A2B1
Overcurrent |
Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this warning may also be caused by an earth fault or supply phase loss.
Remedy:
- Check motor load.
- Check acceleration times in parameter group 23 Speed reference ramp (speed control) or 28 Frequency reference chain (frequency control).
- Check parameters 46.01 Speed scaling, 46.02 Frequency scaling and 46.03 Torque scaling.
- Check motor and motor cable (including phasing and delta/star connection).
- Check for an earth fault in motor or motor cables by measuring the insulation resistances.
- Check there are no contactors opening and closing in motor cable.
- Check that the start-up data in parameter group 99 Motor data corresponds to the motor rating plate.
- Check that there are no power factor correction capacitors or surge absorbers in motor cable.
|
A2B3
Earth leakage |
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.
Remedy:
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable.
- If an earth fault is found, fix or change the motor cable and/or motor.
- If no earth fault can be detected, contact your local ABB representative.
|
A2B4
Short circuit |
Cause: Short-circuit in motor cable(s) or motor.
Remedy:
- Check motor and motor cable for cabling errors.
- Check motor and motor cable (including phasing and delta/star connection).
- Check for an earth fault in motor or motor cables by measuring the insulation resistances.
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
|
A2BA
IGBT overload |
Cause: Excessive IGBT junction to case temperature. This warning protects the IGBT(s) and can be activated by a short circuit in the motor cable.
See also aux codes: 0001 (U-phase upper), 0002 (U-phase lower), 0004 (V-phase upper), etc.
Remedy:
- Check motor cable.
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A3A1
DC link overvoltage |
Cause: Intermediate circuit DC voltage too high (when the drive is stopped).
Remedy:
- Check the supply voltage setting (parameter 95.01 Supply voltage). Note that the wrong setting may cause the motor to rush uncontrollably.
- Check for overloads on the brake chopper or resistor.
|
A3A2
DC link undervoltage |
Cause: Intermediate circuit DC voltage too low (when the drive is stopped).
Remedy:
- Check the supply voltage.
- If the problem persists, contact your local ABB representative.
|
A3AA
DC not charged |
Cause: The voltage of the intermediate DC circuit has not yet risen to operating level.
Remedy:
- If the problem persists, contact your local ABB representative.
|
A490
Incorrect temperature sensor setup |
Cause: Temperature cannot be supervised due to incorrect adapter setup.
Remedy:
- Check the settings of temperature source parameters 35.11 and 35.21.
|
A491
External temperature 1 (Editable message text) |
Cause: Measured temperature 1 has exceeded warning limit.
Remedy:
- Check the value of parameter 35.02 Measured temperature 1.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
- Check the value of 35.13 Temperature 1 warning limit.
|
A492
External temperature 2 (Editable message text) |
Cause: Measured temperature 2 has exceeded warning limit.
Remedy:
- Check the value of parameter 35.03 Measured temperature 2.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
- Check the value of 35.23 Temperature 2 warning limit.
|
A4A0
Control board temperature |
Cause: Control board temperature is too high.
Aux codes:
– (none): Temperature above warning limit
– 0001: Thermistor broken
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- For code 0001: Contact an ABB service representative for control board replacement.
|
A4A1
IGBT overtemperature |
Cause: Estimated drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A4A9
Cooling |
Cause: Drive module temperature is excessive.
Remedy:
- Check ambient temperature. If it exceeds 50 °C /122 °F, ensure that load current does not exceed derated load capacity.
- Check drive module cooling air flow and fan operation.
- Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
|
A4B0
Excess temperature |
Cause: Power unit module temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A4B1
Excess temperature difference |
Cause: High temperature difference between the IGBTs of different phases.
Remedy:
- Check the motor cabling.
- Check cooling of drive module(s).
|
A4F6
IGBT temperature |
Cause: Drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
A581
Fan |
Cause: Cooling fan feedback missing.
Remedy:
- Check the auxiliary code to identify the fan. Code 0 denotes main fan 1.
- Other codes (format XYZ): “X” = state (1: ID run, 2: normal). “Z” = index (1: Main fan 1, 2: Main fan 2, 3: Main fan 3).
- Check fan operation and connection.
- Replace fan if faulty.
|
A5A0
Safe torque off (Programmable warning 31.22) |
Cause: Safe torque off function is active, i.e., safety circuit signal(s) connected to connector STO is lost.
Remedy:
- Check safety circuit connections. See chapter “The Safe torque off function” in Hardware manual.
- Check the value of parameter 95.04 Control board supply.
|
A5EA
Measurement circuit temperature |
Cause: Problem with internal temperature measurement of the drive.
Remedy:
- Check the auxiliary code. They depend on the control unit type.
- Frames R1…R4: Contact your local ABB representative.
- Frames R6…R11: Check specific aux codes (0001: U-phase IGBT, 0002: V-phase, etc.) and contact your local ABB representative.
- FAh code (1111 1010): Ambient temperature.
|
A5EB
PU board powerfail |
Cause: Power unit power supply failure.
Remedy:
- Contact your local ABB representative.
|
A5ED
Measurement circuit ADC |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
A5EE
Measurement circuit DFF |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
A5EF
PU state feedback |
Cause: State feedback from output phases does not match control signals.
Remedy:
- Contact your local ABB representative.
|
A5F0
Charging feedback |
Cause: Charging feedback signal missing.
Remedy:
- Check the feedback signal coming from the charging system.
|
A682
Flash erase speed exceeded |
Cause: The flash memory (in the memory unit) has been erased too frequently, compromising the lifetime of the memory.
Remedy:
- Avoid forcing unnecessary parameter saves by parameter 96.07 or cyclic parameter writes.
- Check the auxiliary code (format XYYY YZZZ). “X” specifies source (1: generic). “ZZZ” specifies the flash subsector number.
|
A686 Checksum mismatch |
Cause:
The calculated parameter checksum does not match any enabled reference checksum.
Programmable warning: 96.54 Checksum action.
Remedy:
- Check that all necessary approved (reference) checksums (96.71…96.72) are enabled in 96.55 Checksum control word.
- Check the parameter configuration.
