Danfoss iC2 Drive

📥 Download Catalog 📥 Download Manual

Below image show terminal details:

Search from below list for iC2 drive faults & alarms:

Fault CodeCause & Solution
WARNING 2
W2 Live
Zero Error
Cause: This warning or fault only appears if programmed in P 9.5.6.2 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this condition.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 33 and 34 for signals, terminal 35 common.
– Check that the drive programming and switch settings match the analog signal type.
– Perform an input terminal signal test.
FAULT 2
F2 Live
Zero Error
Cause: This warning or fault only appears if programmed in P 9.5.6.2 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this condition.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 33 and 34 for signals, terminal 35 common.
– Check that the drive programming and switch settings match the analog signal type.
– Perform an input terminal signal test.
Warning/
fault 3
No Motor
Cause: No motor has been connected to the output of the drive.
WARNING 4
Mains Phase
Loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in P 1.3.1 Mains Imbalance Function.

Troubleshooting:

– Check the supply voltage and supply currents to the drive.
FAULT 4
Mains Phase
Loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in P 1.3.1 Mains Imbalance Function.

Troubleshooting:

– Check the supply voltage and supply currents to the drive.
WARNING 7
DC
Overvoltage
Cause: If the DC-link voltage exceeds the limit, the drive trips after a time.

Troubleshooting:

– Extend the ramp time.
– Change the ramp type.
FAULT 7
DC
Overvoltage
Cause: If the DC-link voltage exceeds the limit, the drive trips after a time.

Troubleshooting:

– Extend the ramp time.
– Change the ramp type.
WARNING 8
DC Under
Voltage
Cause: If the DC-link voltage (DC) drops below the undervoltage limit, the drive trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the drive voltage.
– Perform the input voltage test.
– Perform the soft charge circuit test.
FAULT 8
DC Under
Voltage
Cause: If the DC-link voltage (DC) drops below the undervoltage limit, the drive trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the drive voltage.
– Perform the input voltage test.
– Perform the soft charge circuit test.
WARNING 9
Inverter
Overload
Cause: The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 90% and trips at 100%, while giving a FAULT. The drive cannot be reset until the counter is below 0%.
– The fault occurs when the drive has run with more than 100% overload for too long.

Troubleshooting:

– Compare the output current shown on the control panel with the drive rated current.
– Compare the output current shown on the control panel with measured motor current.
– Show the thermal drive load on the control panel and monitor the value. When running above the drive continuous current rating, the counter increases. When running below the drive continuous current rating, the counter decreases.
FAULT 9
Inverter
Overload
Cause: The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 90% and trips at 100%, while giving a FAULT. The drive cannot be reset until the counter is below 0%.
– The fault occurs when the drive has run with more than 100% overload for too long.

Troubleshooting:

– Compare the output current shown on the control panel with the drive rated current.
– Compare the output current shown on the control panel with measured motor current.
– Show the thermal drive load on the control panel and monitor the value. When running above the drive continuous current rating, the counter increases. When running below the drive continuous current rating, the counter decreases.
WARNING 10
Motor
Overload
Temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the drive issues a warning or an alarm when the counter reaches 100% in P 4.6.7 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long.

Troubleshooting:

– Check if the motor is overheating. Check if the motor is mechanically overloaded.
– Check that the motor current set in P 4.2.2.3 Nominal Current is correct.
– Ensure that the motor data in P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed is set correctly.
– Running AMA in P 4.2.1.3 AMA Mode tunes the drive to the motor more accurately and reduces thermal loading.
FAULT 10
Motor
Overload
Temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the drive issues a warning or an alarm when the counter reaches 100% in P 4.6.7 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long.

Troubleshooting:

– Check if the motor is overheating. Check if the motor is mechanically overloaded.
– Check that the motor current set in P 4.2.2.3 Nominal Current is correct.
– Ensure that the motor data in P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed is set correctly.
– Running AMA in P 4.2.1.3 AMA Mode tunes the drive to the motor more accurately and reduces thermal loading.
WARNING 11
Motor
Thermistor
Overtemp
Cause: Check whether the thermistor is disconnected. Select whether the drive issues a warning or an fault in P 4.6.7 Motor Thermal Protection.

