64FF Fault reset |
Cause: A fault has been reset from the control panel, Drive composer PC tool, fieldbus or I/O.
Remedy:
|
B686 Checksum mismatch |
Cause: Parameter checksum 96.68 Actual checksumA does not match 96.71 Approved checksum A and/ or parameter checksum 96.69 Actual checksumB does not match 96.72 Approved checksum B.
Remedy:
|
A2A1 Current calibration |
Cause: Current offset and gain measurement calibration will occur at next start.
Remedy:
- Informative warning. (See parameter 99.13 ID run requested.)
|
A2B1 Overcurrent |
Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this warning may also be caused by an earth fault or supply phase loss.
Remedy:
- Check motor load.
- Check acceleration times in parameter group 23 Speed reference ramp (speed control), 28 Frequency reference chain (frequency control). Also check parameters 46.01 Speed scaling, 46.02 Frequency scaling and 46.03 Torque scaling.
- Check motor and motor cable (including phasing and delta/star connection).
- Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable. See chapter Electrical installation, section Checking the insulation of the assembly in the Hardware manual of the drive.
- Check there are no contactors opening and closing in motor cable.
- Check that the start-up data in parameter group 99 Motor data corresponds to the motor rating plate.
- Check that there are no power factor correction capacitors or surge absorbers in motor cable.
|
A2B3 Earth leakage |
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.
Remedy:
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable. See chapter Electrical installation, section Checking the insulation of the assembly in the Hardware manual.
- If an earth fault is found, fix or change the motor cable and/or motor.
- If no earth fault can be detected, contact your local ABB representative.
|
A2B4 Short circuit |
Cause: Short-circuit in motor cable(s) or motor.
Remedy:
- Check motor and motor cable for cabling errors.
- Check motor and motor cable (including phasing and delta/star connection).
- Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- For frames R6 to R11, check the auxiliary code.
|
A2BA IGBT overload |
Cause: Excessive IGBT junction to case temperature. This warning protects the IGBT(s) and can be activated by a short circuit in the motor cable.
Remedy:
- Check motor cable.
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A3A1 DC link overvoltage |
Cause: Intermediate circuit DC voltage too high (when the drive is stopped).
Remedy:
- Check the supply voltage setting (parameter 95.01 Supply voltage). Note that the wrong setting of the parameter may cause the motor to rush uncontrollably, or may overload the brake chopper or resistor.
- Check the supply voltage.
- If the problem persists, contact your local ABB representative.
|
A3A2 DC link undervoltage |
Cause: Intermediate circuit DC voltage too low (when the drive is stopped).
Remedy:
- Check the supply voltage.
- If the problem persists, contact your local ABB representative.
|
A3AA DC not charged |
Cause: The voltage of the intermediate DC circuit has not yet risen to operating level.
Remedy:
- Check the supply voltage.
- If the problem persists, contact your local ABB representative.
|
A490 Incorrect temperature sensor setup |
Cause: Temperature cannot be supervised due to incorrect adapter setup. AO settings do not match with 35.11 and 35.21.
Remedy:
- Check the settings of temperature source parameters 35.11 and 35.21.
- Check the settings of temperature source parameters 35.11 and 35.21 against AO parameters 13.12 and 13.22.
|
A491 External temperature 1 |
Cause: Measured temperature 1 has exceeded warning limit. (Editable message text)
Remedy:
- Check the value of parameter 35.02 Measured temperature 1.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
- Check the value of 35.13 Temperature 1 warning limit.
|
A492 External temperature 2 |
Cause: Measured temperature 2 has exceeded warning limit. (Editable message text)
Remedy:
- Check the value of parameter 35.03 Measured temperature 2.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
- Check the value of 35.23 Temperature 2 warning limit.
|
A4A0 Control board temperature |
Cause: Control unit temperature is too high.
Aux code (none): Temperature above warning limit.
Aux code 1: Thermistor broken.
Remedy:
- Check the auxiliary code.
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- If Aux code 1: Contact an ABB service representative for control unit replacement.
|
A4A1 IGBT overtemperature |
Cause: Estimated drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A4A9 Cooling |
Cause: Drive module temperature is excessive.
Remedy:
- Check ambient temperature. If it exceeds 40 °C/104 °F or if it exceeds 50 °C /122 °F, ensure that load current does not exceed derated load capacity of drive. For all P55 frames, check the derating temperatures.
- Check drive module cooling air flow and fan operation.
- Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
|
A4B0 Excess temperature |
Cause: Power unit module temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
- Check Aux code for location: 1: U-phase, 2: V-phase, 3: W-phase, 4: INT board, 6: Air inlet, 7: PCB compartment fan or power supply board, FA: Ambient temperature.
|
A4B1 Excess temperature difference |
Cause: High temperature difference between the IGBTs of different phases.
Remedy:
- Check the motor cabling.
- Check cooling of drive module(s).
|
A4F6 IGBT temperature |
Cause: Drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A581 Fan |
Cause: Cooling fan feedback missing. For frame sizes R6 or larger.
Remedy:
- Check the auxiliary code to identify the fan. Code 0 denotes main fan 1. Other codes (format XYZ): “X” specifies state code (1: ID run, 2: normal). “Y” = 0, “Z” specifies the index of the fan (1: Main fan 1, 2: Main fan 2, 3: Main fan 3).
- Check fan operation and connection.
- Replace fan if faulty.
|
A5A0 Safe torque off |
Cause: Safe torque off function is active, that is, safety circuit signal(s) connected to connector STO is lost.
Remedy:
- Check safety circuit connections. For more information, chapter The Safe torque off function in the Hardware manual of the drive and description of parameter 31.22 STO indication run/stop.
- Check the value of parameter 95.04 Control board supply.
|
A5EA Measurement circuit temperature |
Cause: Problem with internal temperature measurement of the drive. Aux code depends on control unit type.
Aux codes: 0001 (IGBT), 0003 (Board), 0006 (Power supply).
Remedy:
- Contact your local ABB representative.
|
A5EB PU board powerfail |
Cause: Power unit power supply failure.
