OUTPUT
Output transistor fault: Output current exceeded 200% of drive rating |
Cause:
- Phase to ground short.
- Phase to phase short.
- FX BOOST set too high.
- Bad transistor module (IPM).
Remedy:
- Check motor and cabling for shorts.
- Check drive rating against application.
|
LO VOLTS
Low DC Bus Voltage fault: DC bus voltage below 60% of normal. |
Cause:
Remedy:
- Check incoming AC power supply.
|
HI VOLTS
High DC Bus Voltage fault: DC bus voltage above 120% of normal. |
Cause:
- High line voltage.
- Overhauling load.
- DECEL rate is set too fast.
Remedy:
- Check incoming AC line voltage.
- Increase deceleration time.
- Install dynamic braking resistor if necessary.
|
HI TEMP
Temperature fault: Internal drive temperature too high. |
Cause:
- Ambient temperature too high.
- Fan failure (if equipped).
Remedy:
- Check cabinet ventilation and ambient temperature.
- Inspect cooling fans.
|
OVERLOAD
Current Overload fault: Output current rating exceeded for too long. |
Cause:
- Drive undersized for the application.
- Problem with motor and/or driven equipment.
Remedy:
- Check motor sizing.
- Check for mechanical binding or load issues.
- Wait 3 minutes for cool down (UL508C requirement).
|
PWR TRAN
Power Transient fault: Low line voltage. |
Cause:
- AC line dipped or sagged.
Remedy:
- Check AC power supply stability.
|
PWR SAG
Power Sag fault: Control board voltage is below tolerance. |
Cause:
- Erratic AC line.
- A new control board has been installed that is different from the previous version.
Remedy:
- Perform a factory reset using Parameter 65-PROGRAM. (This will update the software and allow the fault to be reset).
|
LANGUAGE
Language fault: Selected language not present. |
Cause:
- Defective language EEPROM.
- Language EEPROM (U11) removed after programming.
Remedy:
- Check EEPROM installation.
|
EXTERNAL
External fault: TB-13D is open or closed to TB-2, depending on setting of Parameter 50 – TB13D. |
Cause:
- External device triggered.
- Wiring issue on terminal inputs.
Remedy:
- Check setting of Parameter 50.
- Check devices wired between TB13D and TB-2.
|
DB ERROR
Dynamic Brake fault: DB circuit has sensed a resistor overload. |
Cause:
- The DB duty cycle is too high, causing the resistors to overheat.
Remedy:
- Reduce braking requirements or cycle time.
- Check resistor sizing.
|
CONTROL
Control Board fault: New software has been installed that is different from the previous version. |
Cause:
- Software version mismatch.
Remedy:
- Perform a factory reset using Parameter 65-PROGRAM.
- This will update the software and allow the fault to be reset.
|
INTERNAL / INTERN (#)
Internal fault: The micro-processor has sensed a problem. |
Cause:
- Electrical noise on control wiring.
- Defective microprocessor.
Remedy:
- Check control wiring shielding and grounding.
- Cycle power.
|
FOLLOWER
Loss of Follower fault: 4-20 mA signal at TB-5B is below 2 mA. |
Cause:
- Parameter 55 – TB5B LOSS is set to FAULT.
- Signal wire break or source failure.
Remedy:
- Check signal wiring at TB-5B.
- Check source signal generator.
|
Blank Display or repeatedly flashes TESTING
The power supply has shut down. |
Cause:
- This can be the result of clogged or failed heatsink fans.
Remedy:
- Check heatsink fans (if equipped).
- Clear any obstructions.
- If heatsinks are not clogged, contact the Lenze AC Tech Service Department.
|