Danfoss HVAC Basic Drive FC 101

📥 Download Catalog 📥Download Manual

Below image show terminal details:

Search from below list for FC101 drive faults & alarms:

Fault CodeCause & Solution
WARNING 2
Live zero
error
Cause: This warning or alarm only appears if parameter 6-01 Live Zero Timeout Function is configured. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. This condition can be caused by broken wiring or a faulty device sending the signal.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 common.
– Check that the frequency converter programming matches the analog signal type.
ALARM 2
Live zero
error
Cause: This warning or alarm only appears if parameter 6-01 Live Zero Timeout Function is configured. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. This condition can be caused by broken wiring or a faulty device sending the signal.

Troubleshooting:

– Check connections on all the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 common.
– Check that the frequency converter programming matches the analog signal type.
WARNING 3
No motor
Cause: No motor is connected to the output of the frequency converter.

Solution:

– Check the cable connection between the frequency converter and the motor.
ALARM 3
No motor
Cause: No motor is connected to the output of the frequency converter.

Solution:

– Check the cable connection between the frequency converter and the motor.
WARNING 4
Mains phase
loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier on the frequency converter. Options are programmed at parameter 14-12 Function at Mains Imbalance.

Troubleshooting:

– Check the supply voltage and supply currents to the frequency converter.
ALARM 4
Mains phase
loss
Cause: A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier on the frequency converter. Options are programmed at parameter 14-12 Function at Mains Imbalance.

Troubleshooting:

– Check the supply voltage and supply currents to the frequency converter.
WARNING 7
DC
overvoltage
Cause: If the DC-link voltage exceeds the limit, the frequency converter trips after a time.

Troubleshooting:

– Extend the ramp time.
– Activate functions in parameter 2-10 Brake Function.
– Activate overvoltage control in parameter 2-17 Over-voltage Control.
ALARM 7
DC
overvoltage
Cause: If the DC-link voltage exceeds the limit, the frequency converter trips after a time.

Troubleshooting:

– Extend the ramp time.
– Activate functions in parameter 2-10 Brake Function.
– Activate overvoltage control in parameter 2-17 Over-voltage Control.
WARNING 8
DC under
voltage
Cause: If the DC-link voltage (DC) drops below the under voltage limit, the frequency converter trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the frequency converter voltage.
– Perform an input voltage test.
ALARM 8
DC under
voltage
Cause: If the DC-link voltage (DC) drops below the under voltage limit, the frequency converter trips after a fixed time delay. The time delay varies with unit size.

Troubleshooting:

– Check that the supply voltage matches the frequency converter voltage.
– Perform an input voltage test.
WARNING 9
Inverter
overload
Cause: The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 90% and trips at 100%, while issuing an alarm. The frequency converter cannot be reset until the counter is below 90%.
– The fault is that the frequency converter is overloaded by more than 100% for too long.

Troubleshooting:

– Compare the output current shown on the LCP with the frequency converter rated current.
– Compare the output current shown on the LCP with measured motor current.
– Display the thermal drive load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
ALARM 9
Inverter
overload
Cause: The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 90% and trips at 100%, while issuing an alarm. The frequency converter cannot be reset until the counter is below 90%.
– The fault is that the frequency converter is overloaded by more than 100% for too long.

Troubleshooting:

– Compare the output current shown on the LCP with the frequency converter rated current.
– Compare the output current shown on the LCP with measured motor current.
– Display the thermal drive load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
WARNING 10
Motor overload
temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter issues a warning or an alarm when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault is that the motor is overloaded by more than 100% for too long.

Troubleshooting:

– Check if the motor is overheating.
– Check if the motor is mechanically overloaded
– Ensure that the motor parameter 1-24 Motor Current is set correctly.
– Ensure motor data in parameters 1-20 through 1-25 are set correctly.
– Run AMA in parameter 1-29 Automatic Motor Adaption (AMA).
ALARM 10
Motor overload
temperature
Cause: According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter issues a warning or an alarm when the counter reaches 100% in parameter 1-90 Motor Thermal Protection. The fault is that the motor is overloaded by more than 100% for too long.

Troubleshooting:

– Check if the motor is overheating.
– Check if the motor is mechanically overloaded
– Ensure that the motor parameter 1-24 Motor Current is set correctly.
– Ensure motor data in parameters 1-20 through 1-25 are set correctly.
– Run AMA in parameter 1-29 Automatic Motor Adaption (AMA).
WARNING 11
Motor
thermistor
over temp
Cause: The thermistor or the thermistor connection is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.

