Lenze SCF Drive

Fault Code and MeaningCause and Remedy
AF
High Temperature Fault

Cause: Ambient temperature is too high; Cooling fan has failed (if equipped).



Remedy: Check installation environment and cooling fans.
CF
Control Fault

Cause: A blank EPM, or an EPM with corrupted data has been installed.



Remedy: Perform a factory reset using Parameter 48 – PROGRAM SELECTION.
cF
Incompatibility Fault

Cause: An EPM with an incompatible parameter version has been installed.



Remedy: Either exchange the EPM, or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive.
dF
Dynamic Braking Fault

Cause: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors.



Remedy: Allow resistors to cool. Check sizing of braking resistors or duty cycle.
EF
External Fault

Cause: TB-13A and/or TB-13C is set as an External Fault input and TB-13A and/or TB-13C is open with respect to TB-2.



Remedy: Refer to Parameter 10 or 12. Check external wiring.
GF
Data Fault

Cause: User data and OEM defaults in the EPM are corrupted.



Remedy: Perform a factory reset or replace EPM.
HF
High DC Bus Voltage Fault

Cause: Line voltage is too high; Deceleration rate is too fast; Overhauling load.



Remedy: Check line voltage. For fast deceleration or overhauling loads, dynamic braking may be required.
JF
Serial Fault

Cause: The watchdog timer has timed out, indicating that the serial link has been lost.



Remedy: Check serial communication wiring and master controller.
LF
Low DC Bus Voltage Fault

Cause: Line voltage is too low.



Remedy: Check input power source and fuses. (Fault clears when voltage returns to normal).
OF
Output Transistor Fault

Cause: Phase to phase or phase to ground short circuit on the output; Failed output transistor; Boost settings are too high; Acceleration rate is too fast.



Remedy: Check motor wiring and insulation. Check boost settings (P11) and acceleration time (P01).
PF
Current Overload Fault

Cause: VFD is undersized for the application; Mechanical problem with the driven equipment.



Remedy: Check drive sizing vs motor load. Inspect driven machinery for jams or friction.
SF
Single-phase Fault

Cause: Single-phase input power has been applied to a three-phase drive.



Remedy: Check input power connections. Ensure three-phase power is applied.
UF
Start Fault

Cause: Start command was present when the drive was powered up.



Remedy: Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL.
F1
EPM Fault

Cause: The EPM is missing or damaged.



Remedy: Install or replace the EPM.
F2 – F9, Fo
Internal Faults

Cause: The control board has sensed a problem.



Remedy: Consult factory.
br
DC BRAKING

Cause: The DC braking circuit is activated.



Remedy: Status message only. Normal operation during DC injection braking.
cE
Configuration Error

Cause: An EPM from a drive with a previous parameter version is installed into a new drive, and an attempt is made to change any parameter settings.



Remedy: The parameters cannot be changed until the Translate function is performed (parameter 48, setting 06).
CL
CURRENT LIMIT

Cause: The output current has exceeded the CURRENT LIMIT setting (Parameter P25) and the drive is reducing the output frequency to reduce the output current.



Remedy: Reduce load. If the drive remains in CURRENT LIMIT for too long, it can trip into a CURRENT OVERLOAD fault (PF).
Er
ERROR

Cause: Invalid data has been entered or an invalid command was attempted.



Remedy: Check range of parameter being entered or command sequence.
GE
OEM Settings Error

Cause: Attempt made to change the OEM default settings when the drive is operating in the OEM mode (see Parameter 48).



Remedy: Disable OEM mode if changes are required.
GF
OEM Data Corruption

Cause: OEM defaults in the EPM are corrupted (displayed when RESET OEM is attempted or upon power-up).



Remedy: Refer to Section 13.1 (Manual Reset/Troubleshooting).
LC
FAULT LOCKOUT

Cause: The drive has failed three restart attempts.



Remedy: Requires a manual reset (STOP command).
SE
SERIAL

Cause: The optional remote keypad is active as the user interface instead of the buttons on the front of the drive.



Remedy: See Parameter 14 – CONTROL to change control source.
SP
START PENDING

Cause: “SP” blinks during the interval between restart attempts.



Remedy: Wait for restart timer to complete.
(Symbol)
DECEL OVERRIDE

Cause: The drive has stopped decelerating to avoid tripping into an HF fault due to regenerative energy from the motor.



Remedy: Drive will resume deceleration once DC bus voltage drops.