Lenze MC 1000 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUTPUT Output transistor fault: Output current exceeded 200% of drive rating. | Cause:
Remedy: Check motor wiring and motor for shorts. Check drive settings. |
| LO VOLTS Low DC Bus Voltage fault: DC bus voltage below 60% of normal. | Cause: Low line voltage. Remedy: Check AC input power. |
| HI VOLTS High DC Bus Voltage fault: DC bus voltage above 120% of normal. | Cause:
Remedy: Check input voltage. Adjust deceleration time. |
| HI TEMP Temperature fault: Internal drive temperature too high. | Cause:
Remedy: Check cooling fans and cabinet ventilation. |
| OVERLOAD Current Overload fault: Output current rating exceeded for too long. | Cause:
Remedy: Check mechanical load and motor sizing. (Note: 3-minute delay before reset is possible). |
| PWR TRAN Power Transient fault: Low line voltage. | Cause: AC line dipped or sagged. Remedy: Check mains supply stability. |
| PWR SAG Power Sag fault: Control board voltage is below tolerance. | Cause:
Remedy: Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset. |
| LANGUAGE Language fault: Selected language not present. | Cause:
Remedy: Replace or reinstall EEPROM. |
| EXTERNAL External fault: TB-13D is open or closed to TB-2, depending on the setting of Parameter 50 – TB13D. | Cause: External device triggered fault or wiring issue. Remedy:
|
| DB ERROR Dynamic Brake fault: DB circuit has sensed a resistor overload. | Cause: The DB duty cycle is too high, causing the resistors to overheat. Remedy: Reduce duty cycle or check resistor sizing. |
| CONTROL Control Board fault: New software has been installed that is different from the previous version. | Cause: Software/Hardware mismatch. Remedy: Perform a factory reset using Parameter 65-PROGRAM. This will update the software and allow the fault to be reset. |
| INTERNAL / INTERN (#) Internal fault: The micro-processor has sensed a problem. | Cause:
Remedy: Check control wiring shielding. |
| FOLLOWER Loss of Follower fault: 4-20 mA signal at TB-5B is below 2 mA. | Cause: Signal loss on input. Remedy: Parameter 55 – TB5B LOSS is set to FAULT. Check signal source. |
| Blank Display / TESTING The power supply has shut down. (Drive will not run). | Cause: This can be the result of clogged or failed heatsink fans. Remedy:
|