Lenze SCM Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| AF High Temp. Fault | Cause: Ambient temperature is too high; Cooling fan has failed (if equipped). Remedy:
|
| CF Control Fault | Cause: A blank EPM, or an EPM with corrupted data has been installed. Remedy:
|
| cF Incompatibility Fault | Cause: An EPM with an incompatible parameter version has been installed. Remedy:
|
| dF Dynamic Braking Fault | Cause: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors. Remedy:
|
| EF External Fault | Cause: One of the TB-13 terminals is set as an External Fault input and that terminal is open with respect to TB-11. Remedy:
|
| GF Data Fault | Cause: User data and OEM defaults in the EPM are corrupted. Remedy:
|
| HF High DC Bus Voltage Fault | Cause: Line voltage is too high; Deceleration rate is too fast; Over-hauling load. Remedy:
|
| JF Remote Keypad Fault | Cause: The communication link between the drive and the optional Remote Keypad has been lost. Remedy:
|
| LF Low DC Bus Voltage Fault | Cause: Line voltage is too low. Remedy:
|
| OF Output Transistor Fault | Cause: Phase to phase or phase to ground short circuit on the output; Boost settings are too high; Acceleration rate is too fast; Failed output transistor. Remedy:
|
| PF Current Overload Fault | Cause: VFD is undersized for the application; Mechanical problem with the driven equipment. Remedy:
|
| UF Start Fault | Cause: Start command was present when the drive was powered up. Remedy:
|
| F1 EPM Fault | Cause: The EPM is missing or damaged. Remedy:
|
| FC, F2-F9, Fo Internal Faults | Cause: The control board has sensed a problem. Remedy:
|
| br DC Braking | Cause: The DC braking circuit is activated. Remedy:
|
| cE Parameter Version Warning | Cause: An EPM with a different parameter version is installed and an attempt is made to change parameter settings without performing the TRANSLATE function. Remedy:
|
| CL Current Limit | Cause: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing output frequency. Remedy:
|
| Er Error | Cause: Invalid data has been entered or an invalid command was attempted. Remedy:
|
| GE OEM Mode Warning | Cause: Attempt made to change OEM default settings when the drive is operating in the OEM mode. Remedy:
|
| GF OEM Data Corruption | Cause: If displayed when RESET OEM attempted: OEM defaults in EPM corrupted. If displayed upon power-up: OEM defaults and user settings in EPM corrupted. Remedy:
|
| LC Fault Lockout | Cause: The drive has failed three restart attempts. Remedy:
|
| SE Serial Active | Cause: The optional remote keypad is active as the user interface instead of the buttons on front of the drive. Remedy:
|
| SP Start Pending | Cause: Blinks during the interval between restart attempts. Remedy:
|
| (Blinking Decimals) Decel Override | Cause: Both upper decimal points blinking. Drive stopped decelerating to avoid tripping into HF fault due to regenerative energy. Remedy:
|
| CP Control Pad | Cause: Speed is set using the up and down buttons on the front of the drive. Remedy:
|
| EI External Current | Cause: Speed is controlled by a 4-20 mA signal wired to TB-25 and TB-2. Remedy:
|
| EU External Voltage | Cause: Speed is controlled by a 0-10 VDC signal wired to TB-5 and TB-2. Remedy:
|
| JG Jog Mode | Cause: The drive is in Jog mode, and the speed is set by Preset Speed #2 (Parameter 32). Remedy:
|
| OP MOP (Motor Operated Pot) | Cause: Contacts wired to TB-13B and TB-13E are used to increase and decrease the drive speed. Remedy:
|
| Pr1 – Pr7 Preset Speeds | Cause: Speed is set by the indicated Preset Speed (Parameters 31-37). Remedy:
|