ABB ACS880 Drive

📥 Download Catalog 📥 Download Manual
📥 Download Crane Manual  

Below image show terminal details:

Model no.R. MinP.BR Max
3-phase, 380 to 480 VohmKW
ACS880-01-02A4-3780.75
ACS880-01-03A3-3781.1
ACS880-01-04A0-3781.5
ACS880-01-05A6-3782.2
ACS880-01-07A2-3783
ACS880-01-09A4-3784
ACS880-01-12A6-3785.5
ACS880-01-017A-3397.5
ACS880-01-025A-33911
ACS880-01-032A-31915
ACS880-01-038A-31918.5
ACS880-01-045A-31322
ACS880-01-061A-31322

Search from below list for ACS880 drive faults & alarms:

Fault CodeCause & Solution
A2A1
Current calibration
Cause: Current offset and gain measurement calibration will occur at next start.

Solution: This is an Informative warning. (See parameter 99.13 ID run requested.)
A2B1
Overcurrent
Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this warning may also be caused by an earth fault or supply
phase loss.

Solution:

1. Check motor load.
2. Check acceleration times in parameter group
23 Speed reference ramp (speed control),
26 Torque reference chain (torque control) or
28 Frequency reference chain (frequency control).
3. Also check parameters 46.01 Speed scaling,
46.02 Frequency scaling and
46.03 Torque scaling.
4.Check motor and motor cable (including phasing and delta/star connection).
5. Check for an earth fault in motor or
motor cables by measuring the insulation resistances of motor and motor cable. See chapter Electrical installation, section
6. Checking the insulation of the assembly in the hardware manual of the drive.
7. Check there are no contactors opening
and closing in motor cable.
8. Check that the start-up data in parameter group 99 Motor data corresponds to the motor rating plate.
9. Check that there are no power factor
correction capacitors or surge absorbers in motor cable.
A2B3
Earth leakage
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.

Solution

1. Check there are no power factor correction capacitors or surge absorbers in motor cable.
2. Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
3. Check the insulation of the assembly in the hardware manual of the drive. If an earth fault is found, fix or change the motor cable and/or motor.
4. If no earth fault can be detected then hardware issue in drive.
A2B4
Short circuit
Cause: Short-circuit in motor cable(s) or motor.

Solution:

1. Check motor and motor cable for cabling errors.
2. Check motor and motor cable (including phasing and delta/star connection).
3. Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
4. Check there are no power factor correction capacitors or surge absorbers in motor cable.
A2BA
IGBT overload
Cause: Excessive IGBT junction to case temperature. This warning protects the IGBT(s) and can be activated by a short circuit in the motor cable.

Solution:

1. Check motor cable.
2. Check ambient conditions.
3. Check air flow and fan operation.
4. Check heatsink fins for dust pick-up.
5. Check motor power against drive power.
A3A1
DC link overvoltage
Cause: Intermediate circuit DC voltage too high (when the drive is stopped).

Solution:

1. Check the supply voltage setting (parameter 95.01 Supply voltage).
Note that the wrong setting of the parameter may cause the motor to rush uncontrollably, or may overload the brake chopper or resistor.
2. Check the supply voltage.
3. If the problem persists, then hardware issue in drive or other issue in drive.
A3A2
DC link undervoltage
Cause: Intermediate circuit DC voltage too low (when the drive is stopped).

Solution:

1. Check the supply voltage setting (parameter 95.01 Supply voltage).
Note that the wrong setting of the parameter may cause the motor to rush uncontrollably, or may overload the brake chopper or resistor.
2. Check the supply voltage.
3. If the problem persists, then hardware issue in drive or other issue in drive.
A3AA
DC not charged
Cause: The voltage of the intermediate DC circuit has not yet risen to operating level.

Solution:

1. Check the supply voltage setting (parameter 95.01 Supply voltage).
Note that the wrong setting of the parameter may cause the motor to rush uncontrollably, or may overload the brake chopper or resistor.
2. Check the supply voltage.
3. If the problem persists, then hardware issue in drive or other issue in drive.
A3C1
DC voltage
difference
Cause: Difference in DC voltages between parallel-connected inverter modules.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
A490
Incorrect temperature
sensor setup
Cause: Sensor type mismatch.

Solution: Check the settings of temperature source parameters 35.11.
A491
External temperature 1
Cause: Measured temperature 1 has exceeded warning limit.

Solution

1. Check the value of parameter 35.02 Measured temperature 1.
2. Check the cooling of the motor (or other equipment whose temperature is being measured).
3. Check the value of 35.13 Temperature 1 warning limit.
A4A1
IGBT
overtemperature
Cause: Estimated drive IGBT temperature is excessive.

Solution:

1. Check ambient conditions.
2. Check air flow and fan operation.
3. Check heatsink fins for dust pick-up.
4. Check motor power against drive power.
A4A9
Cooling
Cause: Drive module temperature is excessive.

Solution:

1. Check ambient temperature. If it exceeds 50 °C /122 °F, ensure that load current does not exceed derated load capacity of drive.
2. Check drive module cooling air flow and fan operation.
3. Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
A4B0
Excess
temperature
Cause: Power unit module temperature is excessive.