- Using 96.55 Checksum control word, enable a checksum parameter and copy the actual checksum into that parameter.
|
A687 Checksum configuration |
Cause:
An action has been defined for a parameter checksum mismatch but the feature has not been configured.
Remedy:
- Contact your local ABB representative for configuring the feature.
- Or, disable the feature in 96.54 Checksum action.
|
A6A4 Motor nominal value |
Cause:
The motor parameters are set incorrectly. The drive is not dimensioned correctly.
Aux codes:
0001: Slip frequency is too small.
0002: Synchronous and nominal speeds differ too much.
0003: Nominal speed is higher than synchronous speed with 1 pole pair.
0004: Nominal current is outside limits.
0005: Nominal voltage is outside limits.
0006: Nominal power is higher than apparent power.
0007: Nominal power not consistent with nominal speed and torque.
0008: Motor nominal power factor is not within limits [0.5…0.97].
Remedy:
- Check the auxiliary code.
- Check the settings of the motor configuration parameters in groups 98 and 99.
- Check that the drive is sized correctly for the motor.
|
A6A5 No motor data |
Cause:
Parameters in group 99 have not been set.
Remedy:
- Check that all the required parameters in group 99 have been set.
- Note: It is normal for this warning to appear during start-up until motor data is entered.
|
A6A6 Voltage category unselected |
Cause:
The voltage category has not been defined.
Remedy:
- Set voltage category in parameter 95.01 Supply voltage.
|
A6A7 System time not set |
Cause:
System time is not set. Timed functions cannot be used and fault log dates are not correct.
Remedy:
- Set the system time manually or connect the control panel to the drive to synchronize the clock.
- If basic control panel is used, synchronize the clock through the EFB or a fieldbus module.
- Set parameter 34.10 Timed functions enable to Disabled to disable the timed functions if they are not used.
|
A6B0 User lock is open |
Cause:
The user lock is open, ie, user lock configuration parameters 96.100…96.102 are visible.
Remedy:
- Close the user lock by entering an invalid pass code in parameter 96.02 Pass code.
- See section Parameter checksum calculation (page 214).
|
A6B1 User pass code not confirmed |
Cause:
A new user pass code has been entered in parameter 96.100 but not confirmed in 96.101.
Remedy:
- Confirm the new pass code by entering the same code in 96.101.
- To cancel, close the user lock without confirming the new code.
|
A6D1 FBA A parameter conflict |
Cause:
The drive does not have a functionality requested by a PLC, or requested functionality has not been activated.
Remedy:
- Check PLC programming.
- Check settings of parameter group 50 Fieldbus adapter (FBA).
|
A6E5 AI parametrization |
Cause:
The current/voltage hardware setting of an analog input does not correspond to parameter settings.
Remedy:
- Check the event log for an auxiliary code to identify the analog input in conflict.
- Adjust either the hardware setting (on the drive control unit) or parameter 12.15/12.25.
- Note: Control board reboot (via power cycle or param 96.08) is required to validate hardware changes.
|
A6E6 ULC configuration |
Cause:
User load curve configuration error.
Aux codes:
0000: Speed points inconsistent.
0001: Frequency points inconsistent.
0002: Underload point above overload point.
0003: Overload point below underload point.
Remedy:
- Check the auxiliary code and see actions below.
- 0000: Check speed points (37.11…37.15) increase in value.
- 0001: Check frequency points (37.20…37.16) increase in value.
- 0002/0003: Check overload points (37.31…37.35) vs underload points (37.21…37.25).
|
A6E7 IPC configuration warning |
Cause:
IPC configuration error.
Aux codes:
0001: IPC incorrectly configured for EFB.
0002: IPC incorrectly configured for FBA.
Remedy:
- Check the auxiliary code.
- 0001: Check parameters 76.21, 58.01, and 76.24.
- 0002: Check parameters 76.21 and 50.01.
|
A6E8 IPC version mismatch |
Cause:
The master and follower(s) do not have the same IPC version and will not run in IPC mode.
Remedy:
- Check 07.05 Firmware version of all drives on the IPC network.
- Load the drive(s) as needed with the desired firmware version.
|
A780 Motor stall |
Cause:
Motor is operating in stall region because of, for example, excessive load or insufficient motor power.
Programmable warning: 31.24 Stall function.
Remedy:
- Check motor load and drive ratings.
- Check fault function parameters.
|
A783 Motor overload |
Cause:
Motor current is too high.
Remedy:
- Check for overloaded motor.
- Adjust the parameters used for the motor overload function (35.51…35.53 and 35.55…35.56).
|
A784 Motor disconnect |
Cause:
All three output phases are disconnected from motor.
Remedy:
- Check that switches between drive and motor are closed.
- Check that all cables between drive and motor are connected and secured.
- If no issue was detected and drive output was actually connected to motor, contact ABB.
|
A793 BR excess temperature |
Cause:
Brake resistor temperature has exceeded warning limit defined by parameter 43.12 Brake resistor warning limit.
Remedy:
- Stop drive. Let resistor cool down.
- Check resistor overload protection function settings (parameter group 43 Brake chopper).
- Check warning limit setting, parameter 43.12.
- Check that the resistor has been dimensioned correctly.
- Check that braking cycle meets allowed limits.
|
A794 BR data |
Cause:
Brake resistor data has not been given.
Aux codes:
0000 0001: Resistance value too low.
0000 0002: Thermal time constant not given.
0000 0003: Maximum continuous power not given.
Remedy:
- Check settings in parameters 43.08…43.10 based on aux code.
- 0001: Check value of 43.10 Brake resistance.
- 0002: Check value of 43.08 Brake resistor thermal tc.
- 0003: Check value of 43.09 Brake resistor Pmax cont.
|
A79C BC IGBT excess temperature |
Cause:
Brake chopper IGBT temperature has exceeded internal warning limit.
Remedy:
- Let chopper cool down.
- Check for excessive ambient temperature.
- Check for cooling fan failure.
- Check for obstructions in the air flow.
- Check the dimensioning and cooling of the cabinet.
- Check resistor overload protection function settings (parameters 43.06…43.10).
- Check minimum allowed resistor value for the chopper being used.
