Danfoss FC360 Drive

📥  Download Catalog 📥 Download Manual

Below image show terminal details:

Search from below list for FC360 drive faults & alarms:

Fault CodeCause & Solution
WARNING 2
Live zero
error
Cause: This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or faulty device sending the signal can cause this condition.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 common.
– Check that the frequency converter programming and switch settings match the analog signal type.
– Perform the input terminal signal test.
ALARM 2
Live zero
error
Cause: This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or faulty device sending the signal can cause this condition.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 common.
– Check that the frequency converter programming and switch settings match the analog signal type.
– Perform the input terminal signal test.
Warning 3
No motor
Cause: No motor has been connected to the output of the frequency converter.
WARNING 4
Mains phase
loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in parameter 14-12 Response to Mains Imbalance.

Troubleshooting:

– Check the supply voltage and supply currents to the frequency converter.
ALARM 4
Mains phase
loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in parameter 14-12 Response to Mains Imbalance.

Troubleshooting:

– Check the supply voltage and supply currents to the frequency converter.
WARNING 7
DC
overvoltage
Cause: If the DC-link voltage exceeds the limit, the frequency converter trips after a time.

Troubleshooting:

– Extend the ramp time.
– Change the ramp type.
ALARM 7
DC
overvoltage
Cause: If the DC-link voltage exceeds the limit, the frequency converter trips after a time.

Troubleshooting:

– Extend the ramp time.
– Change the ramp type.
WARNING 8
DC under
voltage
Cause: If the DC-link voltage (DC-link) drops below the undervoltage limit, the frequency converter trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the frequency converter voltage.
– Perform the input voltage test.
– Perform the soft charge circuit test.
ALARM 8
DC under
voltage
Cause: If the DC-link voltage (DC-link) drops below the undervoltage limit, the frequency converter trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the frequency converter voltage.
– Perform the input voltage test.
– Perform the soft charge circuit test.
WARNING 9
Inverter
overload
Cause: The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at90% and trips at 100%, while giving an alarm. The frequency converter cannot be reset until the counter is below 0%.
– The fault occurs when the frequency converter has run with more than 100% overload for too long.

Troubleshooting:

– Compare the output current shown on the LCP with the frequency converter rated current.
– Compare the output current shown on the LCP with measured motor current.
– Show the thermal frequency converter load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
ALARM 9
Inverter
overload
Cause: The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at90% and trips at 100%, while giving an alarm. The frequency converter cannot be reset until the counter is below 0%.
– The fault occurs when the frequency converter has run with more than 100% overload for too long.

Troubleshooting:

– Compare the output current shown on the LCP with the frequency converter rated current.
– Compare the output current shown on the LCP with measured motor current.
– Show the thermal frequency converter load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
WARNING 10
Motor
overload
temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter issues a warning or an alarm when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long.

Troubleshooting:

• Check for motor overheating.
• Check if the motor is mechanically overloaded.
• Check that the motor current set in parameter 1-24 Motor Current is correct.
• Ensure that motor data in parameters 1-20 to 1-25 is set correctly.
• Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.
ALARM 10
Motor
overload
temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter issues a warning or an alarm when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault occurs when the motor runs with more than 100% overload for too long.

Troubleshooting:

• Check for motor overheating.
• Check if the motor is mechanically overloaded.
• Check that the motor current set in parameter 1-24 Motor Current is correct.
• Ensure that motor data in parameters 1-20 to 1-25 is set correctly.
• Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.
WARNING 11
Motor
thermistor
over temp
Cause: Check whether the thermistor is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.

Troubleshooting:

– Check for motor overheating.
– Check if the motor is mechanically overloaded.
– When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 or 54 is set for voltage.
– Check that parameter 1-93 Thermistor Resource selects terminal 53 or 54.
– When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Selectthe terminal to use in parameter 1-93 Thermistor Resource.
ALARM 11
Motor
thermistor
over temp
Cause: Check whether the thermistor is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.

Troubleshooting:

– Check for motor overheating.
– Check if the motor is mechanically overloaded.
– When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 or 54 is set for voltage.
– Check that parameter 1-93 Thermistor Resource selects terminal 53 or 54.
– When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Selectthe terminal to use in parameter 1-93 Thermistor Resource.
WARNING 12
Torque limit
Cause: The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an alarm.

Troubleshooting:

– If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
– If the generator torque limit is exceeded during ramp-down, extend the ramp-down time.
– If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
– Check the application for excessive current draw on the motor.
ALARM 12
Torque limit
Cause: The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an alarm.

Troubleshooting:

– If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
– If the generator torque limit is exceeded during ramp-down, extend the ramp-down time.
– If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
– Check the application for excessive current draw on the motor.
WARNING 13
Over current
Cause: The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 5 s, then the frequency converter trips and issues an alarm. Shock loading or fast acceleration with high-inertia loads can cause this fault.