Solution:

Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
A4B1
Excess temperature
difference
Cause: High temperature difference between the IGBTs of different phases.

Solution:

1. Check the motor cabling.
2. Check cooling of drive module(s).
A4F6
IGBT temperature
Cause: Drive IGBT temperature is excessive.

Solution:

Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
A580
PU communication
Cause: Communication errors detected between the drive control unit and the power unit.

Solution:

1. Check the connections between the drive control unit and the power unit.
A5A0
Safe torque off
Cause: Safe torque off function is active, ie safety circuit signal(s) connected to connector STO is lost.

Solution:

1. Check safety circuit connections.
2. Check parameter 31.22 STO indication run/stop.
A5EA
Measurement circuit
temperature
Cause: Problem with internal temperature measurement of the drive.

Solution:

1. Check drive hardware.
2. May be hardware issue in drive.
A5EB
PU board
powerfail
Cause: Power unit power supply failure.

Solution:

1. Check drive hardware.
2. May be hardware issue in drive.
A5EC
PU communication
internal
Cause: Communication errors detected between the drive control unit and the power unit.

Solution:

1. Check the connections between the drive control unit and the power unit.
A5ED
Measurement
circuit ADC
Cause: Measurement circuit fault.

Solution:

1. Check drive hardware.
2. May be hardware issue in drive.
A5EE
Measurement
circuit DFF
Cause: Measurement circuit fault.

Solution:

1. Check drive hardware.
2. May be hardware issue in drive.
A5EF
PU state
feedback
Cause: State feedback from output phases does not match control signals.

Solution:

1. Check drive hardware.
2. May be hardware issue in drive.
A5F0
Charging feedback
Cause: Charging feedback signal missing.

Solution:

1. Check the feedback signal coming from the charging system.
A6A4
Motor nominal
value
Cause: The motor parameters are set incorrectly. The drive is not dimensioned
correctly.

Solution:

1. Check the settings of the motor configuration parameters in group 99.
2. Check that the drive is sized correctly for the motor.
A6A5
No motor data
Cause: Parameters in group 99 have not been set.


Solution:

1. Check that all the required parameters in group 99 have been set.

Note: It is normal for this warning to appear during the start-up and continue until the motor data is
entered.
A6A6
Voltage category
unselected
Cause: The voltage category has not been defined.


Solution: Set voltage category in parameter 95.01 Supply voltage.
A6D1
FBA A
parameter
conflict
Cause: The drive does not have a functionality requested by a PLC, or requested functionality has not been activated.

Solution:

1. Check PLC programming.
2. Check settings of parameter groups 50 Fieldbus adapter (FBA).
A6E5
AI parametrization
Cause: The current/voltage hardware setting of an analog input does not correspond to parameter settings.


Solution:

1. Check the event log for an auxiliary code. The code identifies the analog input whose settings are in conflict. Adjust parameter 12.15/ 12.25.

Note: Control board reboot (either by cycling the power or through parameter 96.08 Control board boot) is required to validate any changes in the hardware settings.
A780
Motor stall
Cause: Motor is operating in stall region because of e.g. excessive load or insufficient motor power.


Solution:

1. Check motor load and drive ratings.
2. Check fault function parameters.
3. This is a programmable warning check parameter 31.24 Stall function.
A782
FEN
temperature
Cause 1: Error in temperature measurement when temperature sensor (KTY or PTC) connected to encoder interface FEN-xx is used.

Solution: Check that parameter 35.11 Supervision 1 source / 35.21 Supervision 2 source setting corresponds to actual encoder interface installation.

Cause 2: Error in temperature measurement when KTY sensor connected to encoder interface FEN-01 is used.

Solution: FEN-01 does not support temperature measurement with KTY sensor. Use PTC sensor or other encoder interface module.
A791
Brake resistor
Cause: Brake resistor broken or not connected.


Solution:

1. Check that a brake resistor has been connected.
2. Check the condition of the brake resistor.
A793
BR excess
temperature
Cause: Brake resistor temperature has exceeded warning limit defined by parameter 43.12 Brake resistor warning limit.


Solution:

1. Stop drive. Let resistor cool down.
2. Check resistor overload protection function settings (parameter group 43 Brake chopper).
3. Check warning limit setting, parameter 43.12 Brake resistor warning limit.
4. Check that the resistor has been dimensioned correctly.
5. Check that braking cycle meets allowed limits.
A794
Brake resistor
wiring
Cause: Brake resistor short circuit or brake chopper control fault

Solution:

1. Check brake chopper and brake resistor connection.
2. Ensure brake resistor is not damaged.
A79B
BC short
circuit
Cause: Short circuit in brake chopper IGBT.

Solution:

– Replace brake chopper (if external).
– Drives with internal choppers will need to be returned to ABB.
– Ensure connection and no damages to brake resistor.
A79C
BC IGBT excess
temperature
Cause: Brake chopper IGBT temperature has exceeded internal warning limit.