Remedy:
- Contact your local ABB representative.
|
A5ED Measurement circuit ADC |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
A5EE Measurement circuit DFF |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
A5EF PU state feedback |
Cause: State feedback from output phases does not match control signals.
Remedy:
- Contact your local ABB representative.
|
A5F0 Charging feedback |
Cause: Charging feedback signal missing.
Remedy:
- Check the feedback signal coming from the charging system.
|
A682 Flash erase speed exceeded |
Cause: The flash memory (in the memory unit) has been erased too frequently, compromising the lifetime of the memory.
Remedy:
- Avoid forcing unnecessary parameter saves by parameter 96.07 or cyclic parameter writes (such as user logger triggering through parameters).
- Check the auxiliary code (format XYYY YZZZ). “X” specifies the source of warning (1: generic flash erase supervision). “ZZZ” specifies the flash subsector number that generated the warning.
|
A686 Checksum mismatch |
Cause: Parameter checksum 96.68 Actual checksumA does not match 96.71 Approved checksum A etc.
Remedy:
- Revert parameter changes made after approving the checksum.
- If parameter changes are valid, approve new checksum by setting parameter 96.55 Checksum control word bit 12 (Set approved checksum A) and/or 13 (Set approved checksum B) to 1 = Set.
|
A6A4 Motor nominal value |
Cause: The motor parameters are set incorrectly. The drive is not dimensioned correctly.
Aux codes:
0001: Slip frequency too small.
0002: Sync and nominal speeds differ too much.
0003: Nom speed higher than sync speed.
0004: Nom current outside limits.
0005: Nom voltage outside limits.
0006: Nom power higher than apparent power.
0007: Nom power not consistent with speed/torque.
Remedy:
- Check the auxiliary code.
- Check the settings of the motor configuration parameters in groups 98 and 99.
- Check that the drive is sized correctly for the motor.
|
A6A5 No motor data |
Cause: Parameters in group 99 have not been set.
Remedy:
- Check that all the required parameters in group 99 have been set.
- Note: It is normal for this warning to appear during the start-up and continue until the motor data is entered.
|
A6A6 Voltage category unselected |
Cause: The voltage category has not been defined.
Remedy:
- Set voltage category in parameter 95.01 Supply voltage.
|
A6A7 System time not set |
Cause: System time is not set. Timed functions cannot be used and fault log dates are not correct.
Remedy:
- Set the system time manually or connect the control panel to the drive to synchronize the clock.
- If basic control panel is used, synchronize the clock through the EFB or a fieldbus module.
- Set parameter 34.10 Timed functions enable to Disabled to disable the timed functions if they are not used.
|
A6B0 User lock is open |
Cause: The user lock is open, ie. user lock configuration parameters 96.100…96.102 are visible.
Remedy:
- Close the user lock by entering an invalid pass code in parameter 96.02 Pass code. See section User lock (page 215).
|
A6B1 User pass code not confirmed |
Cause: A new user pass code has been entered in parameter 96.100 but not confirmed in 96.101.
Remedy:
- Confirm the new pass code by entering the same code in 96.101.
- To cancel, close the user lock without confirming the new code. See section User lock.
|
A6D1 FBA A parameter conflict |
Cause: The drive does not have a functionality requested by a PLC, or requested functionality has not been activated.
Remedy:
- Check PLC programming.
- Check settings of parameter groups 50 Fieldbus adapter (FBA).
|
A6E5 AI parametrization |
Cause: The current/voltage hardware setting of an analog input does not correspond to parameter settings.
Remedy:
- Check the event log for an auxiliary code. The code identifies the analog input whose settings are in conflict.
- Adjust either the hardware setting (on the drive control unit) or parameter 12.15/12.25.
- Note: Control unit reboot (either by cycling the power or through parameter 96.08 Control board boot) is required to validate any changes in the hardware settings.
|
A6E6 ULC configuration |
Cause: User load curve configuration error.
Remedy:
Check the auxiliary code (format XXXX ZZZZ). “ZZZZ” indicates the problem:
- 0000: Speed points inconsistent. Check that each speed point (37.11…37.15) has a higher value than the previous point.
- 0001: Frequency points inconsistent. Check that each frequency point (37.20…37.16) has a higher value than the previous point.
- 0002: Underload point above overload point. Check that each overload point (37.31…37.35) has a higher value than the corresponding underload point (37.21…37.25).
- 0003: Overload point below underload point.
|
A780 Motor stall |
Cause: Motor is operating in stall region because of, for example, excessive load or insufficient motor power.
Remedy:
- Check motor load and drive ratings.
- Check fault function parameters (31.24 Stall function).
|
A783 Motor overload |
Cause: Motor current is too high.
Remedy:
- Check for overloaded motor.
- Adjust the parameters used for the motor overload function (35.51…35.53) and 35.55…35.56.
|
A784 Motor disconnect |
Cause: All three output phases are disconnected from motor.
Remedy:
- Check that switches between drive and motor are closed.
- Check that all cables between drive and motor are connected and secured.
- If no issue was detected and drive output was actually connected to motor, contact ABB.
|
A793 BR excess temperature |
Cause: Brake resistor temperature has exceeded warning limit defined by parameter 43.12 Brake resistor warning limit.
Remedy:
- Stop drive. Let resistor cool down.
- Check resistor overload protection function settings (parameter group 43 Brake chopper).
- Check warning limit setting, parameter 43.12.
- Check that the resistor has been dimensioned correctly.
- Check that braking cycle meets allowed limits.
|
A794 BR data |
Cause: Brake resistor data has not been given.
Remedy:
One or more of the resistor data settings (parameters 43.08…43.10) is incorrect. The parameter is specified by the auxiliary code:
- 0001: Resistance value too low. Check value of 43.10.
- 0002: Thermal time constant not given. Check value of 43.08.
- 0003: Maximum continuous power not given. Check value of 43.09.
|
A79C BC IGBT excess temperature |
Cause: Brake chopper IGBT temperature has exceeded internal warning limit.
