Siemens MM430 Drive

📥 Download Catalog 📥 Download Manual
📥 Download Parameter Manual  

Below image show terminal details:

Search from below list for MM430 drive faults & alarms:

Fault CodesCause & Solution
F0001
OverCurrent
Cause:
– Motor power (P0307) does not correspond to the inverter power (r0206)
– Motor leads are too long
– Motor lead short circuit
– Earth faults

Soultion:

Check the following:
– Motor power (P0307) must correspond to inverter power (r0206)
– Cable length limits must not be exceeded
– Motor cable and motor must have no short-circuits or earth faults
– Motor parameters must match the motor in use
– Value of stator resistance (P0350) must be correct
– Motor must not be obstructed or overloaded
– Increase the ramp time
– Reduce the boost level (V/f control: P1311 & P1312, Vector control: P1610 & P1611)
F0002
OverVoltage
Cause:

– DC-link controller disabled (P1240 = 0)
– DC-link voltage (r0026) exceeds trip level (P2172)
– Overvoltage can be caused either by too high main supply voltage or if motor is in regenerative mode. Regenerative mode can be caused by fast ramp downs or if the motor is driven from an active load.

Soultion:

Check the following:
– Supply voltage (P0210) must lie within limits indicated on rating plate
– DC-link voltage controller must be enabled (P1240) and parameterized properly
– Ramp-down time (P1121) must match inertia of load
– Required braking power must lie within specified limits

NOTE: Higher inertia requires longer ramp times; otherwise, apply braking resistor.
F0003
UnderVoltage
Cause:

– Main supply failed
– Shock load outside specified limits

Soultion:

Check the following:
– Supply voltage (P0210) must lie within limits indicated on rating plate
– Supply must not be susceptible to temporary failures or voltage reductions
– Enable kinetic buffering (P1240 = 2)
F0004
Inverter Over
Temperature
Cause:
– Ventilation inadequate
– Ambient temperature is too high

Soultion:

Check the following:
– Load conditions and duty cycle must be appropriate
– Fan must turn when inverter is running
– Pulse frequency (P1800) must be set to default value
– Ambient temperature could be higher than specified for the inverter
Additional meaning for MM440 Frame size FX & GX:
Fault value = 1: Rectifier overtemperature
= 2: Ambient overtemperature
= 3: EBOX overtemperature
F0005
Inverter I2t
Cause:
– Inverter overloaded
– Duty cycle too demanding
– Motor power (P0307) exceeds inverter power capability (r0206)


Soultion:

Check the following:
– Load duty cycle must lie within specified limits
– Motor power (P0307) must match inverter power (r0206)
F0011
Motor Over
Temperature
Cause: Possible Causes Motor overloaded.

Soultion:

Check the following:
– Load duty cycle must be correct
– Motor nominal overtemperatures (P0626-P0628) must be correct
– Motor temperature warning level (P0604) must match

If P0601 = 0 or 1, check the following:
– Check if name plate data are correct (if not perform quick commissioning)
– Accurate equivalent circuit data can be found by performing motor identification (P1910=1)
– Check if motor weight (P0344) is reasonable. Change if necessary
– Via P0626, P0627, P0628 the standard overtemperatures can be changed, if the motor is not a Siemens standard motor

If P0601 = 2, check the following:
– Check if temperature shown in r0035 is reasonable
– Check if the sensor is a KTY84 (other sensors are not supported)
F0012
Inverter temp.
signal lost
Cause: Wire breakage of inverter temperature (heatsink) sensor.

Solution:

1. Check drive control wiring.
F0015
Motor temperature
signal lost
Cause: Open or short circuit of motor temperature sensor. If signal loss is detected, temperature monitoring switches over to monitoring with the motor thermal model.
F0020
Mains Phase
Missing
Cause: Fault occurs if one of the three input phases are missed while the pulses are enabled and drive is loaded

Soultion:

1. Check the input wiring of the mains phases.
F0021
Earth fault
Cause: Fault occurs if the sum of the phase currents is higher than 5 % of the nominal inverter current.

