Aov
Power Supply Overvoltage |
Cause:
The input power supply voltage is too high.
(200 V Class: > 277 Vac, 400 V Class: > 554 Vac)
Remedy:
- Reduce the voltage to within the range in the power supply specifications.
|
AUv
Power Supply Undervoltage |
Cause:
- The capacity of the power supply is too small.
- The AC fuse is open.
- A transistor inside the regenerative unit was destroyed.
- Input wiring or drive output is ground-faulted/short-circuited.
- Distortion in power supply is too large.
- Phase loss in input power supply.
Remedy:
- Increase the capacity of the power supply.
- Lower the impedance of the input power supply wiring.
- Check input power for phase loss or imbalance.
- Consult with your Yaskawa representative if transistor is destroyed.
|
bUS
Option Communication Error |
Cause:
- No signal was received from the PLC.
- Faulty communications wiring or existing short circuit.
- Communication data error occurred due to noise.
- The option card is damaged or not properly connected.
Remedy:
- Check for faulty wiring, disconnected cables, or short circuits.
- Counteract noise (grounding, shielding, surge absorbers).
- Install an EMC noise filter.
- Reinstall or replace the option card.
|
CE
MEMOBUS/Modbus Communication Error |
Cause:
- Control data was not received for the CE detection time set to H5-09.
- Faulty communications wiring or short circuit.
- Communication data error due to noise.
Remedy:
- Check wiring and correct if necessary.
- Counteract noise in control/main circuit and ground wiring.
- Use shielded lines and separate communication wiring from drive power lines.
|
CoF
Current Offset Fault |
Cause:
An error occurred in the power supply detection circuit during adjustment of automatic current offset.
Remedy:
- Cycle the power supply and check operation.
- If fault occurs again, replace the board or regenerative unit.
|
CPF00, CPF01 CPF11 to CPF22 CPF26 to CPF35
Control Circuit Error |
Cause:
There is a self-diagnostic error in the control circuit.
Remedy:
- Cycle power to the regenerative unit.
- If problem continues, replace the control board or entire regenerative unit.
|
CPF02
A/D Conversion Error |
Cause:
Control circuit is damaged (A/D conversion error).
Remedy:
- Cycle power to the regenerative unit.
- If problem continues, replace the control board or entire regenerative unit.
|
CPF03
Control Board Connection Error |
Cause:
There is a connection error between the control board and the regenerative unit.
Remedy:
- Turn off power and check the connection between the control board and unit.
- If problem continues, replace the control board or entire unit.
|
CPF06
EEPROM Memory Data Error |
Cause:
- There is an error in EEPROM control circuit.
- The power supply was switched off while parameters were being saved.
Remedy:
- Turn off power, check connections, or replace control board.
- Reinitialize the regenerative unit (A1-03 = 2220, 3330).
|
CPF07, CPF08
Terminal Board Connection Error |
Cause:
There is a faulty connection between the terminal board and the control board.
Remedy:
- Turn off the power and reconnect the terminal board.
- If problem continues, replace the control board or entire unit.
|
CPF23
Control Board Connection Error |
Cause:
Hardware is damaged (Connection error).
Remedy:
- Turn off power and check connection between control board and unit.
- If problem continues, replace the control board or entire unit.
|
CPF24
Unit Capacity Detect Fault |
Cause:
Hardware is damaged (Regenerative unit capacity cannot be detected correctly).
Remedy:
- If problem continues, replace the control board or entire unit.
|
E5
MECHATROLINK Watchdog Timer Error |
Cause:
Data has not been received from the PLC (Watchdog timed out).
Remedy:
- Execute DISCONNECT or ALM_CLR.
- Issue a CONNECT command or SYNC_SET command.
- Refer to MECHATROLINK Option Technical Manual.
|
EF0
Option Card External Fault |
Cause:
- An external fault was received from the PLC.
- Problem with the PLC program.
Remedy:
- Remove the cause of the external fault.
- Check the PLC program and correct problems.
|
EF1 to EF8
External Fault (Input terminals S1-S8) |
Cause:
- An external device tripped an alarm function.
- Wiring is incorrect.
- Multi-function contact input setting is incorrect.