Solution:

1. Let chopper cool down.
2. Check for excessive ambient temperature.
3. Check for cooling fan failure.
4. Check for obstructions in the air flow.
5 Check the dimensioning and cooling of the cabinet.
6. Check resistor overload protection function settings (parameters 43.06… 43.10).
7. Check minimum allowed resistor value for the chopper being used.
9. Check that braking cycle meets allowed limits.
10 Check that drive supply AC voltage is not excessive.
A7A1
Mechanical brake
closing failed
Cause: Mechanical brake control warning.

Solution:

1. Check mechanical brake connection.
2. Check mechanical brake settings in parameter group 44 Mechanical brake control.
3. Check that acknowledgment signal matches the actual status of the brake.
A7A2
Mechanical brake
opening failed
Cause: Status of mechanical brake acknowledgment is not as expected during brake open.

Solution:

1. Check mechanical brake connection.
2. Check mechanical brake settings in parameter group 44 Mechanical brake control.
3. Check that acknowledgment signal matches the actual status of brake.
A7A5
Mechanical brake
opening not allowed
Cause: Open conditions of mechanical brake cannot be fulfilled (e.g., brake has been prevented from opening by parameter 44.11)

Solution:

1. Check mechanical brake settings in parameter group 44 Mechanical brake control (especially 44.11).
2. Check that the acknowledgment signal (if used) matches the actual status of the brake.
A7B0
Motor speed
feedback
Cause: Motor speed feedback has failed and drive continues operation with open loop control.

Solution:

1. Check the settings of the parameters in groups 90 Feedback selection, 91 Encoder module settings and 92 Encoder 1 configuration.
2. Check encoder installation.
3. This is a Programmable warning: check parameter 90.45 Motor feedback fault.
A7C1
FBA A
communication
Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.

Solution:

1. Check status of fieldbus communication.
2. Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out.
3. Check cable connections.
4. Check if communication master is able to communicate.
5. This is a Programmable warning: check parameter 50.02 FBA A comm loss function.
A7E1
Encoder 1
Cause: Encoder 1 error.

Solution:

1. Check that the parameter settings in groups 92 Encoder 1 configuration are correct.

Note: New settings will only take effect after parameter 91.10 Encoder parameter refresh is used or after the drive control unit is powered up the next time.

2. Check the event log for an auxiliary code. See appropriate actions for each code below.

– Aux code: 410 Data read error- There is an hardware or software issue.
– Aux code: 411 Overspeed- There is an hardware or software issue.
– Aux code: 412 Pulse overfrequency- There is an hardware or software issue.
– Aux code: 413 Cable fault Check the wiring of the encoder. See also parameters 92.20 Enc cable fault func and 92.21 Enc cable fault mode.
– Aux code: 414 Resolver ID run fault- There is an hardware or software issue.
– Aux code: 415 Resolver SW version- There is an hardware or software issue.
– Aux code: 416 Resolver speed scale- There is an hardware or software issue.
– Aux code: 424 Data read error- There is an hardware or software issue.
– Aux code: 425 Cable fault mode not supported Current setting of 92.21 Enc cable fault mode not supported by the FEN-xx module.
– Aux code: 514 Communication loss Check the wiring of the encoder.
A7E2
Encoder 2
Cause: Encoder 2 has been activated by parameter but the encoder interface (FEN-xx) cannot be found.

Solution:

1. Check that the parameter settings in groups 93 Encoder 2 configuration are correct.

Note: New settings will only take effect after parameter 91.10 Encoder parameter refresh is used or after the drive control unit is powered up the next time.

2. Check the event log for an auxiliary code.
– Aux code: 410 Data read error- There is an hardware or software issue.
– Aux code: 411 Overspeed- There is an hardware or software issue.
– Aux code: 412 Pulse overfrequency- There is an hardware or software issue.
– Aux code: 413 Cable fault Check the wiring of the encoder. See also parameters 92.20 Enc cable fault func and 92.21 Enc cable fault mode.
– Aux code: 414 Resolver ID run fault- There is an hardware or software issue.
– Aux code: 415 Resolver SW version- There is an hardware or software issue.
– Aux code: 416 Resolver speed scale- There is an hardware or software issue.
– Aux code: 424 Data read error- There is an hardware or software issue.
– Aux code: 425 Cable fault mode not supported Current setting of 92.21 Enc cable fault mode not supported by the FEN-xx module.
– Aux code: 514 Communication loss Check the wiring of the encoder.
A7EE
Panel loss
Cause: Control panel or PC tool selected as active control location for drive has ceased communicating.