NOTE: This fault only occurs on inverters that have 3 current sensors (Frame sizes D to F & FX, GX)
F0022
Powerstack fault
Cause:

That hardware fault (r0947 = 22 and r0949 = 1) caused by the following events:
(1) DC-link overcurrent = short circuit of IGBT
(2) Short circuit of chopper
(3) Earth fault
(4) I/O board is not properly inserted
– Frame sizes A to C (1),(2),(3),(4)
– Frame sizes D to E (1),(2),(4)
– Frame size F (2),(4)

Since all these faults are assigned to one signal on the power stack, it is not possible to establish which one actually occurred.

MM440 Frame size FX & GX:
– UCE failure was detected, when r0947 = 22 and fault value r0949 = 12 or 13 or 14, depending on UCE.
– I2C bus read out error, when r0947 = 22 and fault value r0949 = 21 (The power has to be switched OFF/ON).

Soultion:

1. Check the I/O board. It has to be fully pressed home.
F0023
Output fault
Cause: One motor phase is disconnected.

Solution:

1. Check motor cable.
2. This fault also comes when you run drive without motor.
F0030
Fan has failed
Cause: Fan no longer working.

Soultion:

– Fault cannot be masked while options module (AOP or BOP) is connected
– Need a new fan
F0035
Auto restart
after n
Cause: Auto restart attempts exceed value of P1211.
F0041
Motor Data
Identification
Failure
Cause: Motor data identification failed.
Fault value = 0: Load missing
1: Current limit level reached during identification.
2: Identified stator resistance less than 0.1 % or greater than 100 %.
3: Identified rotor resistance less than 0.1 % or greater than 100 %.
4: Identified stator reactance less than 50 % and greater than 500 %
5: Identified main reactance less than 50 % and greater than 500 %
6: Identified rotor time constant less than 10 ms or greater than 5 s
7: Identified total leakage reactance less than 5 % and greater than 50 %
8: Identified stator leakage reactance less than 25 % and greater than 250 %
9: Identified rotor leakage inductance less than 25 % and greater than 250 %
20: Identified IGBT on-voltage less than 0.5 V or greater than 10 V
30: Current controller at voltage limit
40: Inconsistency of identified data set, at least one identification failed Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom

Soultion:
– Fault value = 0: Check that the motor is connected to the inverter
– Fault value = 1-40: Check if motor data in P0304 to P0311 are correct
– Check what type of motor wiring is required (star, delta).
F0042
Speed Control
Optimisation
Failure
Cause: Possible Causes Speed control optimisation (P1960) failed.

Fault value
= 0: Time out waiting for stable speed
= 1: Inconsistent readings
F0051
Parameter EEPROM
Fault
Cause: Read or write failure while saving non-volatile parameter

Soultion:

– Factory Reset and new parameterization
– There is an hardware or software issue in drive. Need to repair or replace drive.
F0052
Power stack
Fault
Cause: Read failure for power stack information or invalid data.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
F0053
IO EEPROM
Fault
Cause: Read failure for IO EEPROM information or invalid data

Solution:

– Check data
– Change IO board
F0054
Wrong IO Board
Cause:

– Wrong IO board is connected
– No ID detected on IO board, no data

Solution:

– Check data
– Change IO board
F0060
Asic Timeout
Cause: Internal communications failure

Solution:
– If fault persists, change inverter.
– There is an hardware or software issue in drive. Need to repair or replace drive.
F0070
CB setpoint
fault
Cause: No setpoint values from CB (communication board) during telegram off time.

Solution:

1. Check CB and communication partner.
F0071
USS (BOP-link)
setpoint fault
Cause: No setpoint values from USS during telegram off time.

Solution:

1. Check USS master.
F0072
USS (COMM link)
setpoint fault
Cause: No setpoint values from USS during telegram off time

Solution:

1. Check USS master.
F0080
ADC lost
input signal
Cause:

1. Broken wire.
2. Signal out of limits.

Solution:

1. Check drive control wiring.
F0085
External Fault
Cause: External fault triggered via for example terminal inputs.

Solution:

1. Disable for example terminal input for fault trigger.
F0090
Encoder feedback
loss
Cause: Signal from Encoder lost.

Solution:

– Check encoder fitted. If encoder not fitted, set P0400 = 0 and select SLVC mode (P1300 = 20 or 22)
– If encoder fitted, check correct encoder selected (check encoder set-up in P0400).
– Check connections between encoder and inverter
– Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in r0061)
– Increase encoder loss threshold in P0492
F0101
Stack Overflow
Cause: Software error or processor failure.