Remedy:
- Remove the cause of the external fault and reset.
- Properly connect signal lines (H1-xx = 20 to 2B).
- Check for unused terminals set for External Fault.
|
Err
EEPROM Write Error |
Cause:
- Electrical noise has corrupted data while writing to EEPROM.
- Hardware problem.
Remedy:
- Press “ENTER”, correct parameter setting, and cycle power.
- If problem continues, replace control board or unit.
|
Fan
Internal Circulation Fan Fault |
Cause:
Internal circulation fan malfunctioned (Fan or magnetic contactor failure).
Remedy:
- Cycle power to the regenerative unit.
- Check fan operation and cumulative operation time (U4-03, U4-04).
- Replace cooling fan if damaged or life exceeded.
|
Fdv
Power Supply Frequency Fault |
Cause:
- A momentary power loss occurred.
- Input power supply wiring terminal is loose.
- Fluctuation in voltage is too large.
- The AC power supply fuse is open.
Remedy:
- Investigate/correct cause and reset fault.
- Check wiring and ground faults.
- Consult Yaskawa if transistor is destroyed.
|
FUA
AC Fuse Blowout |
Cause:
The power supply fuse is open (Transistor destroyed or short circuit).
Remedy:
- Check input wiring or drive output for shorts/ground faults.
- Contact Yaskawa representative.
|
FUd
DC Fuse Blowout |
Cause:
- The main transistor failed.
- The drive failed.
Remedy:
- Replace the regenerative unit.
- Replace the drive (consult Yaskawa).
|
nSE
Node Setup Error |
Cause:
- The node setup terminal closed during run.
- A Run command was issued while the node setup function was active.
Remedy:
- Stop the regenerative unit when using the node setup function.
|
oC
Overcurrent |
Cause:
- A momentary power loss occurred.
- One of the cables has shorted out or there is a grounding problem.
- The load is too heavy.
- Noise interference.
- Incorrect wiring of power supply voltage detection circuits.
- Voltage on power supply side is very low.
Remedy:
- Check motor cables and remove short circuits.
- Measure current; if too high, replace with larger capacity unit.
- Review noise interference handling options.
- Correct wiring (r1/l11, s1/l21, t1/l31).
|
oFA00 Option Card Connection Error at Option Port CN5-A |
Cause: Option compatibility error. The option card installed into port CN5-A is incompatible with the regenerative unit.
Remedy:
- Check if the regenerative unit supports the option card to be installed.
- Contact Yaskawa for assistance.
|
oFA01 Option Card Fault at Option Port CN5-A |
Cause: Option not properly connected. The option card connection to port CN5-A is faulty.
Remedy:
- Turn off the power and reconnect the option card.
|
oFA05 to oFA06 oFA10, oFA11 oFA12 to oFA17 oFA30 to oFA43 Option Card Error (CN5-A) |
Cause: There is a fault in the option card. Option card or hardware is damaged.
Remedy:
- Cycle power to the regenerative unit.
- If the problem continues, replace the control board or the entire regenerative unit.
- Contact Yaskawa or a Yaskawa representative for instructions on replacing the control board.
|
oFb00 Option Card Fault at Option Port CN5-B |
Cause: Option compatibility error. The option card installed into port CN5-B is incompatible with the regenerative unit.
Remedy:
- Make sure the regenerative unit supports the option card to be installed.
- Contact Yaskawa for assistance.
|
oFb01 Option Card Fault at Option Port CN5-B |
Cause: Option not properly connected. The option card connection to port CN5-B is faulty.
Remedy:
- Turn off the power and reconnect the option card.
|
oFb02 Option Card Fault at Option Port CN5-B |
Cause: Same type of option card is currently connected. An option card of the same type is already installed in option port CN5-A.
Remedy:
- Only one of each option card type can be installed simultaneously.
- Make sure only one type of option card is connected.
|
oFb03 to oFb11 oFb12 to oFb17 Option Card Error at Option Port CN5-B |
Cause: There is a fault in the option card. Option card or hardware is damaged.
Remedy:
- Cycle power to the regenerative unit.
- If the problem continues, replace the control board or the entire regenerative unit.