Troubleshooting:

– Remove power and check if the motor shaft can be turned.
– Check that the motor size matches the frequency converter.
– Check parameters 1-20 to 1-25 for correct motor data.
ALARM 13
Over current
Cause: The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 5 s, then the frequency converter trips and issues an alarm. Shock loading or fast acceleration with high-inertia loads can cause this fault.

Troubleshooting:

– Remove power and check if the motor shaft can be turned.
– Check that the motor size matches the frequency converter.
– Check parameters 1-20 to 1-25 for correct motor data.
ALARM 14
Earth
(ground)
fault
Cause: There is current from the output phases to ground, either in the cable between the frequency converter and the motor, or in the motor itself.

Troubleshooting:

– Remove power to the frequency converter and repair the ground fault.
– Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter.
ALARM 16
Short circuit
Cause: There is short-circuiting in the motor or motor wiring.

– Remove power to the frequency converter and repair the short circuit.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
WARNING 17
Control word
timeout
Cause: There is no communication to the frequency converter. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] Off.
– If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The frequency converter then ramps down until it trips, while giving an alarm. Parameter 8-03 Control Timeout Time could possibly be increased.

Troubleshooting:

– Check connections on the serial communication cable.
– Increase parameter 8-03 Control Word Timeout Time.
– Check the operation of the communication equipment.
– Verify a proper installation based on EMC requirements.
ALARM 17
Control word
timeout
Cause: There is no communication to the frequency converter. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] Off.
– If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The frequency converter then ramps down until it trips, while giving an alarm. Parameter 8-03 Control Timeout Time could possibly be increased.

Troubleshooting:

– Check connections on the serial communication cable.
– Increase parameter 8-03 Control Word Timeout Time.
– Check the operation of the communication equipment.
– Verify a proper installation based on EMC requirements.
ALARM 18
Start failed
Cause: The speed cannot exceed the value set in parameter 1-78 Compressor Start Max Speed [Hz] during start within the allowed time, which is set in parameter 1-79 Compressor Start Max Time to Trip. The alarm may be caused by a blocked motor.
WARNING 25
Brake resistor
short circuit
Cause: The brake resistor is monitored during start-up. If a short circuit occurs, the brake function is disabled and the alarm appears. The frequency converter is tripped.

Troubleshooting:

– Remove the power to the frequency converter and check the connection of the brake resistor.
WARNING 26
Brake resistor
power limit
Cause: The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-11 Brake Resistor (ohm). The warning is active when the dissipated braking power is higher than the value set in parameter 2-12 Brake Power Limit (kW). The frequency converter trips if the warning persists for 1200 s.

Troubleshooting:

– Decrease brake energy via lower speed or longer ramp time.
ALARM 26
Brake resistor
power limit
Cause: The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-11 Brake Resistor (ohm). The warning is active when the dissipated braking power is higher than the value set in parameter 2-12 Brake Power Limit (kW). The frequency converter trips if the warning persists for 1200 s.

Troubleshooting:

– Decrease brake energy via lower speed or longer ramp time.
WARNING 27
Brake chopper
fault
Cause: The brake transistor is monitored during start-up. If a short circuit occurs, the brake function is disabled, and an alarm is issued. The frequency converter is tripped.

Troubleshooting:

– Remove the power to the frequency converter and remove the brake resistor.
ALARM 27
Brake chopper
fault
Cause: The brake transistor is monitored during start-up. If a short circuit occurs, the brake function is disabled, and an alarm is issued. The frequency converter is tripped.

Troubleshooting:

– Remove the power to the frequency converter and remove the brake resistor.
WARNING 28
Brake check
failed
Cause: The brake resistor is not connected or not working.

Troubleshooting:

– Check if brake resistor is connected or it is too large for the frequency converter.
ALARM 28
Brake check
failed
Cause: The brake resistor is not connected or not working.

Troubleshooting:

– Check if brake resistor is connected or it is too large for the frequency converter.
ALARM 30
Motor
phase U
missing
Cause: Motor phase U between the frequency converter and the motor is missing.

Troubleshooting:

– Remove power from the frequency converter and check motor phase U.
ALARM 31
Motor
phase V
missing
Cause: Motor phase V between the frequency converter and the motor is missing.

Troubleshooting:

– Remove power from the frequency converter and check motor phase V.
ALARM 32
Motor
phase W
missing
Cause: Motor phase W between the frequency converter and the motor is missing.

