Schneider Lexium LXM16D Servo Drive

Fault Code and MeaningCause and Remedy
1100

Parameter out of permissible value range

Cause: The value entered was outside of the permissible value range for this parameter.



Remedy: The entered value must be within the permissible value range.
1101

Parameter does not exist

Cause: Error detected by parameter management: Parameter (subindex) does not exist.



Remedy: Select a different parameter (index).
1102

Parameter does not exist

Cause: Error detected by parameter management: Parameter (subindex) does not exist.



Remedy: Select a different parameter (sub-index).
1103

Parameter write not permissible (READ only)

Cause: Write access to read only parameter.



Remedy: Write only to parameters that are not read-only.
1104

Write access denied (no access authorization)

Cause: Parameter only accessible at expert level.



Remedy: The write access level expert is required.
1105

Block upload / Download not initialized

Cause: N/A



Remedy: N/A
1106

Command not permissible while power stage is active

Cause: Command not permissible while the power stage is enabled (operating state Operation Enabled or Quick Stop Active).



Remedy: Disable the power stage and repeat the command.
1107

Access via other interfaces blocked

Cause: Access occupied by another channel (for example: Commissioning software is active and fieldbus access was tried at the same time).



Remedy: Verify the channel that blocks access.
1108

File cannot be uploaded: Incorrect file ID

Cause: N/A



Remedy: N/A
1109

Data stored after a power outage is invalid

Cause: N/A



Remedy: N/A
110A

System error detected: No Bootloader available

Cause: N/A



Remedy: N/A
110B

Configuration download error detected

Cause: Error detected during parameter check (for example, reference velocity value for operating mode Profile Position is greater than maximum permissible velocity of drive).



Remedy: Value in additional error information shows the Modbus register address of the parameter where the initialization error was detected.
110D

Basic configuration of drive required after factory setting

Cause: “The ‘First Setup’ (FSU) was not run at all or not completed.



Remedy: Perform a First Setup.
110E

Parameter changed that requires a restart of the drive

Cause: Only displayed by the commissioning software. A parameter modification requires the drive to be powered off and on.



Remedy: Restart the drive to activate the parameter functionality. See the chapter Parameters for the parameter that requires a restart of the drive.
110F

Function not available in this type of device

Cause: The specific type of device does not support this function or this parameter value.



Remedy: Verify that you have the correct device type, in particular type of motor, type of encoder, holding brake.
1110

Incorrect file ID for upload or download

Cause: The specific type of device does not support this kind of file.



Remedy: Verify that you have the correct device type or the correct configuration file.
1111

File transfer not correctly initialized

Cause: A previous file transfer has been aborted.



Remedy: N/A
1112

Locking of configuration denied

Cause: An external tool has tried to lock the configuration of the drive for upload or download. This may not work because another tool had already locked the configuration of the drive or the drive is in an operating state that does not allow locking.



Remedy: N/A
1113

System not locked for configuration transfer

Cause: An external tool has tried to transfer the configuration without locking the drive.



Remedy: N/A
1114

Configuration download aborted

Cause: During a configuration download, a communication error or an error in the external tool was detected. The configuration was only partially transferred to the drive and might be inconsistent now.



Remedy: Power the drive off/on and retry to download the configuration or restore the factory settings.
1115

Incorrect configuration file format

Cause: An external tool has downloaded a configuration which has an incorrect format.



Remedy: N/A
1116

Request is processed asynchronously

Cause: N/A



Remedy: N/A
1117

Asynchronous request blocked

Cause: Request to a module is blocked because the module is currently processing another request.



Remedy: N/A
1118

Configuration data incompatible with device

Cause: The configuration data contains data from a different device.



Remedy: Verify device type including type of power stage.
1119

Incorrect data length, too many bytes

Cause: N/A



Remedy: N/A
111A

Incorrect data length, insufficient number of bytes

Cause: N/A



Remedy: N/A
111B

Configuration download error detected

Cause: During a configuration download, one or more configuration values were not accepted by the drive.



Remedy: Verify that the configuration file is valid and matches the type and version of the drive. The value in the additional error info shows the Modbus register address of the parameter where the initialization error was detected.
111C

Not possible to initialize recalculation for scaling

Cause: A parameter could not be initialized.