- Contact Yaskawa or a Yaskawa representative for instructions on replacing the control board.
|
oFC00 Option Card Connection Error at Option Port CN5-C |
Cause: Option compatibility error. The option card installed into port CN5-C is incompatible with the regenerative unit.
Remedy:
- Confirm that the regenerative unit supports the option card to be installed.
- Contact Yaskawa for assistance.
|
oFC01 Option Card Fault at Option Port CN5-C |
Cause: Option not properly connected. The option card connection to port CN5-C is faulty.
Remedy:
- Turn the power off and reconnect the option card.
|
oFC02 Option Card Fault at Option Port CN5-C |
Cause: Same type of option card is currently connected. An option card of the same type is already installed in option port CN5-A or CN5-B.
Remedy:
- Only one of each option card type can be installed simultaneously.
- Make sure only one type of option card is connected.
|
oFC03 to oFC11 oFC12 to oFC17 Option Card Error at Option Port CN5-C |
Cause: There is a fault in the option card. Option card or hardware is damaged.
Remedy:
- Cycle power to the regenerative unit.
- If the problem continues, replace the control board or the entire regenerative unit.
- Contact Yaskawa or a Yaskawa representative for instructions on replacing the control board.
|
oFC50 to oFC55 Option Card Error at Option Port CN5-C |
Cause: Option card is damaged. Option card or hardware is damaged.
Remedy:
- Refer to the option manual for details.
|
oH Heatsink Overheat |
Cause: The heatsink temperature exceeded the overheat pre-alarm level set to L8-02.
- Surrounding temperature is too high.
- Load is too heavy.
- Internal cooling fan is stopped.
Remedy:
- Check the temperature surrounding the regenerative unit (verify it is within specifications).
- Improve the air circulation within the enclosure panel.
- Install a fan or air conditioner to cool the surrounding area.
- Remove anything near the unit producing excessive heat.
- Measure the output current and decrease the load.
- Replace the cooling fan.
- After replacing the fan, set parameter o4-03 to 0 to reset maintenance.
|
oH1 Overheat 1 |
Cause: The heatsink temperature exceeded the regenerative unit overheat level.
- Surrounding temperature is too high.
- Load is too heavy.
- Internal cooling fan is stopped.
Remedy:
- Check the temperature surrounding the regenerative unit.
- Improve the air circulation within the enclosure panel.
- Install a fan or air conditioner to cool the surrounding area.
- Measure the output current and reduce the load.
- Replace the cooling fan.
- After replacing the fan, set parameter o4-03 to 0 to reset maintenance.
|
oL2 Overload |
Cause: The thermal sensor of the regenerative unit triggered the unit overload protection.
- Load is too heavy.
- Regenerative unit capacity is too small.
- The regenerative unit does not operate properly.
Remedy:
- Reduce the load.
- Replace the regenerative unit with a larger model.
- Start regenerative unit operation first, and then start drive operation.
|
oPr External Digital Operator Connection Fault |
Cause: The external operator has been disconnected from the regenerative unit. External operator is not properly connected.
Remedy:
- Check the connection between the operator and the regenerative unit.
- Replace the cable if damaged.
- Turn off the input power, disconnect the operator, reconnect it, and reapply power.
|
ov Overvoltage |
Cause: Voltage in the DC bus has exceeded the overvoltage detection level (200V class: ~410V, 400V class: ~820V).
- A momentary power loss occurred.
- The regenerative load is too large.
- Input power voltage is too high.
- Unit fails to operate due to noise interference.
- Wiring of power supply voltage detection circuits or main circuit terminals is incorrect.
Remedy:
- Investigate and correct the cause and reset the fault.
- Reduce the regenerative load.
- Check the voltage and lower input power voltage within limits.
- Review possible solutions for controlling noise (check ground wiring, etc.).
- Correct the wiring.
|
PF2 Input Power Supply Fault |
Cause: Abnormal oscillation in the main circuit DC bus continued.
- Fluctuation in voltage of input power supply is too large.
- Phase loss in input power supply.
- Capacity of power supply is too small.
- Wiring is too long or phase imbalance is too large.
