INVT GD100-PV Drive Fault Codes:
| Fault Codes | Cause & Solution |
|---|---|
| OUt1 Inverter unit U phase protection | Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OUt2 Inverter unit V phase protection | Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OUt3 Inverter unit W phase protection | Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OC1 Overcurrent during acceleration | Cause: – The acceleration or deceleration is too fast; – The voltage of the grid is too low; – The power of the VFD is too low; – The load transients or is abnormal; – The grounding is short circuited or the output is phase loss; – There is strong external interference; – The overvoltage stall protection is not open. Solution: – Increase the ACC time; – Check the input power; – Select the VFD with a larger power; – Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; – Check the output configuration; – Check if there is strong interference; – Check the setting of related function codes |
| OC2 Overcurrent during deceleration | Cause: – The acceleration or deceleration is too fast; – The voltage of the grid is too low; – The power of the VFD is too low; – The load transients or is abnormal; – The grounding is short circuited or the output is phase loss; – There is strong external interference; – The overvoltage stall protection is not open. Solution: – Increase the ACC time; – Check the input power; – Select the VFD with a larger power; – Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; – Check the output configuration; – Check if there is strong interference; – Check the setting of related function codes |
| OC3 Overcurrent at constant speed | Cause: – The acceleration or deceleration is too fast; – The voltage of the grid is too low; – The power of the VFD is too low; – The load transients or is abnormal; – The grounding is short circuited or the output is phase loss; – There is strong external interference; – The overvoltage stall protection is not open. Solution: – Increase the ACC time; – Check the input power; – Select the VFD with a larger power; – Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; – Check the output configuration; – Check if there is strong interference; – Check the setting of related function codes |
| OV1/OU1 Overvoltage during acceleration | Cause: – The input voltage is abnormal; – There is large energy feedback; – No braking components; – Braking energy is not open. Solution: – Check the input power; – Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; – Install the braking components; – Check the setting of related function codes. |
| OV2/OU2 Overvoltage during deceleration | Cause: – The input voltage is abnormal; – There is large energy feedback; – No braking components; – Braking energy is not open. Solution: – Check the input power; – Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; – Install the braking components; – Check the setting of related function codes. |
| OV3/OU3 Overvoltage at constant speed | Cause: – The input voltage is abnormal; – There is large energy feedback; – No braking components; – Braking energy is not open. Solution: – Check the input power; – Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; – Install the braking components; – Check the setting of related function codes. |
| UV Bus undervoltage | Cause & Solution: 1. An instantaneous power failure occurs. – Reset the fault 2. The AC drive’s input voltage is not within the permissible range. – Adjust the voltage to normal range. 3. The bus voltage is abnormal. – Replace the AC drive. 4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal. – Replace the AC drive. |
| OL1 Motor overload | Cause: – The voltage of the power supply is too low; – The motor setting rated current is incorrect; – The motor stall or load transients is too strong. Solution: – Check the power of the supply line; – Reset the rated current of the motor; – Check the load and adjust the torque lift. |
| OL2 VFD overload | Cause: – The acceleration is too fast; – Reset the rotating motor; – The voltage of the power supply is too low; – The load is too heavy; – The motor power is too large, and the power of the VFD is too small. Solution: – Increase the ACC time; – Avoid the restarting after stopping; – Check the power of the supply line; – Select a VFD with bigger power; – Select a proper motor. |
| SPI Phase loss on input side | Cause & Solution: Phase loss or violent fluctuation occurred to R, S, and T input. 1. Three phase input is abnormal. – Eliminate faults in external circuitry 2. Drive board is abnormal. – Eliminate faults in external circuitry 3. Lightning protection board is abnormal. – There is an hardware or software issue in drive. Need to repair or replace drive. 4. Control board is abnormal. – There is an hardware or software issue in drive. Need to repair or replace drive. |
| SPO Phase loss on output side | Cause & Solution: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical) 1. Motor winding is damaged. Check resistance between motor cables. – Replace motor is winding is damaged. 2. The cable connecting the AC drive and the motor is abnormal. – Check for wiring errors and ensure the output cable is connected properly 3. The AC drive’s three-phase outputs are unbalanced when the motor is running. – Check whether the motor three-phase winding is normal. 4. The drive board or the IGBT is abnormal. – Replace the AC drive. |
| OH1 Rectifier module overheat | Cause & Solution: 1. The ambient temperature is too high. – Lower the ambient temperature. 2. The ventilation is clogged. – Clean the ventilation. 3. The fan is damaged. – Replace the cooling fan. |
| OH2 Inverter module overheat | Cause & Solution: 1. The ambient temperature is too high. – Lower the ambient temperature. 2. The ventilation is clogged. – Clean the ventilation. 3. The fan is damaged. – Replace the cooling fan. |
| EF External Fault | Cause: SI external fault input terminals action. External fault comes when the drive has detected an issue with an external control circuit or device connected to it. This means the drive has detected an issue with an external device or control circuit connected to it. Unlike error codes specific to internal drive components, the EF code is more general and can be triggered by various external factors. Solution: 1. An alarm function of the external equipment was activated. – Inspect external equipment operation. – Remove the cause of the alarm that occurred. 2. Connection has been performed incorrectly. – Check if the wire for the external alarm signal is correctly connected to the terminal to which the “Alarm from external equipment” has been assigned. – Connect the wire for the alarm signal correctly. 3. Incorrect settings. – Check if the “Alarm from external equipment” has not been assigned to an unassigned terminal. – Correct the assignment. |