Solution:

1. Check PC tool or control panel connection.
2. Check control panel connector.
3. Check mounting platform if being used. Disconnect and reconnect the control panel.
4. This is a programmable warning check parameter 49.05 Communication loss action.
A880
Motor bearing
warning
Cause: Warning generated by an on-time timer or a value counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 4: 33.53 Value counter 1 source
– 5: 33.63 Value counter 2 source.
3. This is a Programmable warnings also check following parameter :
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
– 33.55 Value counter 1 warning select
– 33.65 Value counter 2 warning selection
A881
Output relay
warning
Cause: Warning generated by an edge counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 2: 33.33 Edge counter 1 source
– 3: 33.43 Edge counter 2 source.
3. This is a Programmable warnings also check following parameters:
– 33.35 Edge counter 1 warning selection
– 33.45 Edge counter 2 warning selection
A882
Motor starts
warning
Cause: Warning generated by an edge counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 2: 33.33 Edge counter 1 source
– 3: 33.43 Edge counter 2 source.
3. This is a Programmable warnings also check following parameters:
– 33.35 Edge counter 1 warning selection
– 33.45 Edge counter 2 warning selection
A883
Power ups
warning
Cause: Warning generated by an edge counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 2: 33.33 Edge counter 1 source
– 3: 33.43 Edge counter 2 source.
3. This is a Programmable warnings also check following parameters:
– 33.35 Edge counter 1 warning selection
– 33.45 Edge counter 2 warning selection
A884
Main contactor
warning
Cause: Warning generated by an edge counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 2: 33.33 Edge counter 1 source
– 3: 33.43 Edge counter 2 source.
3. This is a Programmable warnings also check following parameters:
– 33.35 Edge counter 1 warning selection
– 33.45 Edge counter 2 warning selection
A885
DC charge
warning
Cause: Warning generated by an edge counter.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 2: 33.33 Edge counter 1 source
– 3: 33.43 Edge counter 2 source.
3. This is a Programmable warnings also check following parameters:
– 33.35 Edge counter 1 warning selection
– 33.45 Edge counter 2 warning selection
A886
On-time 1
warning
Cause: Warning generated by on-time timer 1.

Solution:

1. Check the source of the warning (parameter 33.13 On-time 1 source).
2. This is a Programmable warning: check parameter 33.14 On-time 1 warning select.
A887
On-time 2
warning
Cause: Warning generated by on-time timer 2.

Solution:

1. Check the source of the warning (parameter 33.23 On-time 2 source).
2. This is a Programmable warning: check parameter 33.24 On-time 2 warning select.
A888
Edge counter 1
warning
Cause: Warning generated by edge counter 1.

Solution:

1. Check the source of the warning (parameter 33.33 Edge counter 1 source).
2. This is a Programmable warning: check parameter 33.35 Edge counter 1 warning selection.
A889
Edge counter 2
warning
Cause: Warning generated by edge counter 2.

Solution:

1. Check the source of the warning (parameter 33.43 Edge counter 2 source).
2. This is a Programmable warning: check parameter 33.45 Edge counter 2 warning selection.
A88A
Value integrator 1
warning
Cause: Warning generated by value counter 1.

Solution:

1. Check the source of the warning (parameter 33.53 Value counter 1 source).
2. This is a Programmable warning: check parameter 33.55 Value counter 1 warning select.
A88B
Value integrator 2
warning
Cause: Warning generated by value counter 2.

Solution:

1. Check the source of the warning (parameter 33.63 Value counter 2 source).
2. This is a Programmable warning: check parameter 33.65 Value counter 2 warning select.
A88C
Device clean
warning
Cause: Warning generated by an on-time timer.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 10: 05.04 Fan on-time counter.
3. This is a Programmable warnings check following parameter also:
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
A88D
DC capacitor
warning
Cause: Warning generated by an on-time timer.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 10: 05.04 Fan on-time counter.
3. This is a Programmable warnings check following parameter also:
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
A88E
Cabinet fan
warning
Cause: Warning generated by an on-time timer.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 10: 05.04 Fan on-time counter.
3. This is a Programmable warnings check following parameter also:
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
A88F
Cooling fan
warning
Cause: Warning generated by an on-time timer.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 10: 05.04 Fan on-time counter.
3. This is a Programmable warnings check following parameter also:
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
A890
Additional
cooling fan
warning
Cause: Warning generated by an on-time timer.

Solution:

1. Check the event log for an auxiliary code.
2. Check the source of the warning corresponding to the code:
– 0: 33.13 On-time 1 source
– 1: 33.23 On-time 2 source
– 10: 05.04 Fan on-time counter.
3. This is a Programmable warnings check following parameter also:
– 33.14 On-time 1 warning select
– 33.24 On-time 2 warning select
A8B0
Signal supervision
Cause: Warning generated by a signal supervision function.

Solution:
1. Check the source of the warning (parameter 32.07 Supervision 1 signal).
2. This is a programmable warning check parameter 32.06 Supervision 1 action

A981
External warning 1
Cause: Fault in external device 1.

Soultion:

1. Check the external device.
2. Check setting of parameter 31.01 External event 1 source.
3. This is a Programmable warning: check parameter – 31.01 External event 1 source 31.02 External event 1 type
AF8C
Process PID
sleep mode
Cause: The drive is entering sleep mode.

Solution:

1. This is a informative warning.
2. See section Sleep function for process PID control (page 39), and parameters 40.41…40.48.

AFAA
Autoreset
Cause: A fault is about to be autoreset.

Solution:

1. This is a informative warning no need to take any action.
2. See the settings in parameter group 31 Fault functions.

AFE1
Emergency stop
(off2)
Cause: Drive has received an emergency stop (mode selection off2) command.

