause: The drive the parameters were copied from and the drive you performing the Verify mode on have different electrical specifications or are a different capacity. Remedy: Make sure electrical specifications and capacities are the same for both drives. |
| vFyE Parameter settings in the drive and those saved to the copy function are not the same | Cause: Indicates that parameter settings that have been Read and loaded onto the Copy Unit or Digital Operator are different. Remedy: To synchronize parameters, either write the parameters saved on the USB Copy Unit or LCD digital operator onto the drive, or Read the parameter settings on the drive onto the USB Copy Unit. |
| vrFy Comparing Parameter Settings (flashing) | Cause: The Verify mode has confirmed that parameters settings on the drive and parameters read to the copy device are identical. Remedy: Not an error. |