- Check that braking cycle meets allowed limits.
- Check that drive supply AC voltage is not excessive.
|
A7AB Extension I/O configuration failure |
Cause:
Installed extension module is not the same as configured.
Remedy:
- Check that the installed extension module (shown by parameter 15.02) is the same as selected by parameter 15.01.
|
A7C1 FBA A communication |
Cause:
Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.
Programmable warning: 50.02.
Remedy:
- Check status of fieldbus communication. See user documentation of fieldbus interface.
- Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A data out.
- Check cable connections.
- Check if communication master is able to communicate.
|
A7CE EFB comm loss |
Cause:
Communication break in embedded fieldbus (EFB) communication.
Programmable warning: 58.14.
Remedy:
- Check the status of the fieldbus master (online/offline/error etc.).
- Check cable connections to the EIA-485/X5 terminals 29, 30 and 31 on the control unit.
|
A7EE Panel loss |
Cause:
Control panel or PC tool selected as active control location for drive has ceased communicating.
Programmable warning: 49.05.
Remedy:
- Check PC tool or control panel connection.
- Check control panel connector.
- Check mounting platform if being used.
- Disconnect and reconnect the control panel.
|
A88F Cooling fan |
Cause:
Maintenance timer limit exceeded.
Remedy:
- Consider changing the cooling fan.
- Parameter 05.04 Fan on-time counter shows the running time of the cooling fan.
|
A8A0 AI supervision |
Cause:
An analog signal is outside the limits specified for the analog input.
Programmable warning: 12.03.
Remedy:
- Check signal level at the analog input.
- Check the wiring connected to the input.
- Check the minimum and maximum limits of the input in parameter group 12 Standard AI.
|
A8A1 RO life warning |
Cause:
The relay has changed states more than the recommended number of times.
Aux code 0001: Relay output 1
Aux code 0002: Relay output 2
Aux code 0003: Relay output 3
Remedy:
- Change the control board or stop using the relay output.
- Check the auxiliary code to identify the specific relay output (1, 2, or 3).
|
A8A2 RO toggle warning |
Cause:
The relay output is changing states faster than recommended.
Remedy:
- Replace the signal connected to the relay output source with a less frequently changing signal.
- Check the auxiliary code (e.g., 0001 for Relay output 1).
- Select a different signal with parameter 10.24 RO1 source.
|
A8B0 ABB Signal supervision 1 (Programmable warning: 32.06) |
Cause: Warning generated by the signal supervision function 1.
Remedy:
- Check the source of the warning (parameter 32.07 Supervision 1 signal).
|
A8B1 ABB Signal supervision 2 (Programmable warning: 32.16) |
Cause: Warning generated by the signal supervision function 2.
Remedy:
- Check the source of the warning (parameter 32.17 Supervision 2 signal).
|
A8B2 ABB Signal supervision 3 (Programmable warning: 32.26) |
Cause: Warning generated by the signal supervision function 3.
Remedy:
- Check the source of the warning (parameter 32.27 Supervision 3 signal).
|
A8B3 ABB Signal supervision 4 (Programmable warning: 32.36) |
Cause: Warning generated by the signal supervision function 4.
Remedy:
- Check the source of the warning (parameter 32.37 Supervision 4 signal).
|
A8B4 ABB Signal supervision 5 (Programmable warning: 32.46) |
Cause: Warning generated by the signal supervision function 5.
Remedy:
- Check the source of the warning (parameter 32.47 Supervision 5 signal).
|
A8B5 ABB Signal supervision 6 (Programmable warning: 32.56) |
Cause: Warning generated by the signal supervision function 6.
Remedy:
- Check the source of the warning (parameter 32.57 Supervision 6 signal).
|
A8BE ULC overload warning (Programmable fault: 37.03) |
Cause: Selected signal has exceeded the user overload curve.
Remedy:
- Check for any operating conditions increasing the monitored signal (for example, the loading of the motor if the torque or current is being monitored).
- Check the definition of the load curve (parameter group 37 User load curve).
|
A8BF ULC underload warning (Programmable fault: 37.04) |
Cause: Selected signal has fallen below the user underload curve.
Remedy:
- Check for any operating conditions decreasing the monitored signal (for example, loss of load if the torque or current is being monitored).
- Check the definition of the load curve (parameter group 37 User load curve).
|
A981 External warning 1 (Programmable warning: 31.01) |
Cause: Fault in external device 1.
Remedy:
- Check the external device.
- Check setting of parameter 31.01 External event 1 source.
|
A982 External warning 2 (Programmable warning: 31.03) |
Cause: Fault in external device 2.
Remedy:
- Check the external device.
- Check setting of parameter 31.03 External event 2 source.
|
A983 External warning 3 (Programmable warning: 31.05) |
Cause: Fault in external device 3.
Remedy:
- Check the external device.
- Check setting of parameter 31.05 External event 3 source.
|
A984 External warning 4 (Programmable warning: 31.07) |
Cause: Fault in external device 4.
Remedy:
- Check the external device.
- Check setting of parameter 31.07 External event 4 source.
|
A985 External warning 5 (Programmable warning: 31.09) |
Cause: Fault in external device 5.
Remedy:
- Check the external device.
- Check setting of parameter 31.09 External event 5 source.
|
AF88 Season configuration warning |
Cause: You have configured a season which starts before the previous season.
Remedy:
- Configure the seasons with increasing start dates.
- See parameters 34.60 Season 1 start date…34.63 Season 4 start date.
|
AFAA Autoreset |
Cause: A fault is about to be autoreset.
Remedy:
- Informative warning. See the settings in parameter group 31 Fault functions.
|
AFE1 Emergency stop (off2) |
Cause: Drive has received an emergency stop (mode selection off2) command.
Remedy:
- Check that it is safe to continue operation. Then return emergency stop push button to normal position. Restart drive.
- If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.
|
AFE2 Emergency stop (off1 or off3) |
Cause: Drive has received an emergency stop (mode selection off1 or off3) command.
Remedy:
- Check that it is safe to continue operation. Then return emergency stop push button to normal position. Restart drive.