Remedy:
- Let chopper cool down.
- Check for excessive ambient temperature.
- Check for cooling fan failure.
- Check for obstructions in the air flow.
- Check the dimensioning and cooling of the cabinet.
- Check resistor overload protection function settings (parameters 43.06…43.10).
- Check minimum allowed resistor value for the chopper being used.
- Check that braking cycle meets allowed limits.
- Check that drive supply AC voltage is not excessive.
|
A7A2 Mechanical brake opening failed |
Cause: Status of mechanical brake acknowledgement is not as expected during brake open.
Remedy:
- Check mechanical brake connection.
- Check mechanical brake settings in parameter group 44 Mechanical brake control.
- Check that acknowledgement signal matches the actual status of brake.
|
A7AB Extension I/O configuration failure |
Cause: I/O module is not connected to the device or parameterization conflict with connected I/O module.
Remedy:
- Check that the I/O module is connected to the device.
- Check that no parameters are connected to non-existing I/O parameters.
|
A7AC I/O Module internal error |
Cause: Calibration data is not stored in the I/O module. Analog signals are not working with full accuracy.
Remedy:
|
A7C1 FBA A communication |
Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.
Remedy:
- Check status of fieldbus communication. See user documentation of fieldbus interface.
- Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in, and 53 FBA A data out.
- Check cable connections.
- Check if communication master is able to communicate.
|
A7CE EFB comm loss |
Cause: Communication break in embedded fieldbus (EFB) communication.
Remedy:
- Check the status of the fieldbus master (online/offline/error etc.).
- Check cable connections to the EIA-485/X5 terminals 29, 30 and 31 on the control unit.
|
A7EE Panel loss |
Cause: Control panel or PC tool selected as active control location for drive has ceased communicating.
Remedy:
- Check PC tool or control panel connection.
- Check control panel connector.
- Check mounting platform if being used.
- Disconnect and reconnect the control panel.
|
A88F Cooling fan |
Cause: Maintenance timer limit exceeded.
Remedy:
- Consider changing the cooling fan.
- Parameter 05.04 Fan on-time counter shows the running time of the cooling fan.
|
A8A0 AI supervision |
Cause: An analog signal is outside the limits specified for the analog input.
Remedy:
- Check signal level at the analog input.
- Check the wiring connected to the input.
- Check the minimum and maximum limits of the input in parameter group 12 Standard AI.
|
A8A1 RO life warning |
Cause: The relay has changed states more than the recommended number of times.
Remedy:
Change the control unit or stop using the relay output.
- 0001: Relay output 1.
- 0002: Relay output 2.
- 0003: Relay output 3.
|
A8A2 RO toggle warning |
Cause: The relay output is changing states faster than recommended (e.g., fast changing frequency signal connected). The relay lifetime will be exceeded shortly.
Remedy:
Replace the signal connected to the relay output source with a less frequently changing signal.
- 0001: Relay output 1 (Check 10.24 RO1 source).
- 0002: Relay output 2 (Check 10.27 RO2 source).
- 0003: Relay output 3 (Check 10.30 RO3 source).
|
A8B0 ABB Signal supervision 1 |
Cause: Warning generated by the signal supervision function 1.
Remedy:
- Check the source of the warning (parameter 32.07 Supervision 1 signal).
|
A8B1 ABB Signal supervision 2 |
Cause: Warning generated by the signal supervision function 2.
Remedy:
- Check the source of the warning (parameter 32.17 Supervision 2 signal).
|
A8B2 ABB Signal supervision 3 |
Cause: Warning generated by the signal supervision function 3.
Remedy:
- Check the source of the warning (parameter 32.27 Supervision 3 signal).
|
A8B3 ABB Signal supervision 4 |
Cause: Warning generated by the signal supervision function 4.
Remedy:
- Check the source of the warning (parameter 32.37 Supervision 4 signal).
|
A8B4 ABB Signal supervision 5 |
Cause: Warning generated by the signal supervision function 5.
Remedy:
- Check the source of the warning (parameter 32.47 Supervision 5 signal).
|
A8B5 ABB Signal supervision 6 |
Cause: Warning generated by the signal supervision function 6.
Remedy:
- Check the source of the warning (parameter 32.57 Supervision 6 signal).
|
A8BE ULC overload warning |
Cause: Selected signal has exceeded the user overload curve.
Remedy:
- Check for any operating conditions increasing the monitored signal (e.g., loading of the motor if torque/current is monitored).
- Check the definition of the load curve (parameter group 37 User load curve).
|
A8BF ULC underload warning |
Cause: Selected signal has fallen below the user underload curve.
Remedy:
- Check for any operating conditions decreasing the monitored signal (e.g., loss of load if torque/current is monitored).
- Check the definition of the load curve (parameter group 37 User load curve).
|
A981 External warning 1 |
Cause: Fault in external device 1.
Remedy:
- Check the external device.
- Check setting of parameter 31.01 External event 1 source.
|
A982 External warning 2 |
Cause: Fault in external device 2.
Remedy:
- Check the external device.
- Check setting of parameter 31.03 External event 2 source.
|
A983 External warning 3 |
Cause: Fault in external device 3.
Remedy:
- Check the external device.
- Check setting of parameter 31.05 External event 3 source.
|
A984 External warning 4 |
Cause: Fault in external device 4.
Remedy:
- Check the external device.
- Check setting of parameter 31.07 External event 4 source.
|
A985 External warning 5 |
Cause: Fault in external device 5.
Remedy:
- Check the external device.
- Check setting of parameter 31.09 External event 5 source.
|
AF88 Season configuration warning |
Cause: You have configured a season which starts before the previous season.
Remedy:
- Configure the seasons with increasing start dates, see parameters 34.60 Season 1 start date…34.63 Season 4 start date.
|
AF90 Speed controller autotuning |
Cause: The speed controller autotune routine did not complete successfully.
Remedy:
Check the auxiliary code:
- 0000: Drive was stopped before autotune complete. Start drive and repeat until successful.
