Hitachi NE S1 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Over-current event while at constant speed | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor may be wired incorrectly. Remedy:
|
| E02 Over-current event during deceleration | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter. Remedy:
|
| E03 Over-current event during acceleration | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. Remedy:
|
| E04 Over-current event during other conditions | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. Remedy:
|
| E05 Overload protection | Cause: When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output. Remedy:
|
| E07 Over-voltage protection | Cause: When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. Remedy:
|
| E08 Memory error | Cause: When the built-in memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. Remedy:
|
| E09 Under-voltage error | Cause: A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. Remedy:
|
| E10 Current detection error | Cause: If an error occurs in the internal current detection system, the inverter will shut off its output and display the error code. Remedy:
|
| E11 CPU error | Cause: A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. Remedy:
|
| E12 External trip | Cause: A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor. Remedy:
|
| E13 USP error | Cause: When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. Remedy:
|
| E14 Ground fault protection | Cause: The inverter is protected by the detection of ground faults between the inverter output and the motor upon during powerup tests. Remedy:
|
| E15 Input over-voltage protection | Cause: The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. An over-voltage condition exists. Remedy:
|
| E19 Inverter thermal detection circuit error | Cause: When the thermal sensor in the inverter module is not connected. Remedy:
|
| E21 Temperature error | Cause: When the inverter internal temperature is above the threshold, the thermal sensor detects excessive temperature of power devices. Remedy:
|
| E30 Driver error | Cause: An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. Remedy:
|
| E34 Output phase loss protection | Cause: When a phase loss on its outputs is detected, the inverter output is turned off. (Activated only when C157=01). Remedy:
|
| E38 Low-speed overload protection | Cause: If overload occurs during the motor operation at a very low speed, the inverter will detect the overload and shut off the output. Remedy:
|
| E40 Operator connection error | Cause: When the connection between inverter and operator keypad failed. Remedy:
|
| E41 Modbus communication error | Cause: When “trip” is selected (C076=00) as a behavior in case of communication error, inverter trips when timeout happens. Remedy:
|