- If the emergency stop was unintentional, check the source selected by parameter 21.05 Emergency stop source.
|
AFE9 Start delay |
Cause: The start delay is active and the drive will start the motor after a predefined delay.
Remedy:
- Informative warning. See parameter 21.22 Start delay.
|
AFED Run permissive |
Cause: Run permissive is keeping the drive from running the motor.
Remedy:
- Check the setting of (and source selected by) parameter 20.40 Run permissive.
|
AFEE Start interlock 1 |
Cause: Start interlock 1 is keeping the drive from starting.
Remedy:
- Check the signal source selected for parameter 20.41 Start interlock 1.
|
AFEF Start interlock 2 |
Cause: Start interlock 2 is keeping the drive from starting.
Remedy:
- Check the signal source selected for parameter 20.42 Start interlock 2.
|
AFF0 Start interlock 3 |
Cause: Start interlock 3 is keeping the drive from starting.
Remedy:
- Check the signal source selected for parameter 20.43 Start interlock 3.
|
AFF1 Start interlock 4 |
Cause: Start interlock 4 is keeping the drive from starting.
Remedy:
- Check the signal source selected for parameter 20.44 Start interlock 4.
|
AFF2 Run permissive forced warning |
Cause: A forced DI is used as a source for parameter 20.40 Run permissive.
Remedy:
- If 20.40 Run permissive uses DIx as the source, check if the bit corresponding to DIx in parameter 10.03 DI force selection is 1.
|
AFF3 Start interlock forced warning |
Cause: One or more forced DIs is used as a source for one or more of parameters 20.41 Start interlock 1 … 20.44 Start interlock 4.
Remedy:
- Check all parameters 20.41 Start interlock 1 … 20.44 Start interlock 4.
- If any of these parameters uses DIx as the source, check if the bit corresponding to DIx in parameter 10.03 DI force selection is 1.
|
AFF5 Override new start required |
Cause: The Safe torque off function was active and has been reset while in Override.
Remedy:
- A new start signal is required to start the drive again.
|
AFF6 Identification run |
Cause: Motor ID run will occur at next start.
Remedy:
|
AFF8 Motor heating active |
Cause: Pre-heating is being performed.
Remedy:
- Informative warning. Motor pre-heating is active.
- Current specified by parameter 21.16 Pre-heating current is being passed through the motor.
|
AFFE Override active |
Cause: Drive is in Override mode.
Remedy:
|
B5A0 STO event (Programmable event: 31.22) |
Cause: Safe torque off function is active, ie, safety circuit signal(s) connected to connector STO is lost.
Remedy:
- Informative warning. Check safety circuit connections.
- For more information, see chapter The Safe torque off function in the Hardware manual.
- See description of parameter 31.22 STO indication run/stop.
|
B5A2 Power applied |
Cause: The drive was powered up or the control board was rebooted successfully.
Remedy:
|
B681 Hand mode selected |
Cause: The drive was placed in Hand mode.
Remedy:
- Informative event. Check the control panel to ensure that the current control location is correct.
|
B682 Off mode selected |
Cause: The drive was placed in Off mode.
Remedy:
- Informative event. Check the control panel to ensure that the current control location is correct.
|
B683 Auto mode selected |
Cause: The drive was placed in Auto mode.
Remedy:
- Informative event. Check the control panel to ensure that the current control location is correct.
|
B686 Checksum mismatch (Programmable event: 96.54) |
Cause: The calculated parameter checksum does not match any enabled reference checksum.
Remedy:
- See A686 Checksum mismatch (page 226).
|
B687 Auto start command |
Cause: The drive received a start command while in Auto mode.
Remedy:
|
B688 Auto stop command |
Cause: The drive received a stop command while in Auto mode.
Remedy:
|
B689 Modulating started |
Cause: The drive started modulating.
Remedy:
|
B68A Modulating stopped |
Cause: The drive stopped modulating.
Remedy:
|
D501 No more available PFC motors |
Cause: No more PFC motors can be started because they can be interlocked or in the Hand mode.
Remedy:
- Check that there are no interlocked PFC motors, see parameters: 76.81…76.84.
- If all motors are in use, the PFC system is not adequately dimensioned to handle the demand.
|
D502 All motors interlocked |
Cause: All the motors in the PFC system are interlocked.
Remedy:
- Check that there are no interlocked PFC motors, see parameters 76.81…76.84.
|
D503 VSD controlled PFC motor interlocked |
Cause: The motor connected to the drive is interlocked (unavailable).
Remedy:
- Motor connected to the drive is interlocked and thus cannot be started.
- Remove the corresponding interlock to start the drive controlled PFC motor. See parameters 76.81…76.84.
|
D504 Damper timeout |
Cause: Discharge air or outside air damper has timed out.
Remedy:
- Check the auxiliary code, which identifies the parameter to be checked (see below).
|
D504 (Aux: 0001) Damper timeout |
Cause: Discharge air damper was commanded to open and it timed out while opening.
Remedy:
|
D504 (Aux: 0002) Damper timeout |
Cause: Discharge air damper was commanded to close and it timed out while closing.
Remedy:
|
D504 (Aux: 0003) Damper timeout |
Cause: Outside air damper was commanded to open and it timed out while opening.
Remedy:
|
D504 (Aux: 0004) Damper timeout |
Cause: Outside air damper was commanded to close and it timed out while closing.
Remedy:
|
D50A Running dry (Programmable warning: 82.20) |
Cause: Dry run protection is activated.
Remedy:
- Check the pump inlet for sufficient water level.
- Check dry run protection settings in parameters 82.20 Dry run protection and 82.21 Dry run source.
|
D50B Pipe fill-timeout (Programmable warning: 82.25) |
Cause: Soft pipe fill is reached the timeout limit. The PID output is not reached the setpoint after reference ramping is ended and timeout limit is elapsed.
Remedy:
- Check the pipe for possible leakage.
- See parameter 82.25 Soft pipe fill supervision and 82.26 Time-out limit.
|
D50C Maximum flow protection (Programmable warning: 80.17) |
Cause: Actual flow is exceeded the defined warning level.
Remedy:
- Check the system for leakages.