- 0001: Drive started but not ready to follow autotune. Make sure prerequisites are fulfilled.
- 0002: Required torque reference could not be reached. Decrease torque step (25.38) or increase speed step (25.39).
- 0003: Motor could not accelerate to max speed. Increase torque step (25.38) or decrease speed step (25.39).
- 0004: Motor could not decelerate to min speed. Increase torque step (25.38) or decrease speed step (25.39).
- 0005: Motor could not decelerate with full autotune torque. Decrease torque step (25.38) or speed step (25.39).
- 0006: Autotune could not write a parameter. Run the drive one more time.
- 0007: Drive was ramping down when autotune activated. Run to set point and start autotune one more time.
- 0008: Drive was ramping up when autotune activated. Wait until drive reaches set point and start autotune.
- 0009: Drive was running outside of autotune speed limits. Check limits, set correct setpoint and repeat.
|
AFAA Autoreset |
Cause: A fault is about to be autoreset.
Remedy:
- Informative warning. See the settings in parameter group 31 Fault functions.
|
AFE1 Emergency stop (off2) |
Cause: Drive has received an emergency stop (mode selection off2) command.
Remedy:
- Check that it is safe to continue operation. Then return emergency stop push button to normal position. Restart drive.
- If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.
|
AFE2 Emergency stop (off1 or off3) |
Cause: Drive has received an emergency stop (mode selection off1 or off3) command.
Remedy:
- If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.
|
AFE9 Start delay |
Cause: The start delay is active and the drive will start the motor after a predefined delay.
Remedy:
- Informative warning. See parameter 21.22 Start delay.
|
AFEB Run enable missing |
Cause: No run enable signal is received.
Remedy:
- Check setting of parameter 20.12 Run enable 1 source.
- Switch signal on (for example, in the fieldbus Control Word) or check wiring of selected source.
|
AFED Enable to rotate |
Cause: Signal to rotate has not been received within a fixed time delay of 240 s.
Remedy:
- Switch enable to rotate signal on (e.g. in digital inputs).
- Check the setting of (and source selected by) parameter 20.22 Enable to rotate.
|
AFF6 Identification run |
Cause: Motor ID run will occur at next start.
Remedy:
|
AFF8 Motor heating active |
Cause: Pre-heating is being performed.
Remedy:
- Informative warning. Motor pre-heating is active.
- Current specified by parameter 21.16 Pre-heating current is being passed through the motor.
|
B5A0 STO event |
Cause: Safe torque off function is active, i.e. safety circuit signal(s) connected to connector STO is lost.
Remedy:
- Informative warning. Check safety circuit connections.
- See chapter ‘The Safe torque off function’ in the Hardware manual.
- Check description of parameter 31.22 STO indication run/stop.
|
D50A Running dry |
Cause: Dry run protection is activated.
Remedy:
- Check the pump inlet for sufficient water level.
- Check dry run protection settings in parameters 82.20 Dry run protection and 82.21 Dry run source.
|
D50B Pipe fill-timeout |
Cause: Soft pipe fill has reached the timeout limit. The PID output reached the setpoint after reference ramping ended and timeout limit elapsed.
Remedy:
- Check the pipe for possible leakage.
- See parameter 82.25 Soft pipe fill supervision and 82.26 Time-out limit.
|
D501 No more available PFC motors |
Cause: No more PFC motors can be started because they can be interlocked or in the Hand mode.
Remedy:
- Check that there are no interlocked PFC motors (parameters 76.81…76.84).
- If all motors are in use, the PFC system is not adequately dimensioned to handle the demand.
|
D502 All motors interlocked |
Cause: All the motors in the PFC system are interlocked.
Remedy:
- Check that there are no interlocked PFC motors, see parameters 76.81…76.84.
|
D503 VSD controlled PFC motor interlocked |
Cause: The motor connected to the drive is interlocked (unavailable).
Remedy:
- Motor connected to the drive is interlocked and thus cannot be started.
- Remove the corresponding interlock to start the drive controlled PFC motor. See parameters 76.81…76.84.
|
D505 Max cleaning warning |
Cause: Maximum number of cleanings are reached in defined time. The Pump cleaning is unable to clean the pump and hence, manual cleaning is required.
Remedy:
- Check the pump for blockages.
- Clean the pump manually if needed.
- Check parameters 83.35 Cleaning count fault to 83.37 Maximum cleaning count.
|
D506 Pump cleaning not possible |
Cause: Pump cleaning cannot be started. The drive needs to be in remote control and start signal is activated.
Remedy:
- Change control location to Auto.
|
D507 Pump cleaning needed |
Cause: Dirt detection indicates that the pump needs cleaning but automatic pump cleaning is not allowed.
Remedy:
- Perform pump cleaning manually.
- Start pump cleaning by changing parameter 83.12 ‘Manually force cleaning’ to ‘Start cleaning now’.
|
D511 Cavitation control |
Cause: Cavitation control warning.
Remedy:
- Check the auxiliary code. See actions for each code below.
|
0001 Cavitation detected warning |
Cause: The pump is not getting enough liquid. Check the system.
Remedy:
- Confirm that cavitation is occurring.
- Check the fluid level in the system.
- Adjust the parameters used for the cavitation detection function (86.12 – 86.30) if needed.
|
0002 Cavitation tune required |
Cause: Cavitation control has been selected (86.11); however, there is missing data in 86.21 – 86.25.
Remedy:
- Perform a cavitation curve autotune (86.20).
- Manually enter the data used for the cavitation detection function (86.21 – 86.25) if autotune is not an option.
- Disable cavitation control (86.11) if the above cannot be accomplished.
|
0003 Cavitation curve autotune |
Cause: Cavitation curve autotune has been selected and will be performed on next start (in Hand).
Remedy:
- Press Hand to run the autotune.
- De-select the cavitation curve autotune (86.20) if tune is not desired.
|
D58B Gas pressure outside limits |
Cause: The compressor gas pressure is outside the limits.