Remedy: The address of the parameter that caused the detected error can be read via the parameter _PAR_ScalingError.
111D

Original state of a parameter cannot be restored

Cause: The drive contained an invalid configuration before the recalculation was started. An error was detected during the recalculation.



Remedy: Power the drive off and on again. This may help you to identify the affected parameter(s). Change the parameters as required. Verify that the parameter configuration is valid before starting the recalculation procedure.
1123

Parameter cannot be changed

Cause: Recalculation for scaling is running.



Remedy: Wait for the running recalculation for scaling to finish.
1124

Timeout during recalculation for scaling

Cause: The time between the initialization of the recalculation and the start of the recalculation has been exceeded (30 seconds).



Remedy: Recalculation must be started within 30 seconds after initialization.
1125

Scaling not possible

Cause: The scaling factors for position, velocity or acceleration/deceleration are beyond internal calculation limits.



Remedy: Retry with different scaling factors.
1126

Configuration is blocked by another access channel

Cause: N/A



Remedy: Close other access channel (for example, other instance of commissioning software).
1127

Invalid key received

Cause: N/A



Remedy: N/A
112D

Configuration of edges is not supported

Cause: The selected capture input does not support rising and falling edge at the same time.



Remedy: Set the edge to either “rising” or “falling”.
1130

PTI pulse conflicts with home return in gear mode

Cause: Home return is not allowable when PTI has pulse.



Remedy: Don’t perform home return when PTI has pulse.
1131

PTI pulse conflicts with Jog test run in gear mode

Cause: Jog test run is not allowable when PTI has pulse.



Remedy: Don’t perform Jog test run when PTI has pulse.
1310

Frequency of the external reference value signal too high

Cause: The frequency of the external reference signals (A/B signals, P/D signals or CW/CCW signals) is higher than the permissible value.



Remedy: Verify the frequency of the external reference values. Verify the gear ratio in the operating mode Electronic Gear.
1311

The selected signal input function… cannot be configured

Cause: The selected signal input function or signal output function cannot be used in the selected operating mode.



Remedy: Select another function or change the operating mode.
1312

Limit switch or reference switch signal not defined

Cause: Reference movements require limit switches. These limit switches are not assigned to inputs.



Remedy: Assign the signal input functions Positive Limit Switch, Negative Limit Switch, and Reference Switch.
1313

Configured debounce time not possible for this signal input function

Cause: The signal input function does not support the selected debounce time.



Remedy: Set the debounce time to a valid value.
1314

At least two inputs have the same signal input function

Cause: The same signal input function has been assigned to at least two inputs.



Remedy: Reconfigure the inputs.
1315

Frequency of reference value signal is too high

Cause: The frequency of the pulse signal (A/B, Pulse/Direction, CW/CCW) exceeds the specified range. Received pulses may be lost.



Remedy: Adapt the frequency of the reference value signal to match the input specification of the drive. Also adapt the gear ratio in the operating mode Electronic Gear to the application requirements (position accuracy and velocity).
1317

Interference at PTI input

Cause: Interfering pulses or impermissible edge transitions (A and B signal simultaneously) have been detected.



Remedy: Verify cable specifications, shield connection and EMC.
1600

Oscilloscope: No additional data available

Cause: N/A



Remedy: N/A
1601

Oscilloscope: Parameterization incomplete

Cause: N/A



Remedy: N/A
1602

Oscilloscope: Trigger variable not defined

Cause: N/A



Remedy: N/A
1606

Logging still active

Cause: N/A



Remedy: N/A
1607

Logging: No trigger defined

Cause: N/A



Remedy: N/A
1608

Logging: Invalid trigger option

Cause: N/A



Remedy: N/A
1609

Logging: No channel selected

Cause: N/A



Remedy: N/A
160A

Logging: No data available

Cause: N/A



Remedy: N/A
160B

Parameter cannot be logged

Cause: N/A



Remedy: N/A
160C

Autotuning: Moment of inertia outside permissible range

Cause: The load inertia is too high.



Remedy: Verify that the system can easily be moved. Verify the load. Use a differently rated drive.
160E

Autotuning: Test movement could not be started

Cause: N/A



Remedy: N/A
160F

Autotuning: Power stage cannot be enabled

Cause: Autotuning was not started in the operating state Ready to Switch On.