Remedy:
- Investigate and correct the cause and reset the fault.
|
PF3 Input Phase Loss Detection |
Cause: The voltage balance in the three-phase power supply has broken down.
- Fluctuation in voltage of input power supply is too large.
- Phase loss in input power supply.
- Capacity of power supply is too small.
- Wiring is too long or phase imbalance is too large.
Remedy:
- Investigate and correct the cause and reset the fault.
|
SC Input Short-circuit / Main Transistor Failure |
Cause: Short circuit or ground fault is detected.
- IGBT fault.
- IGBT short circuit detection circuit fault.
Remedy:
- Check the wiring to the drive.
- Turn the power supply off and then on again to check operation.
- If the problem continues, contact your Yaskawa representative.
|
SRC Phase Order Fault |
Cause: The phase order detection direction for the input power supply changed after power was turned on.
- Power supply phase order changed during operation.
- Momentary power loss occurred.
- Input power supply wiring terminal is loose.
- Fluctuation in voltage is too large.
Remedy:
- Investigate and correct the cause and reset the fault.
|
Uv1 Main Circuit Undervoltage |
Cause: DC voltage became equal to or lower than the set value (L2-05).
- Phase loss in input power supply.
- Input power supply wiring terminal is loose.
- Fluctuation occurred in power supply voltage.
- A power loss occurred.
- Main circuit capacitor has deteriorated.
- Relay or contactor in inrush current protection circuit failed.
- Fault occurred in power supply device/wiring.
Remedy:
- Check main circuit power supply wiring for broken wires/mistakes.
- Check terminals for looseness and tighten.
- Check voltage and correct it to be within specifications.
- Check magnetic contactor in the main circuit.
- Improve the power supply.
- Check maintenance period for capacitor (U4-05) and replace if needed.
- Cycle power; if fault persists, replace board/unit.
- Check maintenance period for inrush prevention relay (U4-06).
|
Uv2 Control Power Supply Voltage Fault |
Cause: Voltage is too low for the control regenerative unit input power. Internal circuitry is damaged.
Remedy:
- Cycle power to the regenerative unit. Check if the fault reoccurs.
- If the problem continues, replace either the control board or the entire regenerative unit.
|
Uv3 Undervoltage 3 (Soft-Charge Bypass Circuit Fault) |
Cause: The soft-charge bypass circuit failed. The relay or contactor on the soft-charge bypass circuit is damaged.
Remedy:
- Cycle power to the regenerative unit and see if the fault reoccurs.
- If the problem continues, replace either the control board or the entire regenerative unit.
- Check monitor U4-06 for the performance life of the soft-charge bypass.
- Replace control board/unit if U4-06 exceeds 90%.
|
AEr
Communication Option Station Number Setting Error (CC-Link, CANopen, MECHATROLINK) |
Cause: Station number is set outside the possible setting range.
Remedy:
Set the station number of the option card correctly.
|
Aov
Power Supply Overvoltage |
Cause: The input power supply voltage is too high.
Remedy:
Reduce the voltage to within the range in the power supply specifications.
|
AUv
Power Supply Undervoltage |
Cause:
- The power supply voltage is low.
- A phase loss occurred in the input power supply.
- Voltage detection failed.
Remedy:
- Increase the power supply voltage.
- Check the input power supply for phase loss or an imbalance in the interphase voltages. Investigate and correct the cause and reset the fault.
- Correctly wire r1/ℓ11, ℓ1/ℓ21, and t1/ℓ31.
|
bb
Baseblock |
Cause: External baseblock signal was entered via one of the multi-function input terminals (S1 to S8).
Remedy:
Check external sequence and baseblock signal input timing.
|
bUS
Option Communication Error |
Cause:
- Connection is broken or master controller stopped communicating.
- Option is damaged.
- The option is not properly connected to the regenerative unit.
- A data error occurred due to noise.
Remedy:
- Check for faulty wiring, correct wiring, or repair disconnected cables/short circuits.
- If no wiring problems exist and fault continues, replace the option.
- Reinstall the option (ensure pins are lined up).