| CE RS485 communication Fault | Cause: – The baud rate setting is incorrect; – Fault occurs to the communication wiring; – The communication address is wrong; – There is strong interference to the communication. Solution: – Set proper baud rate; – Check the communication connection distribution; – Set proper communication address; – Chang or replace the connection distribution or improve the anti-interference capability. |
| ItE Current detection fault | Cause: – The control panel connector is in poor contact; – An exception occurs on the magnifying circuit. Solution: – Check the connector and re-plug – Change the main control panel |
| tE Motor autotuning fault | Cause: – The motor capacity does not comply with the VFD capability; – The rated parameter of the motor does not set correctly; – The offset between the parameters from autotuning and the standard parameter is huge; – Autotuning overtime. Solution: – Change the VFD mode; – Set the rated parameter according to the motor name plate; – Empty the motor load; – Check the motor connection and set the parameter; – Check if the upper limit frequency is above 2/3 of the rated frequency |
| EEP EEPROM operation fault | Cause: – Error of controlling the write and read of the parameters; – Damage to EEPROM. Solution: – Press STOP/RST to reset; – Change the main control panel. |
| PIDE PID feedback offline fault | Cause: – PID feedback offline; – PID feedback source disappear. Solution: – Check the PID feedback signal; – Check the PID feedback source. |
| END Running time reached | Cause: The actual running time of the VFD is above the internal setting running time. Solution: Ask for the supplier and adjust the setting running time. |
| OL3 Electronics overload | Cause: The VFD will report overload pre-alarm according to the set value. Solution: Check the load and the overload pre-alarm threshold. |
| ETH1 To-ground short- circuit fault 1 | Cause: – The output of the VFD is short circuited with the ground; – There is fault in the current detection circuit; – There is a great difference between the actual motor power setting and the VFD power. Solution: – Check if the connection of the motor is normal or not; – Change the hall; – Change the main control panel; – Reset the correct motor parameter; – Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| ETH2 To-ground short- circuit fault 2 | Cause: – The output of the VFD is short circuited with the ground; – There is fault in the current detection circuit; – There is a great difference between the actual motor power setting and the VFD power. Solution: – Check if the connection of the motor is normal or not; – Change the hall; – Change the main control panel; – Reset the correct motor parameter; – Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| dEu Speed deviation fault | Cause: Load is too heavy, or stall occurred. Solution: – Check the load to ensure it is proper, increase the detection time. – Check whether control parameters are set properly. |
| STo Maladjustment fault | Cause: – Control parameters of synchronous motor is set improperly; – The parameter gained from autotuning is inaccurate; – The VFD is not connected to motor Solution: – Check the load to ensure it is proper, – Check whether load is proper; – Check whether control parameters are set correctly; – Increase maladjustment detection time |
| LL Electronic underload fault | Cause: The VFD will report the underload pre-alarm according to the set value. Solution: 1. Check the load and the underload pre-alarm point. |
| tSF Hydraulic probe damage | Cause: Hydraulic probe damage. Solution: Replace the hydraulic probe. |
| PINV PV reverse connection fault | Cause: PV wiring is incorrect. Solution: Change the wiring direction of positive and negative terminals, and perform the wiring again. |
| PVOC PV overcurrent | Cause: – ACC or DEC is too fast. – The power of the inverter is too low. – The load transients or is abnormal. – There is to-ground short circuit. Solution: – Increase the ACC/DCC time. – Select the inverter with larger power. – Check if the load is short circuited (to-ground short circuit or line-to-line short circuit) or the rotation is not smooth. |
| PVOV PV overvoltage | Cause: – The solar cell panel input voltage is too high. – Model -4 is set as another model. Solution: – Reduce the number of solarcell panels in series connection. – Check and reset the model. |
| PVLV PV undervoltage | Cause: – The power of the solar cell panels in series connection is too low or it is cloudy and rainy weather. – The starting current of the motor is too high. Solution: – Increase the number of solar cell panels or perform the test in the normal sunlight. – Replace the motor. |
| E-422 Fault on 422 communication with the boost module | Cause: Communication cables are in poor contact. Solution: – Check four communication cables of 422 communication, ensuring that they are connected reliably |
| OV Bus overvoltage detected on the boost side | Cause: The sunlight changes sharply. Solution: – Adjust the boost PI parameters, and enlarge the values of P19.07 and P19.08. |
| A-LS Weak-light pre-alarm | Cause: The sunlight is weak or the solar panel configuration is insufficient. Solution: – The device will automatically run when the light is sufficient. – Check whether the solar panel configuration is sufficient. |
| A-LL Underload pre-alarm | Cause: The pumping pool has no water. Solution: – Check the pumping pool. |
| A-tF Full-water pre-alarm | Cause: The pumping pool is full. Solution: – If you have configured the full-water pre-alarm function, the device automatically stops when the pre-alarm elapsed a period of time. Otherwise, check whether terminals are wired correctly. |
| A-tL Empty-water pre-alarm | Cause: The pumping pool has no water. Solution: – If you have configured the empty-water pre-alarm function, the device automatically stops when the pre-alarm elapsed a period of time. Otherwise, check whether terminals are wired correctly. |