Remedy:
- Check the compressor gas pressure limits configured as AI min and max values.
|
D590 Restart delay |
Cause: Compressor Restart delay.
Remedy:
- Check parameter 21.40 Restart delay.
- The drive cannot be started until the restart delay has elapsed.
|
001 Compressor short cycle protection |
Cause: Short cycle protection active.
Remedy:
- Wait until the restart delay has passed.
|
D591 Min. run time |
Cause: Compressor minimum run time.
Remedy:
- Check parameter 21.41 Minimum run time.
- During the minimum run time the drive runs at the minimum speed/frequency.
|
D602 Cavitation tune completed |
Cause: Cavitation auto tune has finished and stopped the drive.
Remedy:
|
1080 Backup/Restore timeout |
Cause: Control panel or PC tool has failed to communicate with the drive when backup was being made or restored.
Remedy:
- Request backup or restore again.
|
1081 Rating ID fault |
Cause: Drive software has not been able to read the rating ID of the drive.
Remedy:
- Reset the fault to make the drive try to reread the rating ID.
- If the fault reappears, cycle the power to the drive. You may have to repeat this.
- If the fault persists, contact your local ABB representative.
|
2340 Short circuit |
Cause: Short-circuit in motor cable(s) or motor.
Remedy:
- Check motor and motor cable for cabling errors.
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Cycle the power to the drive.
- Auxiliary codes are shown below.
|
2310 Overcurrent |
Cause: Output current has exceeded internal fault limit. Can be caused by earth fault or supply phase loss.
Remedy:
- Check the auxiliary code (format XXXYYYZZ).
- Check motor load.
- Check acceleration times in parameter group 23 or 28.
- Check motor and motor cable (including phasing and delta/star connection).
- Check for earth fault in motor or motor cables by measuring insulation resistances.
|
2330 Earth leakage |
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.
Remedy:
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Check for an earth fault in motor or motor cables by measuring the insulation resistances.
- Try running the motor in scalar control mode if allowed.
- If no earth fault can be detected, contact your local representative.
|
2381 IGBT overload |
Cause: Excessive IGBT junction to case temperature. This fault protects the IGBT(s) and can be activated by a short circuit in the motor cable.
Remedy:
- Check motor cable.
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
3130 Input phase loss |
Cause: Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse.
Remedy:
- Check input power line fuses.
- Check for loose power cable connections.
- Check for input power supply imbalance.
|
3181 Wiring or earth fault |
Cause: Incorrect input power and motor cable connection (i.e. input power cable is connected to drive motor connection).
Remedy:
- Check input power connections.
|
3210 DC link overvoltage |
Cause: Excessive intermediate circuit DC voltage.
Remedy:
- Check that overvoltage control is on (parameter 30.30).
- Check that the supply voltage matches the nominal input voltage of the drive.
- Check the supply line for static or transient overvoltage.
- Check brake chopper and resistor (if present).
- Check deceleration time.
|
3220 DC link undervoltage |
Cause: Intermediate circuit DC voltage is not sufficient because of a missing supply phase, blown fuse or fault in the rectifier bridge.
Remedy:
- Check supply cabling, fuses and switchgear.
|
3381 Output phase loss |
Cause: Motor circuit fault due to missing motor connection (all three phases are not connected).
Remedy:
|
4110 Control board temperature |
Cause: Control unit temperature is too high.
Remedy:
- Check proper cooling of the drive.
- Check the auxiliary cooling fan.
|
4210 IGBT overtemperature |
Cause: Estimated drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
4290 Cooling |
Cause: Drive module temperature is excessive.
Remedy:
- Check ambient temperature.
- Ensure that load current does not exceed derated load capacity of drive.
- Check drive module cooling air flow and fan operation.
- Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
|
42F1 IGBT temperature |
Cause: Drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
4310 Excess temperature |
Cause: Power unit module temperature is excessive.
Remedy:
- See A4B0 Excess temperature.
|
4380 Excess temperature difference |
Cause: High temperature difference between the IGBTs of different phases.
Remedy:
- Check the motor cabling.
- Check cooling of drive module(s).
|
4981 External temperature 1 |
Cause: Measured temperature 1 has exceeded fault limit.
Remedy:
- Check the value of parameter 35.02 Measured temperature 1.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
|
4982 External temperature 2 |
Cause: Measured temperature 2 has exceeded fault limit.
Remedy:
- Check the value of parameter 35.03 Measured temperature 2.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
|
5080 Fan |
Cause: Cooling fan feedback missing.
Remedy:
|
5090 STO hardware failure |
Cause: STO hardware diagnostics has detected hardware failure.
Remedy:
- Contact your local ABB representative quoting the auxiliary code.
- The code contains location information (especially with parallel-connected modules).
- Check auxiliary binary bits (31…28 for inverter module number, etc).
|
5091 Safe torque off (STO indication run/stop) |
Cause: Safe torque off function is active; safety circuit signal connected to connector STO is broken during start or run.
Remedy:
- Check safety circuit connections.
- See chapter ‘The Safe torque off function’ in Hardware manual.
- Check parameter 31.22 STO indication run/stop.
- Check the value of parameter 95.04 Control board supply.
|
5092 PU logic error |
Cause: Power unit memory has cleared.
Remedy:
- Contact your local ABB representative.
|
5093 Rating ID mismatch |
Cause: The hardware of the drive does not match the information stored in the memory (may occur after firmware update).
Remedy:
- Cycle the power to the drive. You may have to repeat this.
|
5094 Measurement circuit temperature |
Cause: Problem with internal temperature measurement of the drive.
Remedy:
- Contact your local ABB representative.
|
5089 SMT circuit malfunction |
Cause: Safe motor temperature fault generated but STO event/fault not generated.
Remedy:
- Check connection between the relay output of the module and the STO terminal.
|
5098 I/O communication loss |
Cause: Communication failure to standard I/O.
Remedy:
- Try resetting the fault.
- Cycle the power to the drive.
|
50A0 Fan |
Cause: Cooling fan stuck or disconnected.