Remedy: Start Autotuning when the drive is in the operating state Ready to Switch On.
1610

Autotuning: Processing stopped

Cause: Autotuning stopped by user command or by detected error (see additional error message in error memory, for example, DC bus undervoltage, limit switches triggered).



Remedy: Remove the cause of the stop and restart Autotuning.
1611

System error detected: Parameter could not be written during Autotuning

Cause: N/A



Remedy: N/A
1612

System error detected: Parameter could not be read during Autotuning

Cause: N/A



Remedy: N/A
1613

Autotuning: Maximum permissible movement range exceeded

Cause: The movement exceeded the adjusted movement range during Autotuning.



Remedy: Increase the movement range value.
1614

Autotuning: Already active

Cause: Autotuning has been started twice simultaneously or an Autotuning parameter is modified during Autotuning.



Remedy: Wait for Autotuning to finish before restarting Autotuning.
1615

Autotuning: This parameter cannot be changed while Autotuning is active

Cause: Parameter AT_gain or AT_J are written during Autotuning.



Remedy: Wait for Autotuning to finish before changing the parameter.
1617

Autotuning: Friction torque or load torque too great

Cause: The current limit has been reached (parameter P4-08).



Remedy: Verify that the system can easily be moved. Verify the load. Use a differently rated drive.
1618

Autotuning: Optimization aborted

Cause: The internal Autotuning sequence has not been finished, there may have been a following error.



Remedy: See the additional information provided in the error memory.
1619

Autotuning: Velocity jump in parameter AT_n_ref is not sufficient

Cause: Parameter AT_n_ref < 2 * AT_n_tolerance. The drive only checks this for the first velocity jump.



Remedy: Modify the parameter AT_n_ref or AT_n_tolerance to meet the required condition.
1620

Autotuning: Load torque too high

Cause: Product rating is not suitable for the machine load. Detected machine inertia is too high compared to the inertia of the motor.



Remedy: Reduce load, verify rating.
1621

System error detected: Calculation error

Cause: N/A



Remedy: N/A
1622

Autotuning: Not possible to perform Autotuning

Cause: Autotuning can only be performed if no operating mode is active.



Remedy: Terminate the active operating mode or disable the power stage.
1623

Autotuning: HALT request has stopped the autotuning process

Cause: Autotuning can only be performed if no operating mode is active.



Remedy: Terminate the active operating mode or disable the power stage.
1624

Auto adaptive tuning: The acceleration and deceleration below the lower limit

Cause: Acceleration below lower limit; inaccurate identification of real-time auto tuning.



Remedy: Increase the operational acceleration and deceleration.
1625

Adaptive notch filter: Oscillation frequency below the lower limit

Cause: When the oscillation frequency is less than 150Hz, the adaptive notch filter exhibits no obvious suppression effect.



Remedy: N/A
1A00

System error detected: FIFO memory overflow

Cause: N/A



Remedy: N/A
1A01

Motor has been changed (different type of motor)

Cause: Detected motor type is different from previously detected motor.



Remedy: Confirm the change.
1A03

System error detected: Hardware and firmware do not match

Cause: N/A



Remedy: N/A
1A04

System error detected: SDFM value not read in time

Cause: N/A



Remedy: Please contact the Technical Support Department.
1B00

System error detected: Incorrect parameters for motor and power stage

Cause: Incorrect manufacturer parameter value (data) non-volatile memory of device.



Remedy: Replace device.
1B02

Target value too high.

Cause: N/A



Remedy: N/A
1B04

Product of encoder simulation resolution and the maximum velocity is too high

Cause: Value in parameter P4-07 or resolution or the encoder simulation P0-18 are too high.



Remedy: Reduce the resolution of the encoder simulation in parameter P0-18 or the maximum velocity in parameter P4-07.
1B05

Error detected during parameter switching

Cause: N/A



Remedy: N/A
1B0B

The operating state at the beginning of the commutation offset identification must be Ready To Switch On

Cause: N/A



Remedy: Set the operating state to Ready To Switch On and restart commutation offset identification.
1B0C

Motor velocity too high.