- Check flow protection settings in parameters 80.15 Maximum flow, 80.17 Maximum flow protection and 80.19 Flow check delay.
|
D50D Minimum flow protection (Programmable warning: 80.18) |
Cause: Actual flow is below the defined warning level.
Remedy:
- Check that the inlet and outlet valves are open.
- Check flow protection settings in parameters 80.16 Minimum flow, 80.18 Minimum flow protection and 80.19 Flow check delay.
|
D50E Outlet minimum pressure (Programmable warning: 82.30) |
Cause: Measured outlet pressure is below the defined warning limit.
Remedy:
- Check the pump outlet for leakages.
- Check the configuration of outlet pressure protection.
- See parameters 82.30 Outlet minimum pressure protection and 82.31 Outlet minimum pressure warning level.
|
D50F Outlet maximum pressure (Programmable warning: 82.35) |
Cause: Measured outlet pressure is above the defined warning limit.
Remedy:
- Check the pump outlet for blockages or closed valve.
- Check the configuration of outlet pressure protection.
- See parameters 82.35 Outlet maximum pressure protection and 82.37 Outlet maximum pressure warning level.
|
D510 Inlet minimum pressure (Programmable warning: 82.40) |
Cause: Measured inlet pressure is below the defined warning level.
Remedy:
- Check the pump inlet for blockages or closed valve.
- Check the configuration of inlet pressure protection.
- See parameters 82.40 Inlet minimum pressure protection and 82.41 Inlet minimum pressure warning level.
|
D590 Restart delay |
Cause: The restart delay is active.
Remedy:
- Check parameter 21.40 Restart delay.
- The drive cannot be started until the restart delay has elapsed. The restart delay can be bypassed by setting parameter 21.42 Restart delay remaining to 0.
|
D590 (Aux: 0000) Restart delay |
Cause: Contact your local ABB representative.
Remedy:
- Contact your local ABB representative.
|
D590 (Aux: 0002) Restart delay |
Cause: Pump short cycle protection.
Remedy:
- Wait for the delay to expire or check protection settings.
|
1080 Backup/Restore timeout |
Cause: Control panel or PC tool has failed to communicate with the drive when backup was being made or restored.
Remedy:
- Request backup or restore again.
|
1081 Rating ID fault |
Cause: Drive software has not been able to read the rating ID of the drive.
Remedy:
- Reset the fault to make the drive try to reread the rating ID.
- If the fault reappears, cycle the power to the drive. You may have to repeat this.
- If the fault persists, contact your local ABB representative.
|
2310 Overcurrent |
Cause: Output current has exceeded internal fault limit. In addition to an actual overcurrent situation, this fault may also be caused by an earth fault or supply phase loss.
Remedy:
- Check the received auxiliary code (format XXXYYYZZ). The ZZ part indicates the overcurrent type and the phase (bit0=U, bit1=V, bit2=W). Bit7=1 indicates SW overcurrent.
- Check the motor load.
- Check acceleration times in parameter group 23 Speed reference ramp or 28 Frequency reference chain.
- Check parameters 46.01 Speed scaling, 46.02 Frequency scaling and 46.03 Torque scaling.
- Check the motor and motor cable (including phasing and delta/star connection).
- Check there are no contactors opening and closing in motor cable.
- Check that the start-up data in parameter group 99 Motor data corresponds to the motor rating plate.
- Check that there are no power factor correction capacitors or surge absorbers in motor cable.
- Check for an earth fault in motor or motor cables by measuring the insulation resistances.
|
2330 Earth leakage |
Cause: Drive has detected load unbalance typically due to earth fault in motor or motor cable.
Remedy:
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Check for an earth fault in motor or motor cables by measuring the insulation resistances.
- Try running the motor in scalar control mode if allowed (See parameter 99.04).
- If no earth fault can be detected, contact your local ABB representative.
|
2340 Short circuit |
Cause: Short-circuit in motor cable(s) or motor.
Auxiliary codes:
0001: Short U-phase upper (R6-R11)
0002: Short U-phase lower (R6-R11)
0004: Short V-phase upper (R6-R11)
0008: Short V-phase lower (R6-R11)
0010: Short W-phase upper (R6-R11)
0020: Short W-phase lower (R6-R11)
0040: DC capacitor short circuit (R6-R11)
0080: State feedback mismatch (R6-R7)
Remedy:
- Check motor and motor cable for cabling errors.
- Check there are no power factor correction capacitors or surge absorbers in motor cable.
- Cycle the power to the drive.
|
2381 IGBT overload |
Cause: Excessive IGBT junction to case temperature. This fault protects the IGBT(s) and can be activated by a short circuit in the motor cable.
Remedy:
- Check motor cable.
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
3130 Input phase loss |
Cause: Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. (Programmable fault 31.21).
Remedy:
- Check input power line fuses.
- Check for loose power cable connections.
- Check for input power supply imbalance.
|
3181 Wiring or earth fault |
Cause: Incorrect input power and motor cable connection (i.e. input power cable is connected to drive motor connection). (Programmable fault 31.23).
Remedy:
- Check input power connections.
|
3210 DC link overvoltage |
Cause: Excessive intermediate circuit DC voltage.
Remedy:
- Check that overvoltage control is on (parameter 30.30).
- Check that the supply voltage matches the nominal input voltage of the drive.
- Check the supply line for static or transient overvoltage.
- Check brake chopper and resistor (if present).
- Check deceleration time.
- Use coast-to-stop function (if applicable).
- Retrofit drive with brake chopper and brake resistor.
- Check that the brake resistor is dimensioned properly and the resistance is between acceptable range.
|
3220 DC link undervoltage |
Cause: Intermediate circuit DC voltage is not sufficient because of a missing supply phase, blown fuse or fault in the rectifier bridge.
Remedy:
- Check supply cabling, fuses and switchgear.
|
3381 Output phase loss |
Cause: Motor circuit fault due to missing motor connection (all three phases are not connected). (Programmable fault 31.19).
Remedy:
|
4110 Control board temperature |
Cause: Control board temperature is too high.
Remedy:
- Check proper cooling of the drive.