- Check options to minimize noise effects (shielded lines, grounding, EMC filters, surge absorbers).
|
CALL
Serial Communication Transmission Error |
Cause:
- Communications wiring is faulty, short circuit, or not connected properly.
- Programming error on the master side.
- Communications circuitry is damaged.
- Termination resistor setting is incorrect.
Remedy:
- Check for wiring errors, correct wiring, repair cables.
- Check communications at start-up and correct programming errors.
- Perform self-diagnostics check. If problem continues, replace control board or unit.
- Install termination resistor at both ends. Set internal termination resistor switch (S2) to ON.
|
CE
MEMOBUS/Modbus Communication Error |
Cause:
- A data error occurred due to noise.
- Communication protocol is incompatible.
- The CE detection time (H5-09) is set shorter than the time required for a communication cycle.
- Incompatible PLC software settings or hardware problem.
- Communications cable is disconnected or damaged.
Remedy:
- Minimize noise (shielded lines, grounding, EMC filters).
- Check H5 parameters and protocol settings in controller.
- Check PLC, change software settings, or set longer CE detection time (H5-09).
- Check PLC and remove cause of error on controller side.
- Check connector signals or replace communications cable.
|
CoF
Current Offset Fault |
Cause: A fault occurred in the current detection circuit.
Remedy:
- Cycle the power supply and check operation.
- If the fault occurs again, replace the board or regenerative unit.
|
CrST
Cannot Reset |
Cause: Fault reset was being executed when a Run command was entered.
Remedy:
- Ensure that a Run command cannot be entered from the external terminals or option during fault reset.
- Turn off the Run command.
|
CyC
MECHATROLINK Communications Cycle Setting Error |
Cause: The communications cycle of the MECHATROLINK option card is out of range.
Remedy:
Correct the setting.
|
E5
MECHATROLINK Watchdog Timer Error |
Cause: There is no continuity in the watchdog timer in the data that is sent by the host controller.
Remedy:
Execute the DISCONNECT or ALM_CLR command, and then move to phase 3 again with the CONNECT or SYNC_SET command.
|
EF0
Option Card External Fault |
Cause:
- An external fault was received from the PLC with F6-03 set to 3.
- There is a problem with the PLC program.
Remedy:
- Remove the cause of the external fault.
- Remove the external fault input from the PLC.
- Check the PLC program and correct problems.
|
EF1 to EF8
External Fault (Input Terminal S1 to S8) |
Cause:
- An external device has tripped an alarm function.
- Wiring is incorrect.
- Multi-function contact inputs are set incorrectly.
Remedy:
- Remove the cause of the external fault and reset the multi-function input value.
- Ensure signal lines are connected properly to terminals assigned for external fault detection.
- Check if unused terminals have been set for H1 parameters (24 to 27, 2C to 2F). Change terminal settings if necessary.
|
FAn
Internal Circulation Fan Fault |
Cause:
- An internal circulation fan is faulty.
- An internal circulation fan or MC power supply is faulty.
Remedy:
- Cycle power. Check operation of fans. Check U4-03/U4-04. Replace fan if expired or faulty.
- If fault occurs repeatedly after power cycle, replace the board or the regenerative unit.
|
Fdv
Power Supply Frequency Fault |
Cause:
- A momentary power loss occurred.
- An input power supply wiring terminal is loose.
- The fluctuation in the voltage of the input power supply is too large.
- The AC power supply fuse is open (transistor destroyed or ground fault/short).
- The phase rotation direction has changed in the input power supply.
- The detected power supply frequency exceeded the allowable value.
Remedy:
- Investigate and correct the cause and reset the fault.
- Refer to Diagnosing and Resetting Faults.
- If fuse is open: Contact Yaskawa representative.
- Correct the wiring (for phase rotation).
- Improve the power supply.
|
HCA Current Alarm |
Cause: Load is too heavy.
Remedy:
- Reduce the load for applications with repetitive operations (i.e., stops and starts).
- Replace the regenerative unit.
|
LT-1 Cooling Fan Maintenance Time |
Cause: The cooling fan has reached 90% of its expected performance life.
Remedy:
- Replace the cooling fan.