Troubleshooting:

– Check for motor overheating.
– Check if the motor is mechanically overloaded.
– When using terminal 33 or 34, check that the thermistor is connected correctly between either terminal 33 or 34 (analog voltage input) and terminal 32 (+10 V supply). Also check that the terminal switch for 33 or 34 is set for voltage. Check that P 4.6.8 Thermistor Resource selects terminal 33 or 34.
– When using terminal 13, 14, or 18 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 32. Select the terminal to use in P 4.6.8 Thermistor Resource.
FAULT 11
Motor
Thermistor
Overtemp
Cause: Check whether the thermistor is disconnected. Select whether the drive issues a warning or an fault in P 4.6.7 Motor Thermal Protection.

Troubleshooting:

– Check for motor overheating.
– Check if the motor is mechanically overloaded.
– When using terminal 33 or 34, check that the thermistor is connected correctly between either terminal 33 or 34 (analog voltage input) and terminal 32 (+10 V supply). Also check that the terminal switch for 33 or 34 is set for voltage. Check that P 4.6.8 Thermistor Resource selects terminal 33 or 34.
– When using terminal 13, 14, or 18 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 32. Select the terminal to use in P 4.6.8 Thermistor Resource.
WARNING 12
Torque Limit
Cause: The torque has exceeded the value in P 5.10.1 Motor Torque Limit or the value in P 5.10.2 Regenerative Torque Limit. P 5.10.6 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an fault.

Troubleshooting:

– If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
– If the generator torque limit is exceeded during ramp-down time, extend the ramp-down time.
– If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
– Check the application for excessive current draw on the motor.
FAULT 12
Torque Limit
Cause: The torque has exceeded the value in P 5.10.1 Motor Torque Limit or the value in P 5.10.2 Regenerative Torque Limit. P 5.10.6 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an fault.

Troubleshooting:

– If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
– If the generator torque limit is exceeded during ramp-down time, extend the ramp-down time.
– If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
– Check the application for excessive current draw on the motor.
WARNING 13
Overcurrent
Cause: The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 5 s, then the drive trips and issues an fault. Shock loading or fast acceleration with high-inertia loads can cause this fault.

Troubleshooting:

– Remove power and check if the motor shaft can be turned.
– Check that the motor size matches the drive.
– Check P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed for correct motor data.
FAULT 13
Overcurrent
Cause: The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 5 s, then the drive trips and issues an fault. Shock loading or fast acceleration with high-inertia loads can cause this fault.

Troubleshooting:

– Remove power and check if the motor shaft can be turned.
– Check that the motor size matches the drive.
– Check P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed for correct motor data.
FAULT 14
Earth (Ground)
Fault
Cause: There is a discharge from the output phases to ground, either in the cable between the drive and the motor or in the motor itself.

Troubleshooting:

– Turn off the drive and remove the ground fault.
– Measure the resistance to ground the motor cables and the motor with a megohmmeter to check for ground faults in the motor.
FAULT 16
Short Circuit
Cause: There is short-circuiting in the motor or motor wiring.

Troubleshooting :

– Remove the power to the drive and repair the short circuit.
WARNING 17
Control Word
Timeout
Cause: There is no communication to the drive. The warning is only active when P 5.2.16 Watchdog Response is NOT set to [0] Off. If P 5.2.16 Watchdog Response is set to [5] Stop and trip, a warning appears, and the drive ramps down to a stop and shows an fault.

Troubleshooting:

– Check the connections on the serial communication cable.
– Increase P 5.2.17 Watchdog Delay.
– Check the operation of the communication equipment.
– Verify that proper EMC installation was performed.
FAULT 17
Control Word
Timeout
Cause: There is no communication to the drive. The warning is only active when P 5.2.16 Watchdog Response is NOT set to [0] Off. If P 5.2.16 Watchdog Response is set to [5] Stop and trip, a warning appears, and the drive ramps down to a stop and shows an fault.

Troubleshooting:

– Check the connections on the serial communication cable.
– Increase P 5.2.17 Watchdog Delay.
– Check the operation of the communication equipment.
– Verify that proper EMC installation was performed.
FAULT 18
Start Falied
Cause: The speed cannot exceed the value set in P 5.6.7 Start Max Speed [Hz] during start within the start time which is set in P 5.6.8 Start Max Time to Trip. The fault may be caused by a blocked motor.

Troubleshooting:

– Check if the motor is blocked.
– Check if the start max speed is set higher than the working speed after ramp up.
– Check if the start max time to trip is set shorter than the normal ramp up time.
FAULT 25
Brake
Resistor
Short Circuit
Cause: The brake resistor is monitored during start-up. If a short circuit occurs, the brake function is disabled and the fault appears. The drive is tripped.