- Check the auxiliary cooling fan.
|
4210 IGBT overtemperature |
Cause: Estimated drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
4290 Cooling |
Cause: Drive module temperature is excessive.
Remedy:
- Check ambient temperature. If it exceeds 50 °C / 122 °F, ensure that load current does not exceed derated load capacity.
- Check drive module cooling air flow and fan operation.
- Check inside of cabinet and heatsink of drive module for dust pick-up. Clean whenever necessary.
|
42F1 IGBT temperature |
Cause: Drive IGBT temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
4310 Excess temperature |
Cause: Power unit module temperature is excessive.
Remedy:
- Check ambient conditions.
- Check air flow and fan operation.
- Check heatsink fins for dust pick-up.
- Check motor power against drive power.
|
4380 Excess temperature difference |
Cause: High temperature difference between the IGBTs of different phases.
Remedy:
- Check the motor cabling.
- Check cooling of drive module(s).
|
4981 External temperature 1 |
Cause: Measured temperature 1 has exceeded fault limit. (Editable message text).
Remedy:
- Check the value of parameter 35.02 Measured temperature 1.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
|
4982 External temperature 2 |
Cause: Measured temperature 2 has exceeded fault limit. (Editable message text).
Remedy:
- Check the value of parameter 35.03 Measured temperature 2.
- Check the cooling of the motor (or other equipment whose temperature is being measured).
|
5080 Fan |
Cause: Cooling fan feedback missing.
Remedy:
- See A581 Fan (page 224 of manual).
|
5090 STO hardware failure |
Cause: STO hardware diagnostics has detected hardware failure.
Remedy:
- Contact your local ABB representative for hardware replacement.
|
5091 Safe torque off |
Cause: Safe torque off function is active, i.e., safety circuit signal(s) connected to connector STO is broken during start or run. (Programmable fault 31.22).
Remedy:
- Check safety circuit connections.
- Check parameter 31.22 STO indication run/stop.
- Check the value of parameter 95.04 Control board supply.
|
5092 PU logic error |
Cause: Power unit memory has cleared.
Remedy:
- Contact your local ABB representative.
|
5093 Rating ID mismatch |
Cause: The hardware of the drive does not match the information stored in the memory. This may occur, for example, after a firmware update.
Remedy:
- Cycle the power to the drive. You may have to repeat this.
|
5094 Measurement circuit temperature |
Cause: Problem with internal temperature measurement of the drive.
Remedy:
- Contact your local ABB representative.
|
5098 I/O communication loss |
Cause: Internal standard I/O communication failure.
Remedy:
- Try resetting the fault or reboot the drive.
|
50A0 Fan |
Cause: Cooling fan stuck or disconnected.
Remedy:
- Check fan operation and connection.
- Replace fan if faulty.
|
5681 PU communication |
Cause: Communication errors detected between the drive control unit and the power unit.
Remedy:
- Check the connection between the drive control unit and the power unit.
- Check the value of parameter 95.04 Control board supply.
|
5682 Power unit lost |
Cause: Connection between the drive control unit and the power unit is lost.
Remedy:
- Check the connection between the control unit and the power unit.
|
5691 Measurement circuit ADC |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
5692 PU board powerfail |
Cause: Power unit power supply failure.
Remedy:
- Contact your local ABB representative.
|
5693 Measurement circuit DFF |
Cause: Measurement circuit fault.
Remedy:
- Contact your local ABB representative.
|
5697 Charging feedback |
Cause: Charging feedback signal missing.
Remedy:
- Check the feedback signal coming from the charging system.
|
5698 Unknown PU fault |
Cause: The power unit logic has generated a fault which is not known by the software.
Remedy:
- Check the logic and software compatibility.
|
6181 FPGA version incompatible |
Cause: Firmware and FPGA versions are incompatible.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
6200 Checksum mismatch |
Cause: The calculated parameter checksum does not match any enabled reference checksum.
Remedy:
- See A686 Checksum mismatch (page 226).
|
6306 FBA A mapping file |
Cause: Fieldbus adapter A mapping file read error.
Remedy:
- Contact your local ABB representative.
|
6481 Task overload |
Cause: Internal fault.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
6487 Stack overflow |
Cause: Internal fault.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
64A1 Internal file load |
Cause: File read error.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
64A4 Rating ID fault |
Cause: Rating ID load error.
Remedy:
- Contact your local ABB representative.
|
64A6 Adaptive program |
Cause: Error running the adaptive program. Check the auxiliary code (format XXYY ZZZZ).
Remedy:
- “XX” specifies the number of the state (00=base program).
- “YY” specifies the number of the function block (0000=generic error).
- “ZZZZ” indicates the problem.
|
64B1 Internal SSW fault |
Cause: Internal fault.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
64B2 User set fault |
Cause: Loading of user parameter set failed because:
- requested set does not exist
- set is not compatible with control program
- drive was switched off during loading
Remedy:
- Ensure that a valid user parameter set exists.
- Reload if uncertain.
|
64B3 Macro parameterization error |
Cause: Loading of macro parameter set failed.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
64E1 Kernel overload |
Cause: Operating system error.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
- If the problem persists, contact your local ABB representative.
|
64FF Fault reset |
Cause: A fault has been reset from the control panel, Drive composer PC tool, fieldbus or I/O.
Remedy:
|
6581 Parameter system |
Cause: Parameter load or save failed.
Remedy:
- Try forcing a save using parameter 96.07 Parameter save manually.
- Retry.
|
6591 Backup/Restore timeout |
Cause: During backup creating or restoring operation a control panel or PC tool has failed to communicate with the drive.
Remedy:
- Check control panel or PC tool communication.
- Check if it is still in backup or restore state.
|
65A1 FBA A parameter conflict |
Cause: The drive does not have a functionality requested by PLC, or requested functionality has not been activated.
Remedy:
- Check PLC programming.
- Check settings of parameter groups 50 Fieldbus adapter (FBA) and 51 FBA A settings.
|
6681 EFB comm loss |
Cause: Communication break in embedded fieldbus (EFB) communication.
Remedy:
- Check the status of the fieldbus master (online/offline/error etc.).