Solution: Run self test routines.
F0221
PID Feedback
below min.
value
Cause: PID Feedback below min. value P2268.

Solution:

– Change value of P2268
– Adjust feedback gain
F0222
PID Feedback
above max.
value
Cause: PID feedback above max. value P2267.

Solution:

– Change value of P2267
– Adjust feedback gain
F0450
BIST Tests
Failure
Cause:

Fault value =
1: Some power section tests have failed
2: Some control board tests have failed
4: Some functional tests have failed
8: Some IO board tests have failed (MM 420 only)
16: Internal RAM failed on power-up check

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
F0452
Belt Failure
Detected
Cause: Load conditions on motor indicate belt failure or mechanical fault.

Solution:

Check the following:
1. No breakage, seizure or obstruction of drive train.
2. If using an external speed sensor, check for correct function. Check parameters: P2192 (delay time for permitted deviation)
3. If using the torque envelope, check parameters:
P2182 (threshold frequency f1)
P2183 (threshold frequency f2)
P2184 (threshold frequency f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3
P2190 (lower torque threshold 3)
P2192 (delay time for permitted deviation)
A0501
Current Limit
Cause:

– Motor power (P0307) does not correspond to the inverter power (P0206)
– Motor leads are too long
– Earth faults

Solution:

Check the following:
– Motor power (P0307) must correspond to inverter power (r0206)
– Cable length limits must not be exceeded
– Motor cable and motor must have no short-circuits or earth faults
– Motor parameters must match the motor in use
– Value of stator resistance (P0350) must be correct
– Motor must not be obstructed or overloaded
– Increase the ramp-up-time.
– Reduce the boost level (V/f control: P1311 & P1312, Vector control: P1610 & P1611)
A0502
Overvoltage limit
Cause:

– Overvoltage limit is reached
– This warning can occur during ramp down, if the dc-link controller is disabled (P1240 = 0)

Solution:

Check the following:
– Supply voltage (P0210) must lie within limits indicated on rating plate
– DC-link voltage controller must be enabled (P1240) and parameterized properly
– Ramp-down time (P1121) must match inertia of load
– Required braking power must lie within specified limits
A0503
UnderVoltage
Limit
Cause:

– Main supply failed
– Main supply (P0210) and consequently DC-link voltage (r0026) below specified limit (P2172)

Solution:

– Supply voltage (P0210) must lie within limits indicated on rating plate
– Supply must not be susceptible to temporary failures or voltage reductions
A0504
Inverter
OverTemperature
Cause: Warning level of inverter heat-sink temperature (P0614) is exceeded, resulting in pulse frequency reduction and/or output frequency reduction (depending on parameterization in P0610)

Solution:

Check the following:
– Load conditions and duty cycle must be appropriate
– Fan must turn when inverter is running
– Pulse frequency (P1800) must be set to default value
– Ambient temperature could be higher than specified for the inverter
A0505
Inverter I2t
Cause: Warning level (P0294) exceeded, output frequency and/or pulse frequency will be reduced if parameterized (P0290).

Solution:

Check the following:
– Load duty cycle must lie within specified limits
– Motor power (P0307) must match inverter power (r0206)
A0511
Motor
OverTemperature
Cause:

– Motor overloaded
– Load duty cycle too high

Solution:

Independently of the kind of temperature determination check the following:
– Load duty cycle must be correct
– Motor nominal overtemperatures (P0626-P0628) must be correct
– Motor temperature warning level (P0604) must match If P0601 = 0 or 1, check the following:
– Check if name plate data are correct (if not perform quick commissioning)
– Accurate equivalent circuit data can be found by performing motor identification (P1910=1)
– Check if motor weight (P0344) is reasonable. Change if necessary
– Via P0626, P0627, P0628 the standard overtemperatures can be changed, if the motor is not a Siemens standard motor

If P0601 = 2, check the following:
– Check if temperature shown in r0035 is reasonable
– Check if the sensor is a KTY84 (other sensors are not supported)
A0522
I2C read
out timeout
Cause: The cyclic access to the UCE Values and powerstack temperatures via the I2C bus (MM440 Frame size FX & GX) is disturbed.
A0523
Output fault
Cause: One motor phase is disconnected.

