INVT GD350-UL Series Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUt1 VFD unit Phase-U protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit. Remedy:
|
| OUt2 VFD unit Phase-V protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit. Remedy:
|
| OUt3 VFD unit Phase-W protection | Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit. Remedy:
|
| OV1 Over-voltage during acceleration | Cause: Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled. Remedy:
|
| OV2 Over-voltage during deceleration | Cause: Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled. Remedy:
|
| OV3 Over-voltage during constant speed running | Cause: Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled. Remedy:
|
| OC1 Over-current during acceleration | Cause: Acceleration is too fast; Grid voltage is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference sources; Overvoltage stall protection is not enabled. Remedy:
|
| OC2 Over-current during deceleration | Cause: See OC1 causes (Accel too fast, Grid low, VFD power small, Load transient, Short circuit, Interference). Remedy:
|
| OC3 Over-current during constant speed running | Cause: See OC1 causes (Grid low, VFD power small, Load transient, Short circuit, Interference, Stall protection). Remedy:
|
| UV Bus undervoltage fault | Cause: Grid voltage is too low; Overvoltage stall protection is not enabled. Remedy:
|
| OL1 Motor overload | Cause: Grid voltage is too low; Rated motor current is set improperly; Motor stall or load jumps violently. Remedy:
|
| OL2 VFD overload | Cause: Acceleration is too fast; The motor in rotating is restarted; Grid voltage is too low; Load is too large; Power is too small. Remedy:
|
| SPI Phase loss on input side | Cause: Phase loss or violent fluctuation occurred to R, S and T input. Remedy:
|
| SPO Phase loss on output side | Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical). Remedy:
|
| OH1 Overheat of rectifier module | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running. Remedy:
|
| OH2 Overheat of VFD module | Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running. Remedy:
|
| EF External fault | Cause: SI external fault input terminal acts. Remedy:
|
| CE 485 communication fault | Cause: Baud rate is set improperly; Communication line fault; Communication address error; Communication suffers from strong interference. Remedy:
|
| ItE Current detection fault | Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit. Remedy:
|
| tE Motor autotuning fault | Cause: Motor capacity does not match with the VFD capacity (diff exceeds 5 power classes); Motor parameter is set improperly; The parameters gained from autotuning deviate sharply from standard; Autotuning timeout. Remedy:
|
| EEP EEPROM fault | Cause: R/W error occurred to the control parameters; EEPROM is damaged. Remedy:
|
| PIDE PID feedback offline fault | Cause: PID feedback offline; PID feedback source disappears. Remedy:
|
| bCE Brake unit fault | Cause: Brake circuit fault or brake tube is damaged; The resistance of external brake resistor is too small. Remedy:
|
| END Running time is up | Cause: The actual running time of the VFD is larger than the set running time. Remedy:
|
| OL3 Electronic overload fault | Cause: The VFD releases overload pre-alarm based on the set value. Remedy:
|
| PCE Keypad communication fault | Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board. Remedy:
|
| UPE Parameter upload error | Cause: The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad. Remedy:
|
| DNE Parameter download error | Cause: The keypad wire is poorly contacted/disconnected; The keypad wire is too long/suffers interference; Data storage error occurred to the keypad. Remedy:
|
| ETH1 To-ground short circuit fault 1 | Cause: VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setting deviates sharply from the VFD power. Remedy:
|
| ETH2 To-ground short circuit fault 2 | Cause: VFD output is short connected to ground; Current detection circuit is faulty; Actual motor power setting deviates sharply from the VFD power. Remedy:
|
| dEu Speed deviation fault | Cause: Load is too heavy, or stall occurred. Remedy:
|
| STo Maladjustment fault | Cause: Control parameters of synchronous motor is set improperly; The parameter gained from autotuning is inaccurate; The VFD is not connected to motor. Remedy:
|
| LL Electronic underload fault | Cause: The VFD performs underload pre-alarm based on the set value. Remedy:
|
| ENC1O Encoder offline fault | Cause: Encoder line sequence is wrong, or signal wires are poorly connected. Remedy:
|
| ENC1D Encoder reversal fault | Cause: The encoder speed signal is contrary to the motor running direction. Remedy:
|
| ENC1Z Encoder Z pulse offline fault | Cause: Z signal wires are disconnected. Remedy:
|
| OT Motor over-temperature | Cause: Motor over-temperature input terminal is valid. Remedy:
|
| STO Safe torque off | Cause: Safe torque off function is enabled by external forces. Remedy:
|
| STL1 Exception occurred to safe circuit of channel H1 | Cause:
Remedy:
|
| STL2 Exception occurred to channel H2 safe circuit | Cause:
Remedy:
|
| STL3 Exception occurred to channel H1 and channel H2 | Cause: Hardware fault occurred to STO circuit. Remedy:
|
| CrCE Safety code FLASH CRC check fault | Cause: Control board is faulty. Remedy:
|
| E-Err Repetitive extension card type | Cause: The two inserted extension cards are of the same type. Remedy:
|
| ENCUV Encoder UVW loss fault | Cause: No electric level variation occurred to UVW signal. Remedy:
|
| F1-Er Failed to identify the extension card in card slot 1 | Cause: There is data transmission in interfaces of card slot 1, however, it cannot read the card type. Remedy:
|
| F2-Er Failed to identify the extension card in card slot 2 | Cause: There is data transmission in interfaces of card slot 2, however, it cannot read the card type. Remedy:
|
| F3-Er Failed to identify the extension card in card slot 3 | Cause: There is data transmission in interfaces of card slot 3, however, it cannot read the card type. Remedy:
|
| C1-Er Communication timeout occurred to the extension card in card slot 1 | Cause: There is no data transmission in interfaces of card slot 1. Remedy:
|
| C2-Er Communication timeout occurred to the extension card in card slot 2 | Cause: There is no data transmission in interfaces of card slot 2. Remedy:
|
| C3-Er Communication timeout occurred to the extension card in card slot 3 | Cause: There is no data transmission in interfaces of card slot 3. Remedy:
|
| E-DP Profibus card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| E-NET Ethernet card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer. Remedy:
|
| E-CAN CANopen card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| E-PN PROFINET card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| E-CAT EtherCAT card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| E-BAC BACNet card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| E-DEV DeviceNET card communication timeout fault | Cause: There is no data transmission between the communication card and the host computer (or PLC). Remedy:
|
| ESCAN Can master/slave communication card communication timeout fault | Cause: There is no data transmission between the CAN master and slave communication cards. Remedy:
|
| S-Err Master-slave synchronous CAN slave fault | Cause: Fault occurred to one of the CAN slave VFDs. Remedy:
|
| PoFF System power failure | Cause: The system is powered off or the bus voltage is too low. Remedy:
|