Remedy:
- Check fan operation and connection.
- Replace fan if faulty.
|
5682 Power unit lost |
Cause: Connection between the drive control unit and the power unit is lost.
Remedy:
- Check the connection between the control unit and the power unit.
|
5691 Measurement circuit ADC |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
5692 PU board powerfail |
Cause: Power unit power supply failure.
Remedy:
- Contact your local ABB representative.
|
5693 Measurement circuit DFF |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
5697 Charging feedback |
Cause: Charging feedback signal missing.
Remedy:
- Check the feedback signal coming from the charging system.
|
5698 Unknown PU fault |
Cause: The power unit logic has generated a fault which is not known by the software.
Remedy:
- Check the logic and software compatibility.
|
6181 FPGA version incompatible |
Cause: Firmware and FPGA versions are incompatible.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If problem persists, contact your local ABB representative.
|
6200 Checksum mismatch |
Cause: Parameter checksum 96.68 (Actual A) != 96.71 (Approved A) or 96.69 (Actual B) != 96.72 (Approved B).
Remedy:
- Revert parameter changes made after approving the checksum.
- If changes are valid, approve new checksum by setting parameter 96.55 Checksum control word bit 12 (or 13) to 1.
|
6306 FBA A mapping file |
Cause: Fieldbus adapter A mapping file read error.
Remedy:
- Contact your local ABB representative.
|
6481 Task overload |
Cause: Internal fault.
Remedy:
- Reboot the control unit (parameter 96.08) or cycle power.
- If problem persists, contact your local ABB representative.
|
6487 Stack overflow |
Cause: Internal fault.
Remedy:
- Reboot the control unit (parameter 96.08) or cycle power.
- If problem persists, contact your local ABB representative.
|
64A1 Internal file load |
Cause: File read error.
Remedy:
- Reboot the control unit (parameter 96.08) or cycle power.
- If problem persists, contact your local ABB representative.
|
64A4 Rating ID fault |
Cause: Rating ID load error.
Remedy:
- Contact your local ABB representative.
|
64A6 Adaptive program |
Cause: Error running the adaptive program.
Remedy:
- Check the auxiliary code (format XXYY ZZZZ).
- XX = State, YY = Function block, ZZZZ = Problem.
- See specific sub-codes below.
|
64A6 (Aux: 000A) Adaptive program |
Cause: Program corrupted or block non-existent.
Remedy:
- Restore the template program or download the program to the drive.
|
64A6 (Aux: 000C) Adaptive program |
Cause: Required block input missing.
Remedy:
- Check the inputs of the block.
|
64A6 (Aux: 0011) Adaptive program |
Cause: Program too large.
Remedy:
- Remove blocks until the error stops.
|
64A6 (Aux: 0012) Adaptive program |
Cause: Program is empty.
Remedy:
- Correct the program and download it to the drive.
|
64A6 (Aux: 001C) Adaptive program |
Cause: A non-existing parameter or block is used in the program.
Remedy:
- Edit the program to correct the parameter reference or use an existing block.
|
64A6 (Aux: 001D) Adaptive program |
Cause: Parameter type invalid for selected pin.
Remedy:
- Edit the program to correct the parameter reference.
|
64A6 (Aux: 001E) Adaptive program |
Cause: Output to parameter failed because parameter was write-protected.
Remedy:
- Check the parameter reference in the program.
- Check for other sources affecting the target parameter.
|
64A6 (Aux: 0023) Adaptive program |
Cause: Program file incompatible with current firmware version.
Remedy:
- Adapt the program to current block library and firmware version.
|
64B1 Internal SSW fault |
Cause: Internal fault.
Remedy:
- Reboot the control unit (parameter 96.08) or cycle power.
- If problem persists, contact your local ABB representative.
|
64B2 User set fault |
Cause: Loading of user parameter set failed (set missing, incompatible, or drive switched off during load).
Remedy:
- Ensure that a valid user parameter set exists.
- Reload if uncertain.
|
64E1 Kernel overload |
Cause: Operating system error.
Remedy:
- Reboot the control unit (parameter 96.08) or cycle power.
- If problem persists, contact your local ABB representative.
|
6581 Parameter system |
Cause: Parameter load or save failed.
Remedy:
- Try forcing a save using parameter 96.07 Parameter save manually.
- Retry.
|
6591 Backup/Restore timeout |
Cause: Control panel or PC-tool failed to communicate during backup/restore.
Remedy:
- Check control panel or PC-tool communication.
|
65A1 FBA A parameter conflict |
Cause: Drive lacks functionality requested by PLC, or functionality not activated.
Remedy:
- Check PLC programming.
- Check settings of parameter groups 50 Fieldbus adapter (FBA) and 51 FBA A settings.
|
6681 EFB comm loss |
Cause: Communication break in embedded fieldbus (EFB).
Remedy:
- Check status of fieldbus master.
- Check cable connections to EIA-485/X5 terminals 29, 30, 31.
|
6682 EFB config file |
Cause: Embedded fieldbus (EFB) configuration file could not be read.
Remedy:
- Contact your local ABB representative.
|
6683 EFB invalid parameterization |
Cause: EFB parameter settings inconsistent or not compatible with protocol.
Remedy:
- Check the settings in parameter group 58 Embedded fieldbus.
|
6684 EFB load fault |
Cause: EFB protocol firmware could not be loaded or version mismatch.
Remedy:
- Contact your local ABB representative.
|
6685 EFB fault 2 |
Cause: Fault reserved for the EFB protocol application.
Remedy:
- Check the documentation of the protocol.
|
6686 EFB fault 3 |
Cause: Fault reserved for the EFB protocol application.
Remedy:
- Check the documentation of the protocol.
|
6882 Text 32-bit table overflow |
Cause: Internal fault.
Remedy:
- Reset the fault.
- Contact your local ABB representative if fault persists.
|
6885 Text file overflow |
Cause: Internal fault.
Remedy:
- Reset the fault.