Cause: N/A



Remedy: N/A
1B0F

Velocity deviation too high

Cause: N/A



Remedy: N/A
2201

System error detected: DC bus transfer error

Cause: N/A



Remedy: N/A
2300

Power stage overcurrent

Cause: Motor short circuit and disabling of the power stage. Motor phases are inverted.



Remedy: Verify the motor power connection.
2301

Braking resistor overcurrent

Cause: Braking resistor short circuit.



Remedy: If you use an external braking resistor, verify correct wiring and rating of the braking resistor.
2302

Output stage U-phase Sigma Delta overcurrent

Cause: Short circuit of the U phase of motor to the ground and other phases occurs or the output stage is disabled. Wrong wiring of phase line for motor.



Remedy: Eliminate the short circuit and ensure the power cable connection of motor is correct.
2303

Output stage W-phase Sigma Delta overcurrent

Cause: Short circuit of the W phase of motor to the ground and other phases occurs or the output stage is disabled. Wrong wiring of phase line for motor.



Remedy: Eliminate the short circuit and ensure the power cable connection of motor is correct.
2304

Output stage U- and W-phase Sigma Delta overcurrent

Cause: Short circuit of the U and W phases of motor to the ground and other phases occurs or the output stage is disabled. Wrong wiring of phase line for motor.



Remedy: Eliminate the short circuit and ensure the power cable connection of motor is correct.
2305

Excessively large output stage current offset

Cause: Excessively high load, motor stalling, loss of encoder connection, or incorrect connection of motor phase lines.



Remedy: Check the connection between motor and load; check the encoder connection; check the power cable connection of motor.
3100

Absence of power supply, undervoltage or overvoltage

Cause: The absence of phase lasts longer than 50 ms. The supply voltage is outside the valid range. The supply frequency is outside the valid range.



Remedy: Assure the consistency of supply voltage with technical parameters.
3101

Absence of 24V output of switching power supply

Cause: Switching power supply is out of service.



Remedy: Please contact the Technical Support Department.
3200

DC bus overvoltage

Cause: Excessively regeneration during deceleration.



Remedy: Verify correct deceleration ramp, rating of drive and braking resistor.
3201

DC bus undervoltage (shutdown threshold)

Cause: Power supply outage, insufficient power supply.



Remedy: Verify mains supply.
3202

DC bus undervoltage (Quick Stop threshold)

Cause: Power supply outage, insufficient power supply.



Remedy: Verify mains supply.
3206

Undervoltage DC bus, missing mains supply…

Cause: Lack of power supply or insufficient supply voltage.



Remedy: Verify that the values of the mains power supply network comply with the technical data.
4100

Power stage overtemperature

Cause: Transistors overtemperature: Ambient temperature is too high, fan is inoperative, dust.



Remedy: Verify the fan, improve the heat dissipation in the cabinet.
4101

Power stage overtemperature

Cause: Transistors overtemperature: Ambient temperature is too high, fan is inoperative, dust.



Remedy: Verify the fan, improve the heat dissipation in the cabinet.
4102

Power stage overload (I²t)

Cause: The current has exceeded the nominal value for an extended period of time.



Remedy: Verify rating, reduce cycle time.
4200

Device overtemperature

Cause: Excessively high ambient temperature due to, for example, dust.



Remedy: Improve heat dissipation in the control cabinet. If a fan is installed, verify correct operation of the fan. Install a fan in the control cabinet. Improve heat transfer from the rear wall of the device to the control cabinet.
4201

Excessively high temperature of CPU

Cause: Excessively high ambient temperature, dust or other factors impair the heat dissipation.



Remedy: Improve the heat dissipation of control cabinet. Please assure the proper functioning of fan (if any). Please install a fan in the control cabinet. Please improve the thermal conductivity from the back of equipment to the control cabinet.
4302

Motor overload (I²t)

Cause: The current has exceeded the nominal value for an extended period of time.



Remedy: Verify that the system can easily be moved. Verify the load. Use a differently sized motor, if necessary.
4402

Braking resistor overload (I²t > 75%)

Cause: Regeneration energy too high. External loads too high. Motor velocity too high. Deceleration too fast. Insufficient braking resistor.