Solution:

1. Check that it is safe to continue operation. Then return emergency stop push button to normal position. Restart drive.
2. If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.

AFE2
Emergency stop
(off1 or off3)
Cause: Drive has received an emergency stop (mode selection off1 or off3) command.

Solution:

1. Check that it is safe to continue operation. Then return emergency stop push button to normal position. Restart drive.
2. If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.
AFEA
Enable start
signal missing
Cause: No enable start signal received.

Solution:

1. Check the setting of (and the source selected by) parameter 20.19 Enable start command.
AFEB
Run enable
missing
Cause: No run enable signal is received.

Solution:

1. Check setting of parameter 20.12 Run enable 1 source.
2. Switch signal on (e.g. in the fieldbus Control Word) or check wiring of selected source.
AFF6
Identification run
Cause: Motor ID run will occur at next start.

Solution:

1. This is a informative warning no need to take any action.
AFF7
Autophasing
Cause: Autophasing will occur at next start.

Solution:

1. This is a informative warning no need to take any action.
2281
Calibration
Cause: Measured offset of output phase current measurement or difference between output phase U2 and W2 current measurement is too great (the values are updated during current calibration).

Solution:

1. Try performing the current calibration again.
2. If problem not resolved then need to repair or replace drive.
2310
Overcurrent
Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this fault may also be caused by an earth fault or supply phase loss.

Solution:

1. Check motor load.
2. Check acceleration times in parameter group 23 Speed reference ramp (speed control), 26 Torque reference chain (torque control) or 28 Frequency reference chain (frequency control).
3. Also check parameters 46.01 Speed scaling, 46.02 Frequency scaling and 46.03 Torque scaling.
4. Check motor and motor cable (including phasing and delta/star connection).
5. Check there are no contactors opening and closing in motor cable.
6. Check that the start-up data in parameter group 99 Motor data corresponds to the motor rating plate.
7. Check that there are no power factor correction capacitors or surge absorbers in motor cable.
8. Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
2330
Earth leakage
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.

Solution:

1. Check there are no power factor correction capacitors or surge absorbers in motor cable.
2. Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
3. Try running the motor in scalar control mode if allowed. (See parameter 99.04 Motor control mode.)
4. After this if problem not resolved then need to repair or replace drive.
2340
Short circuit
Cause: Short-circuit in motor cable(s) or motor. Aux code 0x0080 indicates that the state feedback from output phases does not match the control signals.

Solution:

1. Check motor and motor cable for cabling errors.
2. Check there are no power factor correction capacitors or surge absorbers in motor cable.
3. Cycle the power to the drive.
2381
IGBT overload
Cause: Excessive IGBT junction to case temperature. This fault protects the IGBT(s) and can be activated by a short circuit in the motor cable.

Solution:

1. Check motor cable.
2. Check ambient conditions.
3. Check air flow and fan operation.
4. Check heatsink fins for dust pick-up.
5. Check motor power against drive power.
3130
Input phase
loss
Cause: Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse.

Solution:

1. Check input power line fuses.
2. Check for loose power cable connections.
3. Check for input power supply imbalance.
3180
Charge relay
lost
Cause: No acknowledgement received from charge relay.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
3181
Cross
connection
Cause: Incorrect input power and motor cable connection (i.e. input power cable is connected to drive motor connection).

Solution:

1. Check input power connections.
3210
DC link
overvoltage
Cause: Excessive intermediate circuit DC voltage.

Solution:

1. Check that overvoltage control is on (parameter 30.30 Overvoltage control).
2. Check that the supply voltage matches the nominal input voltage of the drive.
3. Check the supply line for static or transient overvoltage.
4. Check deceleration time. Use coast-to-stop function (if applicable).
5. Retrofit drive with brake chopper and brake resistor.
6. Check that the brake resistor is dimensioned properly and the resistance is between acceptable range for the drive.
3220
DC link
undervoltage
Cause: Intermediate circuit DC voltage is not sufficient because of a missing supply phase, blown fuse or fault in the rectifier bridge.

Solution:

1. Check supply cabling, fuses and switchgear.
3280
Standby
timeout
Cause: Automatic restart failed.

Solution:

1. Check the condition of the supply (voltage, cabling, fuses, switchgear).
3291
DC voltage
difference
Cause: Difference in DC voltages between parallel connected inverter modules.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
3381
Output phase
loss
Cause: Motor circuit fault due to missing motor connection (any of the three phases not connected).
In scalar control mode, the drive detects fault only when the output frequency is above 10% of the motor nominal frequency.


Solution:

1. Connect motor cable.
2. If the drive is in scalar mode and nominal current of the motor is less than 1/6 of the nominal output current of the drive, set parameter 31.19 Motor phase loss to No action.
3385
Autophasing
Cause: Autophasing routine has failed.

Solution: Try other autophasing modes (see parameter 21.13 Autophasing mode) if possible.
4210
IGBT
overtemperature
Cause: Estimated drive IGBT temperature is excessive.

Solution:

1. Check air flow and fan operation.
2. Check heatsink fins for dust pick-up.
3. Check motor power against drive power.
4. Check ambient conditions.
4290
Cooling
Cause: Drive module temperature is excessive.