Troubleshooting:

– Remove power from the frequency converter and check motor phase W.
WARNING 34
communication
fault
Cause: The fieldbus on the communication option card is not working.
ALARM 34
communication
fault
Cause: The fieldbus on the communication option card is not working.
ALARM 38
Internal
fault
Cause: When an internal fault occurs, a code number is shown.

Troubleshooting: See Table for the causes and solutions for different internal faults.


140–142: Power board EEPROM data error. Upgrade the software in the frequency converter to the latest version.
176: The firmware in the frequency converter does not match the frequency converter. Upgrade the software in the frequency converter to the latest version.
256: Flash ROM checksum error. Upgrade the software in the frequency converter to the latest version.
2304: Firmware mismatch between the control card and the power card. Upgrade the software in the frequency converter to the latest version.
2560: Communication error between the control card and the power card. Upgrade the software in the frequency converter to the latest version. If the alarm occurs again, check the connection between the control card and the power card.
3840: Serial flash version error. Upgrade the software in the frequency converter to the latest version.
4608: Frequency converter power size error. Upgrade the software in the frequency converter to the latest version. If the alarm occurs again, contact a Danfoss supplier.
5632: Option hardware version error. The hardware version of the option or the fieldbus variant is not compatible with the frequency converter software.
5888: Option software version error. The software version of the option or the fieldbus variant is not compatible with the frequency converter software. Change either the fieldbus software or the frequency converter software.
6144: The option is not supported. Check if the product supports this option.
6400: Option combination error. Remove the option.
Other: Other internal faults. Power cycle the frequency converter.
WARNING 40
Overload of
digital output
terminal 27
Cause: Check the load connected to terminal 27 or remove the short-circuit connection. Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41
Overload of
digital output
terminal 29
Cause: Check the load connected to terminal 29 or remove the short circuit connection. Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode.
ALARM 46
Power card
supply
Cause: The supply for the gate drive on the power card is out of range. It is generated by the switch mode supply (SMPS) on the power card.

Troubleshooting:

– Check for a defective power card.
WARNING 47
24 V supply
low
Cause: The 24 V DC is measured on the control card.
ALARM 50
AMA
calibration
failed
Cause: A calibration error has occurred.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
ALARM 51
AMA check
Unom and Inom
Cause: The settings for motor voltage, motor current, and motor power are wrong.

Troubleshooting:

– Check the settings in parameters 1-20 to 1-25.
ALARM 52
AMA low
Inom
Cause: The motor current is too low.

Troubleshooting:

– Check the setting in parameter 1-24 Motor Current.
ALARM 53
AMA motor
too big
Cause: The motor is too large for the AMA to operate.
ALARM 54
AMA motor
too small
Cause: The motor is too small for the AMA to operate.
ALARM 55
AMA parameter
out of range
Cause: The parameter values of the motor are outside of the acceptable range. The AMA does not run.
ALARM 56
AMA
interrupted
by user
Cause: The AMA is manually interrupted.
ALARM 57
AMA internal
fault
Cause: Try to restart the AMA again. Repeated restarts can overheat the motor.
ALARM 58
Internal
fault
Cause: Internal fault.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
WARNING 59
Current limit
Cause: The current is higher than the value in parameter 4-18 Current Limit.

Troubleshooting:

– Ensure that motor data in parameters 1-20 to 1-25 is set correctly.
– Possibly increase the current limit.
– Be sure that the system can operate safely at a higher limit.
ALARM 60
External
interlock
Cause: A digital input signal indicates a fault condition external to the frequency converter. An external interlock has commanded the frequency converter to trip.

Troubleshooting:

– Clear the external fault condition.
– To resume normal operation, apply 24 V DC to the terminal programmed for external interlock.
– Reset the frequency converter.
WARNING 61
Feedback
error
Cause: An error between calculated speed and speed measurement from feedback device.

Troubleshooting:

– Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function.
– Set the tolerable error in parameter 4-31 Motor Feedback Speed Error.
– Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout.
ALARM 61
Feedback
error
Cause: An error between calculated speed and speed measurement from feedback device.

Troubleshooting:

– Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function.
– Set the tolerable error in parameter 4-31 Motor Feedback Speed Error.
– Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout.
ALARM 63
Mechanical
brake low
Cause: The actual motor current has not exceeded the release brake current within the start delay time window.
WARNING 65
Control card
over
temperature
Cause: The cutout temperature of the control card has exceeded the upper limit.

Troubleshooting:

– Check that the ambient operating temperature is within the limits.
– Check the fan operation.
– Check the control card.
ALARM 65
Control card
over
temperature
Cause: The cutout temperature of the control card has exceeded the upper limit.