- Contact your local ABB representative if fault persists.
|
7081 Control panel loss |
Cause: Control panel or PC tool selected as active control location has ceased communicating.
Remedy:
- Check PC tool or control panel connection.
- Check control panel connector.
- Disconnect and reconnect the control panel.
|
7082 I/O module comm loss |
Cause: Communication between IO module and drive is not working properly.
Remedy:
- Check the IO module installation.
|
7085 Incompatible option module |
Cause: Fieldbus option module not supported.
Remedy:
- Replace the module with a supported type.
|
7086 AI Overvoltage |
Cause: An overvoltage has been detected on an analog input (switched to voltage mode temporarily).
Remedy:
|
7087 I/O module configuration |
Cause: I/O module configuration not supported or illegal.
Remedy:
- Check the auxiliary code (see specific sub-codes below).
|
7087 (Aux: 0001) I/O config |
Cause: S1/S2 DIP switch position on BIO-01 has changed after power up.
Remedy:
- Reboot control unit (cycle power or parameter 96.08) to activate new DIP switch position.
|
7087 (Aux: 0002) I/O config |
Cause: S1/S2 DIP switch positions are invalid (DO1 would be in both S1 and S2 pins).
Remedy:
- Change S1/S2 DIP switch positions to a supported combination.
- See parameter 05.99 BIO-01 DIP switch status.
|
7121 Motor stall |
Cause: Motor is operating in stall region (excessive load or insufficient power).
Remedy:
- Check motor load and drive ratings.
- Check fault function parameters.
|
7122 Motor overload |
Cause: Motor current is too high.
Remedy:
- Check for overloaded motor.
- Adjust parameters used for motor overload function (35.51…35.53 and 35.55…35.56).
|
7183 BR excess temperature |
Cause: Brake resistor temperature has exceeded fault limit (param 43.11).
Remedy:
- Stop drive. Let resistor cool down.
- Check resistor overload protection settings (Group 43).
- Check fault limit setting 43.11.
- Check that braking cycle meets allowed limits.
|
7192 BC IGBT excess temperature |
Cause: Brake chopper IGBT temperature has exceeded internal fault limit.
Remedy:
- Let chopper cool down.
- Check for excessive ambient temperature.
- Check for cooling fan failure/obstructions.
- Check resistor overload protection settings (Group 43).
- Check braking cycle and drive supply AC voltage.
|
7310 Overspeed |
Cause: Motor is turning faster than highest allowed speed.
Remedy:
- Check minimum/maximum speed settings (30.11, 30.12).
- Check adequacy of motor braking torque.
- Check need for brake chopper and resistor.
|
73B0 Emergency ramp failed |
Cause: Emergency stop did not finish within expected time.
Remedy:
- Check settings of parameters 31.32 and 31.33 (Supervision).
- Check predefined ramp times (23.11…23.15, 23.23).
|
73F0 Overfrequency |
Cause: Maximum allowed output frequency exceeded.
Remedy:
- Check the auxiliary code.
|
73F0 (Aux: 0xFA) Overfrequency |
Cause: Motor turning faster than allowed due to min/max freq settings or high supply voltage.
Remedy:
- Check min/max frequency settings (30.13, 30.14).
- Check used supply voltage and voltage selection parameter 95.01 Supply voltage.
|
7510 FBA A communication |
Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.
Remedy:
- Check status of fieldbus communication.
- See user documentation of fieldbus interface.
- Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out.
- Check cable connections.
- Check if communication master is able to communicate.
|
8001 ULC underload fault |
Cause: User load curve: Signal has been too long under the underload curve.
Remedy:
- See parameter 37.04 ULC underload actions.
|
8002 ULC overload fault |
Cause: User load curve: Signal has been too long over the overload curve.
Remedy:
- See parameter 37.03 ULC overload actions.
|
80A0 AI supervision |
Cause: An analog signal is outside the limits specified for the analog input.
Remedy:
- Check signal level at the analog input.
- Check the auxiliary code (below).
- Check the wiring connected to the input.
- Check the minimum and maximum limits of the input in parameter group 12 Standard AI.
|
80A0: 0001 AI1LessMIN |
Cause: Analog Input 1 value is less than minimum setting.
Remedy:
- Check signal wiring and limits for AI1.
|
80A0: 0002 AI1GreaterMAX |
Cause: Analog Input 1 value is greater than maximum setting.
Remedy:
- Check signal wiring and limits for AI1.
|
80A0: 0003 AI2LessMIN |
Cause: Analog Input 2 value is less than minimum setting.
Remedy:
- Check signal wiring and limits for AI2.
|
80A0: 0004 AI2GreaterMAX |
Cause: Analog Input 2 value is greater than maximum setting.
Remedy:
- Check signal wiring and limits for AI2.
|
80B0 Signal supervision 1 |
Cause: Fault generated by the signal supervision function 1.
Remedy:
- Check the source of the fault (parameter 32.07 Supervision 1 signal).
|
80B1 Signal supervision 2 |
Cause: Fault generated by the signal supervision function 2.
Remedy:
- Check the source of the fault (parameter 32.17 Supervision 2 signal).
|
80B2 Signal supervision 3 |
Cause: Fault generated by the signal supervision function 3.
Remedy:
- Check the source of the fault (parameter 32.27 Supervision 3 signal).
|
80B3 Signal supervision 4 |
Cause: Fault generated by the signal supervision function 4.
Remedy:
- Check the source of the fault (parameter 32.37 Supervision 4 signal).
|
80B4 Signal supervision 5 |
Cause: Fault generated by the signal supervision function 5.
Remedy:
- Check the source of the fault (parameter 32.47 Supervision 5 signal).
|
80B5 Signal supervision 6 |
Cause: Fault generated by the signal supervision function 6.
Remedy:
- Check the source of the fault (parameter 32.57 Supervision 6 signal).
|
9081 External fault 1 |
Cause: Fault in external device 1.
Remedy:
- Check the external device.
- Check setting of parameter 31.01 External event 1 source.
|
9082 External fault 2 |
Cause: Fault in external device 2.