- Check cable connections to the EIA-485/X5 terminals on the control unit.
|
6682 EFB config file |
Cause: Embedded fieldbus (EFB) configuration file could not be read.
Remedy:
- Contact your local ABB representative.
|
6683 EFB invalid parameterization |
Cause: Embedded fieldbus (EFB) parameter settings inconsistent or not compatible with selected protocol.
Remedy:
- Check the settings in parameter group 58 Embedded fieldbus.
|
6684 EFB load fault |
Cause: Embedded fieldbus (EFB) protocol firmware could not be loaded. Version mismatch between EFB protocol firmware and drive firmware.
Remedy:
- Contact your local ABB representative.
|
6685 EFB fault 2 |
Cause: Fault reserved for the EFB protocol application.
Remedy:
- Check the documentation of the protocol.
|
6686 EFB fault 3 |
Cause: Fault reserved for the EFB protocol application.
Remedy:
- Check the documentation of the protocol.
|
6882 Text 32-bit table overflow |
Cause: Internal fault.
Remedy:
- Reset the fault.
- Contact your local ABB representative if the fault persists.
|
6885 Text file overflow |
Cause: Internal fault.
Remedy:
- Reset the fault.
- Contact your local ABB representative if the fault persists.
|
7081 Control panel loss |
Cause: Control panel or PC tool selected as active control location for drive has ceased communicating.
Remedy:
- Check PC tool or control panel connection.
- Check control panel connector.
- Disconnect and reconnect the control panel.
|
7082 I/O module comm loss |
Cause: Communication between IO module and drive is not working properly.
Remedy:
- Check the IO module installation.
|
7085 Incompatible option module |
Cause: Fieldbus option module not supported.
Remedy:
- Replace the module with a supported type.
|
7086 AI Overvoltage |
Cause: An overvoltage has been detected on an analog input.
Remedy:
|
7087 I/O module configuration fault |
Cause: I/O module configuration not supported or illegal.
Remedy:
|
7100 Excitation current |
Cause: Excitation current feedback low or missing.
Remedy:
- (No remedy specified in source)
|
7121 Motor stall |
Cause: Motor is operating in stall region (e.g. excessive load or insufficient motor power).
Remedy:
- Check motor load and drive ratings.
- Check fault function parameters.
|
7122 Motor overload |
Cause: Motor current is too high.
Remedy:
- Check for overloaded motor.
- Adjust the parameters used for the motor overload function (35.51…35.53) and 35.55…35.56.
|
7181 Brake resistor |
Cause: Brake resistor broken or not connected.
Remedy:
- Check that a brake resistor has been connected.
- Check the condition of the brake resistor.
- Check the dimensioning of the brake resistor.
|
7183 BR excess temperature |
Cause: Brake resistor temperature has exceeded fault limit defined by parameter 43.11.
Remedy:
- Stop drive. Let resistor cool down.
- Check resistor overload protection function settings (parameter group 43 Brake chopper).
- Check fault limit setting, parameter 43.11 Brake resistor fault limit.
- Check that braking cycle meets allowed limits.
|
7184 Brake resistor wiring |
Cause: Brake resistor short circuit or brake chopper control fault.
Remedy:
- Check brake chopper and brake resistor connection.
- Ensure brake resistor is not damaged.
|
7191 BC short circuit |
Cause: Short circuit in brake chopper IGBT.
Remedy:
- Ensure brake resistor is connected and not damaged.
- Check the electrical specifications of the brake resistor.
- Replace brake chopper (if replaceable).
|
7192 BC IGBT excess temperature |
Cause: Brake chopper IGBT temperature has exceeded internal fault limit.
Remedy:
- Let chopper cool down.
- Check for excessive ambient temperature.
- Check for cooling fan failure or obstructions.
- Check resistor overload protection function settings (group 43).
- Check that braking cycle meets allowed limits.
- Check that drive supply AC voltage is not excessive.
|
7310 Overspeed |
Cause: Motor is turning faster than highest allowed speed.
Remedy:
- Check minimum/maximum speed settings (30.11, 30.12).
- Check adequacy of motor braking torque.
- Check applicability of torque control.
- Check need for brake chopper and resistor(s).
|
73B0 Emergency ramp failed |
Cause: Emergency stop did not finish within expected time.
Remedy:
- Check the settings of parameters 31.32 and 31.33 (Ramp supervision).
- Check the predefined ramp times (23.11 – 23.15 for mode Off1, 23.23 for mode Off3).
|
73F0 Overfrequency |
Cause: Maximum allowed output frequency exceeded.
Remedy:
- Check the auxiliary code.
|
7510
FBA A communication |
Cause: Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost.
Remedy:
- Check status of fieldbus communication (see fieldbus user docs).
- Check settings of parameter groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in, and 53 FBA A data out.
- Check cable connections.
- Check if communication master is able to communicate.
|
8001
ULC underload fault |
Cause: User load curve: Signal has been too long under the underload curve.
Remedy:
- See parameter 37.04 ULC underload actions.
|
8002
ULC overload fault |
Cause: User load curve: Signal has been too long over the overload curve.
Remedy:
- See parameter 37.03 ULC overload actions.
|
80A0
AI supervision |
Cause: An analog signal is outside the limits specified for the analog input.
Remedy:
- Check signal level at the analog input.
- Check the wiring connected to the input.
- Check minimum/maximum limits in parameter group 12 Standard AI.
- Aux Codes:
- 0001: AI1 Less MIN
- 0002: AI1 Greater MAX
- 0003: AI2 Less MIN
- 0004: AI2 Greater MAX
|
80B0
Signal supervision 1 |
Cause: Fault generated by the signal supervision function 1.
Remedy:
- Check the source of the fault (parameter 32.07 Supervision 1 signal).
|
80B1
Signal supervision 2 |
Cause: Fault generated by the signal supervision function 2.
Remedy:
- Check the source of the fault (parameter 32.17 Supervision 2 signal).
|
80B2
Signal supervision 3 |
Cause: Fault generated by the signal supervision function 3.