Solution:

1. Check ambient temperature. If it exceeds , ensure that load current does not exceed derated load capacity of drive.
2. Check drive module cooling air flow and fan operation.
3. Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
4310
Excess
temperature
Cause: Power unit module temperature is excessive.

Solution:

1. Check ambient conditions.
2. Check air flow and fan operation.
3. Check heatsink fins for dust pick-up.
4. Check motor power against drive power.
4380
Excess
temperature
difference
Cause: High temperature difference between the IGBTs of different phases.

Solution:

1. Check the motor cabling.
2. Check cooling of drive module(s).
42F1
IGBT
temperature
Cause: Drive IGBT temperature is excessive.

Solution:

1. Check ambient conditions.
2. Check air flow and fan operation.
3. Check heatsink fins for dust pick-up.
4. Check motor power against drive power.
4981
External
temperature 1
Cause: Measured temperature 1 has exceeded fault limit.

Solution:

1. Check the value of parameter 35.02 Measured temperature 1.
2. Check the cooling of the motor (or other equipment whose temperature is being measured).
3. Check the value of parameter 35.12 Temperature 1 fault limit.
5080
Fan
Cause: Cooling fan is stuck or disconnected.

Solution:

1. Check fan operation and connection.
2. Replace fan if faulty.
5090
STO hardware
failure
Cause: STO hardware diagnostics has detected hardware failure.


Solution: There is an hardware issue in drive. Need to repair or replace drive.
5091
Safe
torque off
Cause: Safe torque off function is active, ie. safety circuit signal(s) connected to connector STO is broken during start or run.

Solution:

1. Check safety circuit connections.
2. This is a Programmable fault: check parameter 31.22 STO indication run/stop.
5092
PU logic
error
Cause: Power unit memory has cleared.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5093
Rating ID
mismatch
Cause: The hardware of the drive does not match the information stored in the memory. This may occur eg. after a firmware update.

Solution:

1. Cycle the power to the drive.
2. You may have to be repeat this.
3. If fault not resolved after this then need to repair or replace drive.
5681
PU
communication
Cause: Communication errors detected between the drive control unit and the power unit.

Solution: Check the connection between the drive control unit and the power unit.
5682
Power unit
lost
Cause: Connection between the drive control unit and the power unit is lost.

Solution: Check the connection between the control unit and the power unit.
5690
PU communication
internal
Cause: Internal communication error.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5691
Measurement
circuit ADC
Cause: Measurement circuit fault.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5692
PU board
powerfail
Cause: Power unit power supply failure.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5693
Measurement
circuit DFF
Cause: Measurement circuit fault.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5694
PU communication
configuration
Cause: Version check cannot find a matching power unit FPGA logic.

Solution: Update the FPGA logic of the power unit.
5696
PU state
feedback
Cause: State feedback from output phases does not match control signals.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
5697
Charging
feedback
Cause: Charging feedback signal missing.

Solution: Check the feedback signal coming from the charging system.
5698
Unknown PU
fault
Cause: The power unit logic generated a fault which is not known by software.

Solution: Check the logic and software compatibility.
6180
Internal SW
error
Cause: Internal error.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
6181
FPGA version
incompatible
Cause: Firmware and FPGA versions are incompatible.

Solution:

1. Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
2. After this same problem comes then need to repair or replace drive.
6306
FBA A
mapping file
Cause: Fieldbus adapter A mapping file read error.

Solution: There is an hardware or software issue in drive need to repair or replace drive.
6481
Task
overload
Cause: Internal fault. There is an internal issue in drive

Solution:

1. Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
2. After this same problem then need to repair or replace drive.
6487
Stack overflow
Cause: Internal fault. There is an internal issue in drive

Solution:

1. Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
2. After this same problem then need to repair or replace drive.
64A1
Internal
file load
Cause: File read error. There is an internal issue in drive

Solution:

1. Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
2. After this same problem then need to repair or replace drive.
64A2
Internal record
load
Cause: Internal record load error.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
64A3
Application
loading
Cause: Application file incompatible or corrupted.

Note: This fault cannot be reset.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
64B2
User set
fault
Cause: Loading of user parameter set failed because
• requested set does not exist
• set is not compatible with control program
• drive was switched off during loading.

Solution: Ensure that a valid user parameter set exists. Reload if uncertain.
64E1
Kernel
overload
Cause: Operating system error.

Solution:

1. Reboot the control unit(using parameter 96.08 Control board boot) or by cycling power.
2. After this same problem then need to repair or replace drive.
6581
Parameter
system
Cause: Parameter load or save failed.

Solution: Try forcing a save using parameter 96.07 Parameter save manually. Retry.
65A1
FBA A
parameter
conflict
Cause: The drive does not have a functionality requested by PLC, or requested functionality has not been activated.

Solution:

1. Check PLC programming.
2. Check settings of parameter groups 50 Fieldbus adapter (FBA) and 51 FBA A settings.
6881
Text data
overflow
Cause: Internal fault.

Solution:

1. Reset the fault.
2. If fault not reset then there is an hardware or software issue in drive. Need to repair or replace drive.
6882
Text 32-bit
table overflow
Cause: Internal fault.