Troubleshooting:

– Remove the power to the drive and check the connection of the brake resistor.
WARNING 26
Brake Resistor
Power Limit
Cause: The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in P 3.3.2 Brake Resistor Value. The warning is active when the dissipated braking power is higher than the value set in P 3.3.3 Brake Resistor Power Limit. The drive trips if the warning persists for 1200 s.

Troubleshooting:

– Decrease brake energy via lower speed or longer ramp time.
FAULT 26
Brake Resistor
Power Limit
Cause: The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in P 3.3.2 Brake Resistor Value. The warning is active when the dissipated braking power is higher than the value set in P 3.3.3 Brake Resistor Power Limit. The drive trips if the warning persists for 1200 s.

Troubleshooting:

– Decrease brake energy via lower speed or longer ramp time.
FAULT 27
Brake
IGBT/Brake
Chopper Short
Circuited
Cause: The brake transistor is monitored during start-up. If a short circuit occurs, the brake function is disabled, and an fault is issued. The drive is tripped.

Troubleshooting:

– Remove the power to the drive and remove the brake resistor.
FAULT 28
Brake Check
Cause: The brake resistor is not connected or not working.

Troubleshooting:

– Check if the brake resistor is connected or it is too large for the drive.
FAULT 30
Motor Phase
U Missing
Cause: Motor phase U between the drive and the motor is missing.

Troubleshooting:

– Turn off the drive and check motor phase U.
FAULT 31
Motor Phase
V Missing
Cause: Motor phase V between the drive and the motor is missing.

Troubleshooting:

– Turn off the drive and check motor phase V.
FAULT 32
Motor Phase
W Missing
Cause: Motor phase W between the drive and the motor is missing.

Troubleshooting:

– Turn off the drive and check motor phase W.
WARNING 36
Mains Failure
Cause: This warning/alarm is only active if the supply voltage to the drive is lost and P 2.3.7 Power Loss Controller Limit is not set to [0] No Function.

Troubleshooting:

– Check the fuses to the drive and mains supply to the unit.
FAULT 36
Mains Failure
Cause: This warning/alarm is only active if the supply voltage to the drive is lost and P 2.3.7 Power Loss Controller Limit is not set to [0] No Function.

Troubleshooting:

– Check the fuses to the drive and mains supply to the unit.
FAULT 38
Internal Fault
Cause: When an internal fault occurs, a code number is shown.

Troubleshooting:

See below Table for the causes and solutions for different internal faults. If the fault persists, contact the Danfoss supplier or service
department for assistance.

140-142: Power board EEPROM data error. Upgrade the software in the drive to the latest version.
176: The firmware in the drive does not match the drive. Upgrade the software in the drive to the latest version.
256: Flash ROM checksum error. Upgrade the software in the drive to the latest version.
2304: Firmware mismatch between the control card and the power card. Upgrade the software in the drive to the latest version.
2560: Communication error between the control card and the power card. Upgrade the software in the drive to the latest version. If the fault occurs again, check the connection between the control card and the power card.
3840: Serial flash version error. Upgrade the software in the drive to the latest version.
4608: Drive power size error. Upgrade the software in the drive to the latest version. If the fault occurs again, contact a Danfoss supplier.
Other: Other internal faults. Power cycle the drive.
WARNING 40
Overload of
Digital
Output
Terminal 15
Troubleshooting:

– Check the load connected to terminal 15 or remove the short-circuit connection.
– Check P 9.4.1.1 Digital I/O Mode and P 9.4.2.1 T 15 Mode.
FAULT 46
Gate Drive
Voltage
Cause: The supply for the gate drive on the power card is out of range. It is generated by the switch mode supply (SMPS) on the power card.

Troubleshooting:

– Check for a defective power card.
WARNING 47
24 V
Supply Low
Cause: The 24 V DC is measured on the control card. This alarm appears when the detected voltage of terminal 12 is lower than 18 V.

Troubleshooting:

– Check for a defective control card.
FAULT 47
24 V
Supply Low
Cause: The 24 V DC is measured on the control card. This alarm appears when the detected voltage of terminal 12 is lower than 18 V.