Remedy: Reduce load, velocity, deceleration. Verify correct braking resistor rating.
4403

Braking resistor overload (I²t > 100%)

Cause: Regeneration energy too high. External loads too high. Motor velocity too high. Deceleration too fast. Insufficient braking resistor.



Remedy: Reduce load, velocity, deceleration. Verify correct braking resistor rating.
5207
Function is not supported

Cause: The hardware revision does not support the function.


Remedy:
5430
System error detected: EEPROM read error

Cause: System error detected.


Remedy:
5431
System error: EEPROM write error

Cause: System error detected.


Remedy:
5446
System error detected: EEPROM checksum error (used for power outage data)

Cause: Internal EEPROM not operative.


Remedy: Restart the drive. If the detected error persists, contact Technical Support.
5600
Motor connection phase error detected

Cause: Missing motor phase.


Remedy: Verify connection of motor phases.
5603
Commutation error detected

Cause: Incorrect wiring of motor cable. Encoder signals are lost or subject to interference. The load torque is greater than the motor torque. The encoder EEPROM contains incorrect data.


Remedy: Verify motor phases, verify encoder wiring. Improve EMC, verify grounding and shield connection. Use a differently sized motor that can withstand the load torque. Verify the motor data. Contact Technical Support.
5604
Output stage overcurrent is detected

Cause: Incorrect encoder signal/incorrect connection of motor phase line/motor overload.


Remedy: Assure the correct connection of encoder/ensure the correct power connection for motor/check the mechanical system to avoid stalling; check the matching between motor and load; check the acceleration ramp.
610D
Error detected in selection parameter

Cause: Incorrect parameter value selected.


Remedy: Verify the value to be written.
6114
System error detected: Impermissible function call from interrupt service routine

Cause: Incorrect programming.


Remedy:
7100
System error detected: Invalid power stage data

Cause: Error detected in power stage data stored in device (incorrect CRC), error detected in internal memory data.


Remedy: Contact Technical Support or replace the device.
7111
Parameter cannot be changed because the external braking resistor is active

Cause: An attempt is made to change one of the parameters P0-22, P0-23 or P0-24 even though the external braking resistor is active.


Remedy: Verify that the external braking resistor is not active if one of the parameters P0-22, P0-23 or P0-24 has to be changed.
7122
Invalid motor data parameter

Cause: Error detected in motor data stored in motor encoder, error detected in internal memory data.


Remedy: Contact Technical Support or replace the motor.
712D
Motor model data not configured

Cause: Motor model data not configured.


Remedy: Perform FSU “first setup” or set the parameter P6-00.
7136
Incorrect encoder type selected with parameter P6-01

Cause:


Remedy: Perform FSU “first setup” or set the parameter P6-01.
7139
Encoder offset: Data segment in encoder is incorrect

Cause:


Remedy:
713B
Motor has been changed (different type of motor)

Cause: Detected motor type is different from previously detected motor.


Remedy: Power-on the servo drive again. Restore the servo drive to factory default. Contact Technical Support or replace the device.
7200
System error detected: Calibration analog/digital converter during manufacturing / incorrect BLE file

Cause:


Remedy:
7347
System error detected: Position initialization not possible

Cause: Analog and digital encoder signals subject to massive interference.


Remedy: Reduce encoder signal interference, verify shield connection. Contact Technical Support.
7500
RS485/Modbus: Overflow error detected

Cause: EMC, cabling.


Remedy: Verify cables.
7501
RS485/Modbus: Framing error detected

Cause: EMC, cabling.


Remedy: Verify cables.
7502
RS485/Modbus: Parity error detected

Cause: EMC, cabling.


Remedy: Verify cables.
7503
RS485/Modbus: Receive error detected

Cause: EMC, cabling.


Remedy: Verify cables.
760C
Maximum encoder frequency exceeded

Cause: Velocity too high for the encoder.


Remedy:
7619
Incorrect communication between module and encoder

Cause: Incorrect encoder wiring/adjustment or incorrect encoder parameter settings.


Remedy: Verify encoder cable: wiring and shield connection. Verify encoder parameter settings. Verify encoder adjustment.
761A
Incorrect communication between module and encoder

Cause: Incorrect encoder wiring.