Remedy:
- Check the source of the fault (parameter 32.27 Supervision 3 signal).
|
80B3
Signal supervision 4 |
Cause: Fault generated by the signal supervision function 4.
Remedy:
- Check the source of the fault (parameter 32.37 Supervision 4 signal).
|
80B4
Signal supervision 5 |
Cause: Fault generated by the signal supervision function 5.
Remedy:
- Check the source of the fault (parameter 32.47 Supervision 5 signal).
|
80B5
Signal supervision 6 |
Cause: Fault generated by the signal supervision function 6.
Remedy:
- Check the source of the fault (parameter 32.57 Supervision 6 signal).
|
9081
External fault 1 |
Cause: Fault in external device 1.
Remedy:
- Check the external device.
- Check setting of parameter 31.01 External event 1 source.
|
9082
External fault 2 |
Cause: Fault in external device 2.
Remedy:
- Check the external device.
- Check setting of parameter 31.03 External event 2 source.
|
9083
External fault 3 |
Cause: Fault in external device 3.
Remedy:
- Check the external device.
- Check setting of parameter 31.05 External event 3 source.
|
9084
External fault 4 |
Cause: Fault in external device 4.
Remedy:
- Check the external device.
- Check setting of parameter 31.07 External event 4 source.
|
9085
External fault 5 |
Cause: Fault in external device 5.
Remedy:
- Check the external device.
- Check setting of parameter 31.09 External event 5 source.
|
D404
Running dry |
Cause: Dry run protection is activated.
Remedy:
- Check the pump inlet for sufficient water level.
- Check dry run protection settings in parameters 82.20 Dry run protection and 82.21 Dry run source.
|
D405
Pipe fill-timeout |
Cause: Soft pipe fill has reached timeout limit. The PID output has not reached the setpoint after reference ramping ended.
Remedy:
- Check the pipe for possible leakage.
- See parameter 82.25 Soft pipe fill supervision and 82.26 Time-out limit.
|
D406
Maximum flow protection |
Cause: Actual flow is exceeded the defined fault level.
Remedy:
- Check the system for leakages.
- Check flow protection settings in parameters 80.15 Maximum flow, 80.17 Maximum flow protection and 80.19 Flow check delay.
|
D407
Minimum flow protection |
Cause: Actual flow is below the defined fault level.
Remedy:
- Check that the inlet and outlet valves are open.
- Check flow protection settings in parameters 80.16 Minimum flow, 80.18 Minimum flow protection and 80.19 Flow check delay.
|
D408
Outlet minimum pressure |
Cause: The measured outlet pressure is below the defined fault limit.
Remedy:
- Check the pump outlet for leakages.
- Check the configuration of outlet pressure protection.
- See parameters 82.30 Outlet minimum pressure protection and 82.32 Outlet minimum pressure fault level.
|
D409
Outlet maximum pressure |
Cause: The measured outlet pressure is above the defined fault limit.
Remedy:
- Check the pump outlet for blockages or closed valve.
- Check the configuration of outlet pressure protection.
- See parameters 82.35 Outlet maximum pressure protection and 82.38 Outlet maximum pressure fault level.
|
D40A
Inlet minimum pressure |
Cause: The measured inlet pressure is below the defined fault level.
Remedy:
- Check the pump inlet for blockages or closed valve.
- Check the configuration of inlet pressure protection.
- See parameters 82.40 Inlet minimum pressure protection and 82.42 Inlet minimum pressure fault level.
|
D40B
Damper timeout |
Cause: Discharge air or outside air damper has timed out.
Remedy:
- Check the auxiliary code to identify the parameter:
- 0001: Discharge air damper open fail (See 84.05).
- 0002: Discharge air damper close fail (See 84.08).
- 0003: Outside air damper open fail (See 84.15).
- 0004: Outside air damper close fail (See 84.18).
|
D40C
Multipump run permissive timeout |
Cause: The run permissive setting (20.40) was not satisfied within the time set in parameter 20.40 or 76.64.
Remedy:
- Check the signal source selected for parameter 20.40 Run permissive.
|
FA81
Safe torque off 1 |
Cause: Safe torque off function is active, that is, STO circuit 1 is broken.
Remedy:
- Check safety circuit connections.
- See chapter “The Safe torque off function” in Hardware manual.
- See parameter 31.22 STO indication run/stop.
- Check value of parameter 95.04 Control board supply.
|
FA82
Safe torque off 2 |
Cause: Safe torque off function is active, that is, STO circuit 2 is broken.
Remedy:
- Check safety circuit connections (See remedy for FA81).
|
FF61
ID run |
Cause: Motor ID run was not completed successfully.
Remedy:
- Check the nominal motor values in parameter group 99 Motor data.
- Check that no external control system is connected to the drive.
- Cycle the power to the drive.
- Check that no operation limits prevent completion. Restore default settings and try again.
- Check that the motor shaft is not locked.
- Auxiliary Codes:
- 0001: Max current limit too low (Check 99.06, 30.17).
- 0002: Max speed limit/field weakening too low (Check 30.11, 30.12, 99.07-99.09).
- 0003: Max torque limit too low (Check 99.12, Group 30).
- 0004: Current measurement calibration failed (Contact ABB).
- 0005-0008: Internal error (Contact ABB).
- 0009: Acceleration didn’t finish (Async motors).
- 000A: Deceleration didn’t finish (Async motors).
- 000B: Speed dropped to zero (Async motors).
- 000C: First accel fail (PM motors).
- 000D: Second accel fail (PM motors).
- 000E-0010: Internal error (Contact ABB).
- 0011: Pulse test error (Sync reluctance motors).
- 0012: Motor too large for advanced standstill ID run.
- 0013: Motor data error (Async motors).
|
FF63
STO diagnostics failure |
Cause: SW internal malfunction.
Remedy:
- Reboot the control unit (using parameter 96.08 Control board boot) or by cycling power.
|
FF81
FB A force trip |
Cause: A fault trip command has been received through fieldbus adapter A.
Remedy:
- Check the fault information provided by the PLC.
|
FF8E
EFB force trip |
Cause: A fault trip command has been received through the embedded fieldbus interface.
Remedy:
- Check the fault information provided by the PLC.
|