Troubleshooting:

– Check for a defective control card.
FAULT 50
AMA
Calibration
Failed
Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
FAULT 51
AMA Check
Unom and
Inom
Cause: The settings for motor voltage, motor current, and motor power are wrong.

Troubleshooting:

– Check settings in P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed.
FAULT 52
AMA Low
Inom
Cause: The motor current is too low.

Troubleshooting:

– Check the settings in parameter 1-24 Motor Current.
FAULT 53
AMA Big
Motor
Cause: The motor is too big for the AMA to operate.
FAULT 54
AMA Small
Motor
Cause: The motor is too small for the AMA to operate.
FAULT 55
AMA
Parameter
Range
Cause: The AMA cannot run because the paramenter values of the motor are out of the acceptable range.
FAULT 56
AMA Interrupt
Cause: The AMA is manually interrupted.
FAULT 57
AMA Timeout
Troubleshooting:

– Try to restart the AMA. Repeated restarts can overheat the motor.
FAULT 58
AMA Internal
Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
WARNING 59
Current Limit
Cause: The current is higher than the value in P 2.7.1 Output Current Limit %.

Troubleshooting:

– Ensure that the motor data in P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed is set correctly.
– Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit.
FAULT 59
Current Limit
Cause: The current is higher than the value in P 2.7.1 Output Current Limit %.

Troubleshooting:

– Ensure that the motor data in P 4.2.2.1 Nominal Power to P 4.2.2.5 Nominal Speed is set correctly.
– Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit.
FAULT 60
External
Interlock
Cause: A digital input signal indicates a fault condition external to the drive. An external interlock has commanded the drive to trip.

Troubleshooting:

– Clear the external fault condition.
– To resume normal operation, apply 24 V DC to the terminal programmed for external interlock.
– Reset the drive.
FAULT 63
Mechanical
Brake Low
Cause: The actual motor current has not exceeded the release brake current within the start delay time window.
WARNING 69
Power Card
Temperature
Cause: The cutout temperature of the power card has exceeded the upper limit.

Troubleshooting:

– Check that the ambient operating temperature is within limits.
– Check the fan operation.
– Check the power card.
FAULT 69
Power Card
Temperature
Cause: The cutout temperature of the power card has exceeded the upper limit.

Troubleshooting:

– Check that the ambient operating temperature is within limits.
– Check the fan operation.
– Check the power card.
FAULT 80
Drive
Initialized
to Default
Value
Cause: Parameter settings are initialized to default settings after a manual reset.

Troubleshooting:

– To clear the fault, reset the unit.
WARNING 87
Auto
DC-Braking
Cause: Occurs in IT mains when the drive coasts, and the DC voltage is higher than 830 V for 400 V units and 425 V for 200 V units. The motor consumes energy on the DC link. This function can be enabled/disabled in P 2.3.13 Auto DC Braking.
WARNING 95
Lost Load
Detected
Cause: Torque is below the torque level set for no load, indicating a lost load detection. P 5.2.9 Lost Load Function is set for alarm.

Troubleshooting:

– Troubleshoot the system.
– Reset the drive after the fault is cleared.
FAULT 95
Lost Load
Detected
Cause: Torque is below the torque level set for no load, indicating a lost load detection. P 5.2.9 Lost Load Function is set for alarm.

Troubleshooting:

– Troubleshoot the system.
– Reset the drive after the fault is cleared.
FAULT 99
Locked
Rotor
Cause: The rotor is blocked. It is only enabled for PM motor control.

Troubleshooting:

– Check if the motor shaft is locked.
– Check if the start current triggers the current limit set in P 2.1.5 Output Current Limit %.
– Check if it increases the value in P 4.6.15 Sync. Locked Rotor Detection Time [s].
FAULT 126
Motor
Rotating
Cause: During AMA start-up, the motor is rotating. It is only valid for PM motor.

Troubleshooting:

– Check if the motor is rotating before starting the AMA.
WARNING 127
Back EMF
Too High
Cause: This warning applies to PM motors only. When the back EMF exceeds 90% x Uinvmax (overvoltage threshold) and does not drop to normal level within 5 s, this warning is reported. The warning remains until the back EMF returns to a normal level.
Warning
fault 61
Feedback Error
Err. 89
Parameter
read only
Meaning: Parameters cannot be changed.
Err. 95
Not while
running
Meaning: Parameters can only be changed when the motor is stopped.
Err. 96
A wrong
password
was entered
Meaning: Occurs when using a wrong password for changing a password-protected parameter.