- Set parameter o4-03 to 0 to reset the Maintenance Monitor.
|
LT-2 Capacitor Maintenance Time |
Cause: The main circuit and control circuit capacitors have reached 90% of their expected performance lives.
Remedy:
- Replace either the control board or the entire regenerative unit.
- For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.
|
LT-3 Soft Charge Bypass Relay Maintenance Time |
Cause: The DC bus soft charge relay has reached 90% of expected performance life.
Remedy:
- Replace either the control board or the entire regenerative unit.
- For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.
|
oH Heatsink Overheat |
Cause:
- Surrounding temperature is too high.
- Airflow around the regenerative unit is restricted.
- The ambient temperature is too high.
- The load is too large.
- Internal cooling fan has stopped.
Remedy:
- Check the surrounding/ambient temperature.
- Improve air circulation or install a cooling device (fan/AC) within the enclosure.
- Remove heat-generating objects nearby.
- Provide proper installation space (refer to manual page 27).
- Clear dust or debris clogging the cooling fan.
- Measure output current and lower the load.
- Replace the cooling fan (refer to manual page 124) and reset o4-03 to 0.
|
oL2 Overload |
Cause:
- Load is too heavy.
- The regenerative unit does not operate.
Remedy:
- Reduce the load.
- Start regenerative unit operation first, and then start regenerative unit operation.
|
ov DC Bus Overvoltage |
Cause:
- Electrical noise interference causes the unit to operate incorrectly.
- There was a regenerative load while the regenerative unit is stopped.
- The power supply voltage is too high.
- Wiring of power supply voltage detection circuits or main circuit terminals is incorrect.
Remedy:
- Review noise interference solutions (check ground wiring, install surge protector to MC coil).
- Set number of fault restarts (L5-01) to a value other than 0.
- Operate the regenerative unit.
- Lower the voltage so it is within specifications.
- Check and correct the wiring (r1/l11, s1/l21, t1/l31 and R/L1, S/L2, T/L3).
|
PAUv Power Supply Undervoltage Pre-Alarm |
Cause:
- The power supply voltage is low.
- A phase loss occurred in the input power supply.
- Voltage detection failed.
Remedy:
- Increase the power supply voltage.
- Check input power supply for phase loss or imbalance. Investigate/correct cause and reset fault.
- Check r1/l11, s1/l21, t1/l31 to see if they are wired correctly.
|
PF3 Input Phase Loss Detection |
Cause:
- The fluctuation in the voltage of the input power supply is too large.
- A phase loss occurred in the input power supply.
- The interphase voltage balance is bad.
Remedy:
- Investigate the cause and implement countermeasures.
- Refer to “Diagnosing and Resetting Faults” on page 114 for details.
|
PFDv Power Supply Frequency Pre-Alarm |
Cause:
- Momentary power loss has occurred.
- Voltage distortion is large.
- Voltage detection failure.
- Phase loss has occurred.
Remedy:
- Activate the momentary power loss ride-thru.
- Increase the power supply capacity.
- Confirm r1/l11, s1/l21, t1/l31 are correctly wired.
- Confirm the power supply and regenerative unit are correctly connected.
|
SE MEMOBUS/Modbus Test Mode Fault |
Cause: A fault occurred during MEMOBUS/Modbus Communications Test Mode.
Remedy:
- Always stop the operation of the regenerative unit before you perform MEMOBUS/Modbus communications tests.
|
SRC Phase Order Fault |
Cause:
- A momentary power loss occurred.
- An input power supply wiring terminal is loose.
- The fluctuation in the voltage of the input power supply is too large.
Remedy:
- Investigate and correct the cause and reset the fault.
- Refer to “Diagnosing and Resetting Faults” on page 114 for details.
|
Uv Undervoltage |
Cause:
- Phase loss in the regenerative unit input power.
- Loose wiring in the regenerative unit input power terminals.
- There is a problem with the regenerative unit input power voltage.
- A power loss occurred.
- Internal circuitry is worn.
- The input power transformer is too small/voltage drops when switched on.
- Air inside the regenerative unit is too hot.
- The CHARGE light is broken or disconnected.
Remedy:
- Check for wiring errors in the main circuit input power. Correct wiring.