Troubleshooting:

– Check that the ambient operating temperature is within the limits.
– Check the fan operation.
– Check the control card.
ALARM 67
Option module
configuration
has changed
Cause: One or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit.
ALARM 68
Safe stop
activated
Cause: Safe Torque Off (STO) is activated. If STO is in manual restart mode (default), to resume normal operation, apply 24 V DC to terminals 37 and 38 and initiate a reset signal (via fieldbus, digital I/O, or [Reset]/[Off Reset] key). If STO is in automatic restart mode, applying 24 V DC to terminals 37 and 38 automatically resumes the frequency converter to normal operation.
ALARM 69
Power card
temperature
Cause: The cutout temperature of the power card has exceeded the upper limit.

Troubleshooting:

– Check that the ambient operating temperature is within limits.
– Check fan operation.
– Check the power card.
ALARM 80
Drive
initialised
to default
value
Cause: Parameter settings are initialized to default settings after a manual reset.

Troubleshooting:

– To clear the alarm, reset the unit.
WARNING 87
Auto
DC-Braking
Cause: Occurs in IT mains when the frequency converter coasts, and the DC voltage is higher than 830 V for 400 V units and 425 V for 200 V units. The motor consumes energy on the DC link. This function can be enabled/disabled in parameter 0-07 Auto DC Braking.
ALARM 88
Option
detection
Cause: A new option configuration has been detected. Set parameter 14-89 Option Detection to [1] Enable Option Change, and power cycle the frequency converter to accept the new configuration.
ALARM 95
Broken belt
Cause: Torque is below the torque level set for no load, indicating a broken belt. Parameter 22-60 Broken Belt Function is set for alarm.

Troubleshooting:

– Troubleshoot the system and reset the frequency converter after clearing the fault.
ALARM 99
Locked Rotor
Cause: The rotor is blocked. It is only enabled for PM motor control.

Troubleshooting:

– Check if the motor shaft is locked.
– Check if the start current triggers the current limit set in parameter 4-18 Current Limit.
– Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s].
ALARM 126
Motor
Rotating
Cause: During AMA start-up, the motor is rotating. It is only valid for PM motor.

Troubleshooting:

– Check if the motor is rotating before starting the AMA.
WARNING 127
Back EMF
too High
Cause: This warning applies to PM motors only. When the back EMF exceeds 90% x Uinvmax (overvoltage threshold) and does not drop to a normal level within 5 s, this warning is reported. The warning remains until the back EMF returns to a normal level.
Alarm 35
Option fault
Cause: Fieldbus or option B detects internal errors.
Warning 36
Mains
failure
Cause: This warning/alarm is only active if the supply voltage to the frequency converter is lost and parameter 14-10 Mains Failure is NOT set to [0] No Function.
Alarm 36
Mains
failure
Cause: This warning/alarm is only active if the supply voltage to the frequency converter is lost and parameter 14-10 Mains Failure is NOT set to [0] No Function.
warning 90
Feedback
monitor
Cause: A feedback fault is detected by option B.
alarm 90
Feedback
monitor
Cause: A feedback fault is detected by option B.
alarm 101
Flow/pressure
information
missing
Cause: Flow/pressure information missing.
alarm 120
Position
control
fault
Cause: Position control fault.
alarm 250
New spare
part
Cause: New spare part. This alarm comes when you change hardware.
alarm 251
New type
code
Cause: New type code.
alarm 252
Tension limit
Cause: Tension limit
nw-run
Not while
running
Cause: Parameter can only be changed when the motor is stopped.
Err.
A wrong
password
was
entered
Cause: Occurs when using a wrong password for changing a password-protected parameter
Err 84Cause: Communication between the LCP and the frequency converter is lost.
Err 85Cause: The LCP key is disabled. One of the LCP keys is disabled in parameter group 0-4* LCP Keypad.
Err 86Cause: Data copy failure: Occurs when data is copied from frequency converter to LCP, or from LCP to frequency converter (parameter 0-50 LCP Copy).
Err 87Cause: Invalid LCP data: Occurs when data is being copied from LCP to frequency converter (parameter 0-50 LCP Copy).
Err 88 Cause: LCP data incompatible: Occurs when data is being copied from LCP to frequency converter (parameter 0-50 LCP Copy), typically because data is moved between frequency converters that have major software differences.
Err 89 Cause: An operation is issued via LCP to write a value to a parameter that is read-only.
Err 90 Cause: LCP, serial communication, or fieldbus communication attempts to update the same parameters at the same time.
Err 91 Cause: The parameter value that is input via the LCP is invalid.
Err 92 Cause: The parameter value that is input via the LCP exceeds limits.
Err 93 Cause: The LCP copy operation cannot be conducted when the frequency converter is running.
donE Cause: A notification that the LCP Copy process is finished.
NWrun Cause: The parameter cannot be changed while the frequency converter is running.
Err. Cause: The password that is input via the LCP is incorrect.