Solution: Reset the fault. If fault not reset then need to repair or replace drive.
6883
Text 64-bit
table overflow
Cause: Internal fault.

Solution: Reset the fault. If fault not reset then need to repair or replace drive.
6885
Text file
overflow
Cause: Internal fault.

Solution: Reset the fault. If fault not reset then need to repair or replace drive.
7080
Option module
comm loss
Cause: Communication between drive and option module (FEN-xx and/or FIO-xx) is lost.

Solution:

1. Check that the option modules are properly seated in their slots.
2. Check that the option modules or slot connectors are not damaged. To pinpoint the problem, try installing the modules into different slots.
7081
Panel port
communication
Cause: Control panel or PC tool selected as active control location for drive has ceased communicating.

Solution:

1. Check PC tool or control panel connection.
2. Check control panel connector.
3. Disconnect and reconnect the control panel.
4. This is a Programmable fault: check parameter 49.05 Communication loss action.
7121
Motor stall
Cause: Motor is operating in stall region because of e.g. excessive load or insufficient motor power.

Solution:

1. Check motor load and drive ratings.
2. Check fault function parameters.
7181
Brake resistor
Cause: Brake resistor broken or not connected.

Solution:

1. Check that a brake resistor has been
connected.heck the condition of the brake
resistor.
2. Check the dimensioning of the brake
resistor.
7183
BR excess
temperature
Cause: Brake resistor temperature has exceeded fault limit defined by parameter 43.11 Brake resistor fault limit.

Solution:

Stop drive.
Let resistor cool down.
Check resistor overload protection function settings (parameter group 43 Brake chopper).
Check fault limit setting, parameter 43.11 Brake resistor fault limit.
Check that braking cycle meets allowed limits.
7184
Brake resistor
wiring
Cause: Brake resistor short circuit or brake chopper control fault.

Solution:

1. Check brake chopper and brake resistor connection.
2. Ensure brake resistor is not damaged.
7191
BC short
circuit
Cause: Short circuit in brake chopper IGBT.

Solution:

1. Ensure brake resistor is connected and not damaged.
2. Check the electrical specifications of the brake resistor.
7192
BC IGBT
excess temp
Cause: Brake chopper IGBT temperature has exceeded internal fault limit.

Solution:

1. Let chopper cool down.Check for excessive ambient temperature.
2. Check for cooling fan failure.
3. Check for obstructions in the air flow.
4. Check the dimensioning and cooling of the cabinet.
5. Check that braking cycle meets allowed limits.
6. Check that drive supply AC voltage is not excessive.
71A2
Mechanical brake
closing failed
Cause: Mechanical brake control fault. Activated e.g., if brake acknowledgment is not as expected during brake closing.

Solution:

1. Check mechanical brake connection.
2. Check mechanical brake settings in parameter group 44 Mechanical brake control.
3. Check that the acknowledgment signal matches the actual status of the brake.
4. This is a Programmable fault: check parameter 44.17 Brake fault function
71A3
Mechanical brake
opening failed
Cause: Mechanical brake control fault. Activated e.g. if brake acknowledgment is not as expected during brake opening.

Solution:

1. Check mechanical brake connection.
2. Check mechanical brake settings in parameter group 44 Mechanical brake control.
3. Check that acknowledgment signal matches actual status of brake.
4. This is a Programmable fault: check parameter 44.17 Brake fault function
71A5
Mechanical brake
opening not
allowed
Cause: Open conditions of mechanical brake cannot be fulfilled (e.g., the brake has been prevented from opening by parameter 44.11).

Solution:

1. Check mechanical brake settings in parameter group 44 Mechanical brake control (especially 44.11).
2. Check that the acknowledgment signal (if used) matches the actual status of the brake.
7301
Motor speed
feedback
Cause: No motor speed feedback received. Encoder speed differs too much from internal speed estimate.
Solution:

1. Check the parameter 90.41 setting and the actual source selected.
2. Check electrical connection of the encoder and pulse sin/cos nr.
3. This is a Programmable fault: check parameter 90.45 Motor feedback fault
7310
Overspeed
Cause: Motor is turning faster than highest allowed speed due to incorrectly set minimum/maximum speed, insufficient braking torque or changes in load when using torque reference.

Solution:

1. Check minimum/maximum speed settings, parameters 30.11 Minimum speed and 30.12 Maximum speed.
2. Check adequacy of motor braking torque.
3. Check applicability of torque control.
4. Check need for brake chopper and resistor(s).
7380
Encoder internal
Cause: Internal fault.

Solution: There is an hardware or software issue in drive or encoder/encoder board. Need to repair or replace drive.
7381
Encoder 1
Cause: Encoder 1 feedback fault.

Solution:

1. If fault appears during first start-up before encoder feedback is used:
– Check cable between encoder and encoder interface module (FEN-xx) and order of connector signal wires at both ends of cable.
2. If fault appears after encoder feedback has already been used or during drive :
– Check that encoder connection wiring or encoder is not damaged.
– Check that encoder interface module (FEN-xx) connection or module is not damaged.
– Check earthings (when disturbances are detected in communication between encoder interface module and encoder).
3. For more information on encoders, see parameter groups 90 Feedback selection, 91 Encoder module settings, 92 Encoder 1 configuration and 93 Encoder 2 configuration.
7391
Encoder 2
Cause: Encoder 2 feedback fault.