Solution:

1. Check motor cable.
2. This fault also comes when you run drive withut motor and rating of motor is small as compare to drive.
A0535
Braking
Resistor Hot
Cause: Braking resistor hot.

Solution:

– Increase duty cycle P1237
– Increase ramp down time P1121
A0541
Motor Data
Identification
Active
Cause: Motor data identification (P1910) selected or running.

Solution: This is a informative warning.
A0542
Speed Control
Optimisation
Active
Cause: Speed Control Optimisation (P1960) is selected or running.
A0590
Encoder feeback
loss warning
Cause: Possible Causes Signal from Encoder lost and Inverter has switched to sensorless vector control.

Solution:

Stop inverter and then
– Check encoder fitted. If encoder not fitted, set P0400 = 0 and select SLVC mode (P1300 = 20 or 22)
– If encoder fitted, check correct encoder selected (check encoder set-up in P0400).
– Check connections between encoder and inverter
– Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in r0061)
– Increase encoder loss threshold in P0492
A0600
RTOS Overrun
Warning
A0700
CB warning 1
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0701
CB warning 2
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0702
CB warning 3
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0703
CB warning 4
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0704
CB warning 5
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0705
CB warning 6
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0706
CB warning 7
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0707
CB warning 8
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0708
CB warning 9
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0709
CB warning 10
Cause: CB (communication board) specific.

Solution: See CB user manual.
A0710
CB communication
error
Cause: Communication with CB (communication board) is lost.

Solution:

1. Check CB hardware.
A0711
CB configuration
error
Cause: CB (communication board) reports a configuration error.

Solution:

1. Check CB parameters.
A0910
Vdc-max
controller
de-activated
Cause: Vdc max controller has been de-activated, since controller is not capable of keeping DC-link voltage (r0026) within limits (P2172).
– Occurs if main supply voltage (P0210) is permanently too high
– Occurs if motor is driven by an active load, causing motor to go into regenerative mode
– Occurs at very high load inertias, when ramping down

Solution:

Check the following:
– Input voltage (P0210) must lie within range
– Load must be match
A0911
Vdc-max
controller
active
Cause: Vdc max controller is active; so ramp-down times will be increased automatically to keep DC-link voltage (r0026) within limits (P2172).
A0912
Vdc-min
controller
active
Cause: Vdc min controller will be activated if DC-link voltage (r0026) falls below minimum level (P2172). The kinetic energy of the motor is used to buffer the DC-link voltage, thus causing deceleration of the drive! So short mains failures do not necessarily lead to an undervoltage trip.
A0920
ADC parameters
not set properly
Cause: ADC parameters should not be set to identical values, since this would produce illogical results.

Fault value =
0: Parameter settings for output identical
1: Parameter settings for input identical
2: Parameter settings for input do not correspond to ADC type
A0921
DAC parameters
not set properly
Cause: DAC parameters should not be set to identical values, since this would produce illogical results.

Fault value =
0: Parameter settings for output identical
1: Parameter settings for input identical
2: Parameter settings for output do not correspond to DAC type
A0922
No load
applied to
inverter
Cause: No Load is applied to the inverter. As a result, some functions may not work as under normal load conditions.

Solution: This alarm also comes when you run drive without motor or rating of motor is small as compare to drive.
A0923
Both JOG Left
and JOG Right
are requested
Cause: Both JOG right and JOG left (P1055/P1056) have been requested. This freezes the RFG output frequency at its current value.
A0936
PID Autotuning
Active
Cause: PID Autotuning (P2350) selected or running.

Solution: This is a informative warning.
A0952
Belt Failure
Warning
Cause: Load conditions on motor indicate belt failure or mechanical fault.

Solution:

Check the following:
1. No breakage, seizure or obstruction of drive train.
2. If using an external speed sensor, check for correct function. Check parameters: P2192 (delay time for permitted deviation)
3. If using the torque envelope, check parameters:
P2182 (threshold frequency f1)
P2183 (threshold frequency f2)
P2184 (threshold frequency f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3)
P2190 (lower torque threshold 3)
P2192 (delay time for permitted deviation)