Troubleshooting:

– Check if the motor is overheating.
– Check if the motor is mechanically overloaded.
– Ensure that the thermistor is connected correctly.
– If using a thermal switch or thermistor, ensure that the programming of parameter 1-93 Thermistor Source matches sensor wiring.
ALARM 11
Motor
thermistor
over temp
Cause: The thermistor or the thermistor connection is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.

Troubleshooting:

– Check if the motor is overheating.
– Check if the motor is mechanically overloaded.
– Ensure that the thermistor is connected correctly.
– If using a thermal switch or thermistor, ensure that the programming of parameter 1-93 Thermistor Source matches sensor wiring.
WARNING 13
Over current
Cause: The inverter peak current limit is exceeded. The warning lasts about 1.5 s, then the frequency converter trips and issues an alarm.

Troubleshooting:

– This fault may be caused by shock loading or fast acceleration with high inertia loads.
– Turn off the frequency converter. Check if the motor shaft can be turned.
– Check that the motor size matches the frequency converter.
– Incorrect motor data in parameters 1-20 through 1-25.
ALARM 13
Over current
Cause: The inverter peak current limit is exceeded. The warning lasts about 1.5 s, then the frequency converter trips and issues an alarm.

Troubleshooting:

– This fault may be caused by shock loading or fast acceleration with high inertia loads.
– Turn off the frequency converter. Check if the motor shaft can be turned.
– Check that the motor size matches the frequency converter.
– Incorrect motor data in parameters 1-20 through 1-25.
ALARM 14
Earth
(ground)
fault
Cause: There is current from the output phases to earth, either in the cable between the frequency converter and the motor or in the motor itself.

Troubleshooting:

– Remove power to the frequency converter and repair the earth fault.
– Check for earth faults in the motor by measuring the resistance to ground of the motor leads and the motor with a megohmmeter.
ALARM 16
Short circuit
Cause: There is short-circuiting in the motor or motor wiring.

Solution: Remove power to the frequency converter and repair the short circuit.
WARNING 17
Control word
timeout
Cause: There is no communication to the frequency converter. The warning is only active when 8-04 Control Word Timeout Function is NOT set to OFF.
– If 8-04 Control Word Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it trips, while giving an alarm. 8-03 Control Timeout Time could possibly be increased

Troubleshooting:

– Check connections on the serial communication cable.
– Increase 8-03 Control Word Timeout Time
– Check the operation of the communication equipment.
– Verify a proper installation based on EMC requirements.
ALARM 17
Control word
timeout
Cause: There is no communication to the frequency converter. The warning is only active when 8-04 Control Word Timeout Function is NOT set to OFF.
– If 8-04 Control Word Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it trips, while giving an alarm. 8-03 Control Timeout Time could possibly be increased

Troubleshooting:

– Check connections on the serial communication cable.
– Increase 8-03 Control Word Timeout Time
– Check the operation of the communication equipment.
– Verify a proper installation based on EMC requirements.
WARNING 24
Fan fault
Cause: The fan warning function is an extra protection function that checks whether the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled).

Troubleshooting:

– Check fan resistance.
ALARM 24
Fan fault
Cause: The fan warning function is an extra protection function that checks whether the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled).

Troubleshooting:

– Check fan resistance.
ALARM 30
Motor
phase U
missing
Cause: Motor phase U between the frequency converter and the motor is missing.

Solution: Remove power from the frequency converter and check motor phase U.
ALARM 31
Motor
phase V
missing
Cause: Motor phase V between the frequency converter and the motor is missing.

Solution: Remove power from the frequency converter and check motor phase V.
ALARM 32
Motor
phase W
missing
Cause: Motor phase W between the frequency converter and the motor is missing.

Solution: Remove power from the frequency converter and check motor phase W.
ALARM 38
Internal
fault
Cause: Internal fault.

Troubleshooting:

– Cycle power
– Check that the option is properly installed
– Check for loose or missing wiring
– There is an hardware or software issue in drive. Need to repair or replace drive.
ALARM 44
Earth
fault II
Cause: There is a discharge from the output phases to ground, either in the cable between the frequency converter and the motor or in the motor itself.

Troubleshooting:

– Turn off the frequency converter and remove the ground fault.
– Measure the resistance to ground of the motor cables and the motor with a megohmmeter to check for a ground fault in the motor.
ALARM 46
Gate drive
voltage low
Cause: The supply on the power card is out of range. There are 3 supplies generated by the switch mode power supply (SMPS) on the power card: 24 V, 5 V, and ±18 V.

Troubleshooting:

– Check the power card.
ALARM 47
24 V supply
low
Cause: The 24 V DC is measured on the control card.It occurs when the detected voltage on terminal 12 is lower than 18 V. Check the control card and the load connected.
ALARM 51
AMA check
Unom and
Inom
Cause: The setting of motor voltage, motor current, and motor power is presumably wrong.