Solution:

1. If fault appears during first start-up before encoder feedback is used:
– Check cable between encoder and encoder interface module (FEN-xx) and order of connector signal wires at both ends of cable.
2. If fault appears after encoder feedback has already been used or during drive :
– Check that encoder connection wiring or encoder is not damaged.
– Check that encoder interface module (FEN-xx) connection or module is not damaged.
– Check earthings (when disturbances are detected in communication between encoder interface module and encoder).
3. For more information on encoders, see parameter groups 90 Feedback selection, 91 Encoder module settings, 92 Encoder 1 configuration and 93 Encoder 2 configuration.
73A0
Speed feedback
configuration
Cause: Speed feedback configuration incorrect, eg. an encoder that is not present is selected as the feedback interface.

Solution:

1. Check the feedback source selection parameters in group 90 Feedback selection.
2. In case the source is an encoder interface, check parameter settings in groups 91 Encoder module settings, 92 Encoder 1 configuration and 93 Encoder 2 configuration.
73A1
Load feedback
Cause: No load feedback received.

Solution:

1. Check the setting of parameter 90.51 Load feedback selection, and the actual source selected.
2. In case the source is an encoder interface, check parameter settings in groups 91 Encoder module settings, 92 Encoder 1 configuration and 93 Encoder 2 configuration.
7510
FBA A
communication
Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.

Solution:

1. Check status of fieldbus communication.
2. Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out.
3. Check cable connections.
4. Check if communication master is able to communicate.
5. This is a Programmable fault: check parameter 50.02 FBA A comm loss function.
Note: If the module has been changed from FieldBus (for example FPBA) to some other option module (for example BMIO), the factory defaults need to be applied (see parameter 96.06).
80B0
Signal
supervision
Cause: Fault generated by the signal supervision 1 function.

Solution:

1. Check the source of the fault (parameter 32.07 Supervision 1 signal).
2. This is a Programmable fault: check parameter 32.06 Supervision 1 action
9081
External
fault 1
Cause: Fault in external device 1.

Solution:

Check the external device.
Check setting of parameter 31.01 External event 1 source.
This is a Programmable fault: check parameter 31.01 External event 1 source 31.02 External event 1 type.
FA81
Safe torque
off 1
Cause: Safe torque off function is active, ie. STO circuit 1 is broken.

Solution: Check safety circuit connections.
FA82
Safe torque
off 2
Cause: Safe torque off function is active, ie. STO circuit 2 is broken.

Solution: Check safety circuit connections.
FF61
ID run
Cause: Motor ID run was not completed successfully.

Solution:

1. Check the nominal motor values in parameter group 99 Motor data.
2. Check that no external control system is connected to the drive.
3. Cycle the power to the drive (and its control unit, if powered separately).
4. Check that no operation limits prevent the completion of the ID run. Restore parameters to default settings and try again.
5. Check that the motor shaft is not locked.
FF81
FB A force
trip
Cause: A fault trip command has been received through fieldbus adapter A.

Solution:

Check the fault information provided by the PLC.
FF82
FB B force
trip
Cause: A fault trip command has been received through fieldbus adapter B.

Solution:

1. Check the fault information provided by the PLC.
FF8E
EFB force
trip
Cause: A fault trip command has been received through the embedded fieldbus interface.

Solution: Check the fault information provided by the PLC.
2391
BU current
difference
Cause: AC phase current difference between parallel-connected inverter modules is excessive.

Solution:

1. Check motor cabling.
2. Check there are no power factor correction capacitors or surge absorbers in motor cable.
2392
BU earth
leakage
Cause: Total earth leakage of inverter modules is excessive.

Solution:

1. Check there are no power factor correction capacitors or surge absorbers in motor cable.
2. Measure insulation resistances of motor cables and motor.
2E01
Earth leakage
Cause: IGBT supply unit has detected an earth fault.

Solution:

1. Check AC fuseheck for earth leakages.
2. Check supply cabling.
3. Check power modules.
4. Check there are no power factor correction capacitors or surge absorbers in supply cable.
3000
Invalid
voltage chain
datapoints
Cause: Parametrization of the speed/torque limitation curve (in the DC voltage reference chain) are inconsistent.

Solution:

1. Check that the speed points of the curve (defined by 29.70…29.79) are in increasing order.
3E00
Input phase
loss
Cause : Input phase loss comes when input phase loss detected by the IGBT bridge. A 3E00 fault code in your ABB ACS880 drive indicates an input phase loss. This means the drive isn’t detecting all three phases of the incoming AC power supply.

Solution:

1. Check the auxiliary code.
2. Check the source of the fault corresponding to the code: 1: Phase A, 2: Phase B, 4: Phase C, 8: Phase cannot be detected.
3. Check the AC fuses.
4. Check for input power supply imbalance.