Remedy:
- Check the external device.
- Check setting of parameter 31.03 External event 2 source.
|
9083 External fault 3 |
Cause: Fault in external device 3.
Remedy:
- Check the external device.
- Check setting of parameter 31.05 External event 3 source.
|
9084 External fault 4 |
Cause: Fault in external device 4.
Remedy:
- Check the external device.
- Check setting of parameter 31.07 External event 4 source.
|
9085 External fault 5 |
Cause: Fault in external device 5.
Remedy:
- Check the external device.
- Check setting of parameter 31.09 External event 5 source.
|
D401 Max cleaning fault |
Cause: The maximum number of cleanings are reached in the defined time. The pump cleaning is unable to clean the pump and hence, manual cleaning is required.
Remedy:
- Check the pump for blockages.
- Clean the pump manually if needed.
- Check parameters 83.35 Cleaning count fault to 83.37 Maximum cleaning count.
|
D404 Running dry |
Cause: Dry run protection is activated.
Remedy:
- Check the pump inlet for sufficient water level.
- Check dry run protection settings in parameters 82.20 Dry run protection and 82.21 Dry run source.
|
D405 Pipe fill-timeout |
Cause: Soft pipe fill has reached timeout limit. The PID output is not reached the setpoint after reference ramping is ended and the timeout limit is elapsed.
Remedy:
- Check the pipe for possible leakage.
- See parameter 82.25 Soft pipe fill supervision and 82.26 Time-out limit.
|
D40C Cavitation detected |
Cause: The pump is not getting enough liquid.
Remedy:
- Check the fluid level in the system.
- Restart the pump and confirm if cavitation is still occurring.
- Adjust the parameters used for the cavitation detection function (86.12 – 86.30) if needed.
|
FA81 Safe torque off 1 |
Cause: Safe torque off function is active, ie. STO circuit 1 is broken.
Remedy:
- Check safety circuit connections.
- For more information, see chapter The Safe torque off function in the Hardware manual.
- Check description of parameter 31.22 STO indication run/stop.
- Check the value of parameter 95.04 Control board supply.
|
FA82 Safe torque off 2 |
Cause: Safe torque off function is active, ie. STO circuit 2 is broken.
Remedy:
- Check safety circuit connections (same as FA81).
- Check parameter 95.04.
|
FF61 ID run |
Cause: Motor ID run was not completed successfully.
Remedy:
- Check the nominal motor values in parameter group 99 Motor data.
- Check that no external control system is connected to the drive.
- Cycle the power to the drive (and its control unit, if powered separately).
- Check that no operation limits prevent the completion of the ID run.
- Restore parameters to default settings and try again.
- Check that the motor shaft is not locked.
- Check the auxiliary code below for specific causes.
|
FF61: 0001 Maximum current limit too low |
Cause: Current limit restriction during ID run.
Remedy:
- Check settings of parameters 99.06 Motor nominal current and 30.17 Maximum current.
- Make sure that 30.17 > 99.06.
- Check that the drive is dimensioned correctly according to the motor.
|
FF61: 0002 Maximum speed limit or calculated field weakening point too low |
Cause: Speed/Frequency limits restricted.
Remedy:
- Check settings of parameters: 30.11 Minimum speed, 30.12 Maximum speed, 99.07 Motor nominal voltage, 99.08 Motor nominal frequency, 99.09 Motor nominal speed.
- Make sure that 30.12 > (0.55 × 99.09) > (0.50 × synchronous speed).
- Make sure 30.11 ≤ 0.
- Make sure supply voltage ≥ (0.66 × 99.07).
|
FF61: 0003 Maximum torque limit too low |
Cause: Torque limit restricted.
Remedy:
- Check settings of parameter 99.12 Motor nominal torque, and the torque limits in group 30 Limits.
- Make sure that the maximum torque limit in force is greater than 100%.
|
FF61: 0004 Current measurement calibration |
Cause: Calibration did not finish within reasonable time.
Remedy:
- Contact your local ABB representative.
|
FF61: 0005…0008 Internal error |
Cause: Internal software/hardware error during ID run.
Remedy:
- Contact your local ABB representative.
|
FF61: 0009 Acceleration fail (Async motors) |
Cause: Acceleration did not finish within reasonable time.
Remedy:
- Contact your local ABB representative.
|
FF61: 000A Deceleration fail (Async motors) |
Cause: Deceleration did not finish within reasonable time.
Remedy:
- Contact your local ABB representative.
|
FF61: 000B Speed drop (Async motors) |
Cause: Speed dropped to zero during ID run.
Remedy:
- Contact your local ABB representative.
|
FF61: 000C First accel fail (PM motors) |
Cause: First acceleration did not finish within reasonable time.
Remedy:
- Contact your local ABB representative.
|
FF61: 000D Second accel fail (PM motors) |
Cause: Second acceleration did not finish within reasonable time.
Remedy:
- Contact your local ABB representative.
|
FF61: 000E…0010 Internal error |
Cause: Internal error.
Remedy:
- Contact your local ABB representative.
|
FF61: 0011 Pulse test error (Synch Reluctance) |
Cause: Pulse test error.
Remedy:
- Contact your local ABB representative.
|
FF61: 0012 Motor too large for advanced standstill ID run |
Cause: Motor size incompatibility.
Remedy:
- Check that the motor and drive sizes are compatible.
- Contact your local ABB representative.
|
FF61: 0013 Motor data error (Async motors) |
Cause: Motor data error.
Remedy:
- Check that the motor nominal value settings in the drive are the same as in the motor nameplate.
- Contact your local ABB representative.
|
FF63 STO diagnostics failure |
Cause: SW internal malfunction.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
|
FF81 FB A force trip |
Cause: A fault trip command has been received through fieldbus adapter A.
Remedy:
- Check the fault information provided by the PLC.
|
FF8E EFB force trip |
Cause: A fault trip command has been received through the embedded fieldbus interface.
Remedy:
- Check the fault information provided by the PLC.
|