Solution: Check the settings.
ALARM 52
AMA low Inom
Cause: The motor current is too low.

– Check the settings.
ALARM 53
AMA motor
too big

Cause: The motor is too large for the AMA to be performed.
ALARM 54
AMA motor
too small
Cause: The motor is too small for the AMA to be performed.
ALARM 55
AMA Parameter
out of range
Cause: The parameter values found from the motor are outside the acceptable range.
ALARM 56
AMA
interrupted
by user
Cause: The AMA is interrupted.
ALARM 57
AMA timeout
Cause: Try to start the AMA again a number of times, until the AMA is performed. Note that repeated runs may heat the motor to a level where the resistance Rs and Rr are increased. In most cases, this is not critical.
ALARM 58
AMA internal
fault
Cause: AMA internal fault.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
WARNING 59
Current limit
Cause: The current is higher than the value in parameter 4-18 Current Limit.
ALARM 60
External
interlock
Cause: External interlock has been activated. To resume normal operation, apply 24 V DC to the terminal programmed for external Interlock and reset the frequency converter (via serial communication, digital I/O, or by pressing [Reset]).
ALARM 69
Power card
temperature
Cause: The temperature on the power card is either too high or too low.

Troubleshooting:

– Ensure that the ambient operating temperature is within the limits.
– Check if the filters are clogged.
– Check the fan operation.
– Check the power card.
ALARM 70
Illegal
power section
configuration
Cause: The control card and power card are incompatible. Contact your supplier with the type code of the unit from the nameplate and the part numbers of the cards to check compatibility.
ALARM 80
Drive
initialised
to default
value
Cause: Parameter settings are initialised to default settings after a manual reset.
ALARM 95
Broken belt
Cause: Torque is below the torque level set for no load, indicating a broken belt. Parameter 22-60 Broken Belt Function is set for alarm.

Troubleshooting:

– Troubleshoot the system and reset the frequency converter after clearing the fault.
ALARM 126
Motor
Rotating
Cause: During AMA start-up, the motor is rotating. It is only valid for PM motor.

Troubleshooting:

– Check if the motor is rotating before starting the AMA.
WARNING 127
Back EMF
too High
Cause: This warning applies to PM motors only. When the back EMF exceeds 90% x Uinvmax (overvoltage threshold) and does not drop to a normal level within 5 s, this warning is reported. The warning remains until the back EMF returns to a normal level.
WARNING 200
Fire Mode
Cause: Fire mode has been activated.
WARNING 202
Fire Mode
Limits
Exceeded
Cause: Fire Mode has suppressed one or more warranty-voiding alarms.
ALARM 250
New Spare
Part
Cause: The power or switch mode supply has been exchanged.
ALARM 251
New Type
Code
Cause: The frequency converter has a new type code.
Err 84
LCP comm.
Cause: Lost Communication between the LCP and the frequency converter is lost.
Err 85
Button disabled
Cause: The LCP key is disabled. One of the LCP keys has been disabled in parameter group 0-4* LCP Keypad.
Err 86
LCP copy
failed
Cause: Data copy failure. This error occurs when data is copied from frequency converter to LCP, or from LCP to frequency converter (parameter 0-50 LCP Copy).
Err 88
Data not
compatible
Cause: LCP data incompatible. This error occurs when data is being copied from LCP to frequency converter (parameter 0-50 LCP Copy). The typical reason is that data is moved between frequency converter and LCP that have major software differences.
Err 89
Read only
Cause: Parameter read only. An operation is issued via LCP to write a value to a parameter that is read-only.
Err 90
Database
busy
Cause: The parameter database of the frequency converter is busy.
Err 91
Parameter
invalid
Cause: The parameter value that is input via the LCP is invalid.
Err 92
Exceeds
limits
Cause: The parameter value that is input via the LCP exceeds limits.
Err 93
Motor is
running
Cause: The LCP copy operation cannot be performed when the frequency converter is running.
Err 95
Not while
running
Cause: The parameter cannot be changed while the frequency converter is running.
Err 96
Password
rejected
Cause: The password that is input via the LCP is incorrect.
Alarm 50
AMA
calibration
failed
Cause: AMA calibration failed
Warning 66
Heat sink
temperature
low
Cause: Heat sink temperature low.
Warning 79
Illegal
PS config
Cause: Illegal PS config.
alarm 79
Illegal
PS config
Cause: Illegal PS config.
ALARM 84Cause: LCP error
warning 87
Auto DC brake
Cause: Auto DC brake.
WARNING 200
Fire Mode
Cause: Fire mode has been activated.