Remedy: Verify encoder cable: wiring and shield connection.
761D
Maximum velocity of the encoder is exceeded

Cause: Velocity too high for the encoder. In the case of BISS, the reason may also be a detected encoder communication error.


Remedy:
762A
Incremental encoder initialization failed

Cause: Encoder is not connected or the communication is disturbed, EMC.


Remedy: Please check the cable connection. Please check the cable specifications, shield connection and EMC.
762B
Incremental encoder initialization failed: The motor rotates when powered on

Cause: The motor rotates when the drive is powered on, which results in the failure of initial position identification.


Remedy: Stop and perform the power-on again.
762C
Motor velocity detected by incremental encoder exceeds maximum threshold

Cause: Encoder signal is disturbed, velocity is too high for the encoder.


Remedy: Reduce encoder signal interference, verify shield connection. Reduce motor velocity.
A061
Position change in reference value for operating mode Electronic Gear too high

Cause: Position reference change is too high. Error detected at signal input for reference value.


Remedy: Reduce the resolution of the master. Verify signal input for reference value signal.
A065
Parameter cannot be written

Cause: A data set is still active.


Remedy: Wait until the currently active data set has been terminated.
A068
Offset positioning not possible

Cause: Operating mode Electronic Gear inactive or no gear method selected.


Remedy: Start operating mode Electronic Gear and/or select a gear method.
A069
Setting the offset position is not possible

Cause: If offset positioning is active, it is not possible to set the position offset.


Remedy: Wait until ongoing offset positioning has finished.
A06B
Position deviation in operating mode Electronic Gear too high

Cause: The position deviation has become excessively high due to a velocity limitation or the release of direction.


Remedy: Verify the velocity of the external reference values and the velocity limitation. Verify release of direction.
A300
Deceleration after HALT request still running

Cause: HALT was removed too soon. New command was sent before motor standstill was reached after a HALT request.


Remedy: Wait for complete stop before removing HALT signal. Wait until motor has come to a complete standstill.
A301
Drive in operating state Quick Stop Active

Cause: Error with error class 1 detected. Drive stopped with Quick Stop.


Remedy:
A302
Stop by positive limit switch

Cause: The positive limit switch was activated because movement range was exceeded, incorrect operation of limit switch or signal disturbance.


Remedy: Verify application. Verify limit switch function and connection.
A303
Stop by negative limit switch

Cause: The negative limit switch was activated because movement range was exceeded, incorrect operation of limit switch or signal disturbance.


Remedy: Verify application. Verify limit switch function and connection.
A306
Stop by user-initiated software stop

Cause: Drive is in operating state Quick Stop Active due to a software stop request. The activation of a new operating mode is not possible, the error code is sent as the response to the activation command.


Remedy: Clear break condition with command Fault Reset.
A307
Interruption by internal software stop

Cause: In the operating modes Homing and Jog, the movement is internally interrupted by an internal software stop. The activation of a new operating mode is not possible.


Remedy: Perform a Fault Reset.
A308
Drive is in operating state Fault or Fault Reaction Active

Cause: Error with error class 2 or higher detected.


Remedy: Verify the error code (HMI or commissioning software), remove the cause and perform a Fault Reset.
A309
Drive not in operating state Operation Enabled

Cause: A command was sent that requires the drive to be in the operating state Operation Enabled (for example, a command to change the operating mode).


Remedy: Set drive to operating state Operation Enabled and repeat the command.
A310
Power stage not enabled

Cause: Command cannot be used because the power stage is not enabled (operating state Operation Enabled or Quick Stop Active).


Remedy: Set drive to an operating state in which the power stage is enabled, see state diagram.
A311
Operating mode change active

Cause: A start request for an operating mode has been received while a change of the operating mode was active.


Remedy:
A313
Position overflow, zero point is therefore no longer valid

Cause: The movement range limits were exceeded and the zero point is no longer valid. An absolute movement requires a valid zero point.


Remedy: Define a valid zero point by means of the operating mode Homing.
A317
Motor is not at a standstill

Cause: Command sent which is not permissible when the motor is not at a standstill. (e.g., Change of software limit switches, monitoring signals, reference point).


Remedy: Wait until the motor has come to a standstill (x_end = 1).
A318
Operating mode active (x_end=0)

Cause: Activation of a new operating mode is not possible while another operating mode is still active.