- Ensure terminals are properly tightened (Refer to Wire Gauges/Tightening Torque on page 52).
- Check voltage; lower voltage so it is within limits listed in specifications.
- Improve the power supply.
- Check capacitor maintenance time (U4-05). Replace board/unit if >90%.
- Check for alarm when magnetic contactor/breaker are closed. Check transformer capacity.
- Check the temperature inside the regenerative unit.
- Replace either the control board or the entire regenerative unit.
|
vrE Resonance Detection |
Cause: There is noise on the power supply line.
Remedy:
- Investigate the source of the noise and implement countermeasures.
|
Err EEPROM Write Error |
Cause: The data was corrupted by noise when writing data to the EEPROM.
Remedy:
- Press the ENTER key.
- Set the parameters again.
- Cycle the power supply. Refer to Diagnosing and Resetting Faults.
Cause: EEPROM Hardware Failure.
Remedy:
- Replace the board or regenerative unit. Consult your Yaskawa representative.
|
oPE01 Unit Capacity Setting Error |
Cause: The Unit Model Selection (o2-04) and the actual capacity of the regenerative unit are not the same.
Remedy:
- Correct the value set to o2-04.
|
oPE02 Parameter Range Setting Error |
Cause: Parameters were set outside the possible setting range.
Remedy:
- Use U1-18 to find parameters set outside the range.
- Set parameters to the proper values.
Note: When multiple errors occur simultaneously, other errors are given precedence over oPE02.
|
oPE03 Multi-Function Input Selection Error |
Cause: The same function is assigned to two multi-function inputs (Excludes “Not used” and “External Fault”).
Remedy:
- Ensure all multi-function inputs (H1-01 to H1-08) are assigned to different functions.
- Re-enter the multi-function settings to ensure this does not occur.
|
oPE04 Terminal Board Mismatch Error |
Cause: The regenerative unit was replaced (but the removable terminal block with parameter backup was not replaced).
Remedy:
- Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the regenerative unit.
Cause: The removable terminal block with parameter backup was replaced.
Remedy:
- Initialize parameters after regenerative unit replacement by setting A1-03 to 2220.
|
oPE05 Run Command Selection Error |
Cause: The Run Command Selection 1 is assigned to an option card (b1-02 = 3) and an input option card is not connected to the unit.
Remedy:
- Reconnect the input option card to the regenerative unit.
|
oPE07 Multi-Function Analog Input Selection Error |
Cause: At least two of these parameters have the same setting: H3-02, H3-10, or H3-06.
Remedy:
- Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.
Note: Both 1F (Through mode) and F (Through mode) can be set to H3-02, H3-10, or H3-06 simultaneously.
|
oPE30 Incorrect Input Voltage Adjustment |
Cause: The setting of o2-04 (Unit Model Selection) changed, or ERPROM failed for the input voltage offset.
Remedy:
- For information on clearing the fault, consult with your Yaskawa representative or the nearest Yaskawa sales office.
|
CoPy
Writing Parameter Settings (flashing)
|
Cause:
(Normal Operation Task)
Remedy:
None required.
|
CPyE
Error Writing Data
|
Cause:
–
Remedy:
–
|
CSEr
Copy Unit Error
|
Cause:
–
Remedy:
–
|
dFPS
Model Mismatch
|
Cause:
–
Remedy:
–
|
End
Task Complete
|
Cause:
(Normal Operation Task)
Remedy:
None required.
|
iFEr
Communication Error
|
Cause:
–
Remedy:
–
|
ndAT
Model, Voltage Class, Capacity Mismatch
|
Cause:
–
Remedy:
–
|
rdEr
Error Reading Data
|
Cause:
–
Remedy:
–
|
rEAd
Reading Parameter Settings (flashing)
|
Cause:
(Normal Operation Task)
Remedy:
None required.
|
vAEr
Voltage Class, Capacity Mismatch
|
Cause:
–
Remedy:
–
|
vFyE
Parameter settings in the regenerative unit and those saved to the copy function are not the same
|
Cause:
–
Remedy:
–
|
vrFy
Comparing Parameter Settings (flashing)
|
Cause:
(Normal Operation Task)
Remedy:
None required.
|