Remedy: Wait until the command in the operating mode has finished (x_end=1) or terminate active operating mode with HALT command.
A319
Manual tuning/Autotuning: Movement out of range

Cause: The movement exceeds the parameterized maximum movement range.


Remedy: Verify permissible movement range value and time interval.
A31A
Manual tuning/Autotuning: Amplitude/offset too high

Cause: Amplitude plus offset for tuning exceed internal velocity or current limitation.


Remedy: Choose lower amplitude and offset values.
A31B
Halt requested

Cause: Command not permissible while Halt is requested.


Remedy: Clear Halt request and repeat command.
A31C
Invalid position setting with software limit switch

Cause: Value for negative (positive) software limit switch is greater (less) than value for positive (negative) software limit switch.


Remedy: Set correct position values.
A31D
Velocity range exceeded parameter P4-07

Cause: The velocity was set to a value greater than the maximum permissible velocity in parameter P4-07 or current motor maximum velocity.


Remedy: Reduce the velocity value.
A31E
Stop by positive software limit switch

Cause: Not possible to execute command because positive software limit switch was triggered.


Remedy: Return to the permissible movement range.
A31F
Stop by negative software limit switch

Cause: Not possible to execute command because negative software limit switch was triggered.


Remedy: Return to the permissible movement range.
A320
Permissible position deviation exceeded

Cause: External load or acceleration are too high.


Remedy: Reduce external load or acceleration. Use a differently rated drive, if necessary. Error response can be adjusted via parameter P0-20.
A324
Error detected during homing

Cause: Homing movement was stopped in response to a detected error.


Remedy: Possible sub-error codes: E A325, E A326, E A327, EA328 or E A329.
A325
Limit switch to be approached not enabled

Cause: Homing to positive limit switch or negative limit switch is disabled.


Remedy: Enable limit switch via ‘IOsigLimP’ or ‘IOsigLimN’.
A326
Reference switch not found between positive limit switch and negative limit switch

Cause: Reference switch inoperative or not correctly connected.


Remedy: Verify the function and wiring of the Reference switch.
A329
More than one signal positive limit switch/negative limit switch/reference switch active

Cause: Reference switch or limit switch not connected correctly or supply voltage for switches too low.


Remedy: Verify the wiring and 24 VDC supply voltage.
A32A
Positive limit switch triggered with negative direction of movement

Cause: Start reference movement with negative direction and activate the positive limit switch (switch in opposite direction of movement).


Remedy: Verify correct connection and function of limit switch. Activate a jog movement with negative direction of movement.
A32B
Negative limit switch triggered with positive direction of movement

Cause: Start reference movement with positive direction and activate the negative limit switch (switch in opposite direction of movement).


Remedy: Verify correct connection and function of limit switch. Activate a jog movement with positive direction of movement.
A32C
Reference switch error detected (switch signal briefly enabled or switch overtraveled)

Cause: Switch signal disturbance. Motor subjected to vibration or shock when stopped after activation of the switch signal.


Remedy: Verify supply voltage, cabling and function of switch. Verify motor response after stopping and optimize control loop settings.
A32D
Positive limit switch error detected (switch signal briefly enabled or switch overtraveled)

Cause: Switch signal disturbance. Motor subjected to vibration or shock when stopped after activation of the switch signal.


Remedy: Verify supply voltage, cabling and function of switch. Verify motor response after stopping and optimize control loop settings.
A32E
Negative limit switch error detected (switch signal briefly enabled or switch overtraveled)

Cause: Switch signal disturbance. Motor subjected to vibration or shock when stopped after activation of the switch signal.


Remedy: Verify supply voltage, cabling and function of switch. Verify motor response after stopping and optimize control loop settings.
A32F
Index pulse not found

Cause: Index pulse signal not connected or not working properly.


Remedy: Verify index pulse signal and connection.
A330
Reference movement to index pulse cannot be Reproduced

Cause: The position difference between the index pulse and the switching point is insufficient.


Remedy: Increase the distance between the index pulse and the switching point. If possible, the distance between the index pulse and the switching point should be a half motor revolution.
A332
Jog error detected (additional info = detailed error code)

Cause: Jog movement was stopped in response to a detected error.


Remedy: For additional info, verify the detailed error code in the error memory.
A334
Timeout Standstill Window monitoring

Cause: Position deviation after movement greater than standstill window. This may have been caused by an external load.


Remedy: Verify load. Verify settings for standstill window (parameter P6-15, P6-16 and P6-17). Optimize control loop settings.
A336
System error detected: Jerk limitation with position offset after end of movement

Cause:


Remedy:
A338
Operating mode unavailable

Cause: The selected operating mode is not available.


Remedy:
A33A
No valid zero point (ref_ok=0)

Cause: No zero point defined by means of operating mode Homing. Zero point no longer valid due to movement beyond permissible movement range.


Remedy: Use operating mode Homing to define a valid zero point. Use a motor with an absolute encoder.
A33C
Function not available in this operating mode

Cause: Activation of a function which is not available in the active operating mode. Example: Start of backlash compensation while autotuning/manual tuning is active.


Remedy:
A347
Permissible position deviation exceeded

Cause: External load or acceleration are too high.


Remedy: Reduce external load or acceleration. Threshold value can be adjusted via the parameter P0-20.
A349
Position setting exceeds system limits

Cause: Position scaling of P5-01 and P5-02 results in a scaling factor that is too small.


Remedy: Change P5-01 and P5-02 in such a way as to increase the resulting scaling factor.
A350
Change for jerk filter input position too great

Cause: Operating mode Electronic Gear with processing method ‘Position synchronization with compensation movement’ has been activated which resulted in a position change greater than 0.25 revolutions.


Remedy: Deactivate jerk filter processing for Electronic Gear or use processing method ‘Position synchronization without compensation movement’.
A351
Function cannot be executed with this position scaling factor

Cause: The positions scaling factor is set to a value less than 1rev/131072usr_p, which is less than the internal resolution.


Remedy: Use a different position scaling factor or deactivate the selected function.
A35C
The triggered limit switch fails to move to the new reference position

Cause: The limit switch trigger signal holds, and the motor fails to move any more.


Remedy: Remove the limit switch signal.
B100
RS485/Modbus: Indeterminable service

Cause: Unsupported Modbus service was received.


Remedy: Verify application on the Modbus master.
B101
Incorrect I/O data configuration

Cause: The I/O data configuration or the Modbus I/O scanning configuration contains an invalid parameter.


Remedy: Verify the configuration of the I/O data.
B200
RS485/Modbus: Protocol error detected

Cause: Logical protocol error detected: Incorrect length or unsupported subfunction.


Remedy: Verify application on the Modbus master.
B201
RS485/Modbus: Interruption of the connection

Cause: Connection monitoring has detected an interruption of the connection.


Remedy: Verify all connections and cables used for data exchange. Verify that the device is on.
B202
RS485/Modbus: Interruption of the connection

Cause: Connection monitoring has detected an interruption of the connection.


Remedy: Verify all connections and cables used for data exchange. Verify that the device is on.
B203
RS485/Modbus: Incorrect number of monitor objects

Cause:


Remedy:
C200
One of the MD index exceeds border

Cause: One of the MD index exceed border. Available MD index is between 0 … 47.


Remedy: Please check script content.
C201
Error when loading script from EEPROM

Cause: Error when loading script from EEPROM.


Remedy: Power-on servo drive again. Perform factory restore to device. Contact Technical Support or replace the device.
C202
No script available

Cause: No script available.


Remedy: Download script to servo drive again. Contact Technical Support or replace the device.
C203
Script operation cycletime is exceeded

Cause: Too much script content, script can not be finished within cycletime defined in parameter P7-00.


Remedy: Increase value of parameter P7-00 or set P7-00 to 0.
C204
Insufficient RAM when saving script to EEPROM

Cause: Insufficient RAM when saving script to EEPROM.


Remedy: Try to simplify script content. Contact Technical Support or replace the device.
C205
Illegal operation of divided by 0 found in script

Cause: Illegal operation of divided by 0 found in script.


Remedy: Check script content.
C206
One of the timer base exceeds border

Cause: One of the timer base exceeds border. Available timer base is between 1 … 20000 ms.


Remedy: Check script content.
Exxx
User defined error in DYC mode

Cause:


Remedy: