Mitsubishi FR-F800 Drive

Search from below list for FR-F800 drive faults & alarms:

Fault CodeCause & Solution
HOLD
Operation
panel lock
Cause: Operation lock mode is set. Operation other than STOP/RESET is invalid.

Solution:

– Press MODE for 2s to release lock.
LOCD
Password
locked
Cause: Password function is active. Display and setting of parameter is restricted.

Solution:

– Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.
Er1
Write
disable
error
Cause:

– You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to disable parameter write.
– Frequency jump setting range overlapped.
– Adjustable 5 points V/F settings overlapped
– The PU and inverter cannot make normal communication

Solution:

– Check the setting of Pr. 77 Parameter write selection
– Check the settings of Pr. 31 to 36 (frequency jump).
– Check the settings of Pr. 100 to Pr. 109 (adjustable 5 points V/F).
– Check the connection of the PU and inverter.
Er2
Write error
during
operation
Cause: Parameter write was attempted while Pr.77 Parameter write selection = “0”.

Check point:

– Check the Pr. 77 setting.
– Check that the inverter is not operating.

Solution:

– Set “2” in Pr. 77.
– After stopping operation, make parameter setting.
Er3
Calibration
error
Cause: Analog input bias and gain calibration values are too close.

Check point:

– Check the settings of C3, C4, C6 and C7 (calibration functions).
Er4
Mode
designation
error
Cause:

– Parameter setting was attempted in the External or NET operation mode while Pr. 77 = “1”.
– Parameter write was attempted when the command source is not at the operation panel (FR-DU08).

Check point:

– Check that operation mode is “PU operation mode”.
– Check the Pr. 77 setting.
– Check the Pr. 551 setting.

Solution:

– After setting the operation mode to the “PU operation mode”, make parameter setting.
– After setting Pr. 77 = “2”, make parameter setting.
– Set Pr.551 = “2 (initial value)”.
Er8
USB memory
device
operation
error
Cause:

– An operation command was given during the USB memory device operation.
– A copy operation (writing) was performed while the PLC function was in the RUN state.
– A copy operation was attempted for a password locked project.

Check point:

– Check if the USB memory device is operating.
– Check if the PLC function is in the RUN state.
– Check if the project data is locked with a password.

Solution:

– Perform the operation after the USB memory device operation is completed.
– Stop the PLC function.
– Unlock the password of the project data using FR Configurator2.
rE1
Parameter
read error
Cause:

– A failure has occurred at the operation panel side EEPROM while reading the copied parameters.
– A failure has occurred in the USB memory device while copying the parameters or reading the PLC function project data.

Solution:

– Perform parameter copy again.
– Perform PLC function project data copy again.
– The USB memory device may be faulty. Replace the USB memory device.
– The operation panel (FR-DU08) may be faulty.
rE2
Parameter
write error
Cause:

– Parameter copy from the operation panel to the inverter was attempted during operation.
– A failure has occurred at the operation panel side EEPROM while writing the copied parameters.
– A failure has occurred in the USB memory device while writing the copied parameters or PLC function project data.

Check point:

– Check that the inverter is stopped.

Solution:

– After stopping the operation, perform parameter copy again.
– The operation panel (FR-DU08) may be faulty.
– Perform parameter copy or PLC project data copy again.
– The USB memory device may be faulty. Replace the USB memory device.
rE3
Parameter
verification
error
Cause:

– The data in the inverter are different from the data in the operation panel.
– A failure has occurred at the operation panel side EEPROM during parameter verification.
– A failure has occurred in the USB memory device during parameter verification.
– The data in the inverter are different from the data in the USB memory device or the personal computer (FR Configurator2).

Check point:

– Check the parameter setting of the source inverter against the setting of the destination inverter.

Solution:

– Continue the verification by SET button pressing .
– Perform parameter verification again.
– The operation panel (FR-DU08) may be faulty.
– The USB memory device may be faulty. Replace the USB memory device.
– Verify the PLC function project data again.
rE4
Model error
Cause:

– The series of the source inverter used to copy or verify parameters is not the same as the target inverter.
– The operation panel data was incorrect when attempting to verify parameters or copy parameters from the operation panel to the inverter.

Check point:

– Check that the source inverter being used to verify or copy parameters is the same series as the target inverter.
– Check that the copying of parameters was not interrupted due to a loss of power to the inverter or the operation panel being disconnected.

Solution:

– Use the same model (FR-F800 series) for parameter copy and verification.
– Perform parameter copy read again.
rE6
File error
Cause:

– The parameter copy file in the USB memory device cannot be recognized.
– An error has occurred in the file system during transfer of the PLC function data or writing to RAM.

Solution:

– Perform parameter copy again.
– Copy the PLC function project data again.
rE7
File
quantity
error
Cause: A parameter copy was attempted to the USB memory device in which the copy files from 001 to 099 had already been saved.

Check point:

– Check if the number of copy files in the USB memory device has reached 99.

Solution:

– Delete the copy file in the USB memory device and perform parameter copy again.
rE8
No PLC
function
project file
Cause: The specified PLC function project file does not exist in the USB memory device.

Check point:

– Check that the file exists in the USB memory device.
– Check that the folder name and the file name in the USB memory device is correct.

Solution:

– The data in the USB memory device may be damaged.
Err.Cause:

– The RES signal is on
– The PU and inverter cannot make normal communication (contact fault of the connector)
– When the voltage drops in the inverter’s input side.
– When the control circuit power (R1/L11, S1/L21) and the main circuit power (R/L1, S/L2, T/L3) are connected to a separate power, it may appear at turning ON of the main circuit. It is not a fault.

Solution:

– Turn OFF the RES signal.
– Check the connection of the PU and inverter.
– Check the voltage on the inverter’s input side.
OL
Stall
prevention
(overcurrent)
Cause:

– During acceleration: When the output current of the inverter exceeds the stall prevention level (Pr. 22 “Stall prevention operation level”, etc.), this function stops the increase in frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has reduced below stall prevention operation level, this function increases the frequency again.

– During constant-speed operation: When the output current of the inverter exceeds the stall prevention level (Pr. 22 “Stall prevention operation level”, etc.), this function reduces frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has reduced below stall prevention operation level, this function increases the frequency up to the set value.

– During deceleration: When the output current of the inverter exceeds the stall prevention level (Pr. 22 “Stall prevention operation level”, etc.), this function stops the decrease in frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has decreased below stall prevention operation level, this function decreases the frequency again.

Check point:

– Check that the Pr. 0 Torque boost setting is not too large.
– Check that the Pr. 7 Acceleration time and Pr. 8 Deceleration time settings are not too small.
– Check that the load is not too heavy.
– Are there any failure in peripheral devices?
– Check that the Pr. 13 Starting frequency is not too large.
– Check the motor for use under overload.
– Check that Pr. 22 Stall prevention operation level is appropriate.

Solution:

– Gradually increase or decrease the Pr. 0 setting by 1% at a time and check the motor status.(Refer to page 5-515.)
– Set a larger value in Pr. 7 “Acceleration time” and Pr. 8 “Deceleration time”.
– Reduce the load.
– Try Advanced magnetic flux vector control.
– Change the Pr. 14 “Load pattern selection” setting.
– The stall prevention operation current can be set in Pr. 22 “Stall prevention operation level”. The acceleration/deceleration time may change. Increase the stall prevention operation level with Pr. 22 “Stall prevention operation level”, or disable stall prevention with Pr. 156 “Stall prevention operation selection”. (Use Pr. 156 to set either operation continued or not at OL operation.)
oL
Stall
prevention
(overvoltage)
Cause:

During deceleration:
– If the regenerative energy of the motor becomes excessive and exceeds the regenerative energy consumption capability, this function stops the decrease in frequency to prevent overvoltage trip. As soon as the regenerative energy has decreased, deceleration resumes.
– If the regenerative energy of the motor becomes excessive when regeneration avoidance function is selected (Pr. 882 = 1), this function increases the speed to prevent overvoltage trip.

Check point:

– Check for sudden speed reduction.
– Regeneration avoidance function (Pr. 882 to Pr. 886) is being used?

Solution:

– The deceleration time may change. Increase the deceleration time using Pr. 8 Deceleration time.
TH
Electronic
thermal relay
function
pre-alarm
Cause: Appears if the cumulative value of the electronic thermal O/L relay reaches or exceeds 85% of the preset level of Pr. 9 “Electronic thermal O/L relay”. If the value reaches 100% of Pr. 9 setting, motor overload trip (E.THM) occurs.

Check point:

– Check for large load or sudden acceleration.
– Is the Pr. 9 Electronic thermal O/L relay setting is appropriate?

Solution:

– Reduce the load weight or the number of operation times.
– Set an appropriate value in Pr. 9 Electronic thermal O/L relay.
PS/P5
PU stop
Cause: The motor is stopped using STOP/RESET key under the mode other than the PU operation mode. (To enable STOP/RESET key under the mode other than the PU operation mode, set Pr. 75 “Reset selection/disconnected PU detection/PU stop selection”.

Check point:

– Check for a stop made by pressing STOP/RESET button of the operation panel.

Solution:

– Turn the start signal OFF and release with PU/EXT button.
CP
Parameter
copy
Cause: Appears when parameter copy is performed between inverters FR-F820-02330(55K) or lower, FR- F840-01160(55K) or lower, FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.

Check point:

– Resetting of Pr. 9, Pr. 30, Pr. 51, Pr. 56, Pr. 57, Pr. 72, Pr. 80, Pr. 82, Pr. 90 to Pr. 94, Pr. 453, Pr. 455, Pr. 458 to Pr. 462, Pr. 557, Pr. 859, Pr. 860 and Pr. 893 is necessary.

Solution:

– Set the initial value in Pr.989 Parameter copy alarm release.
SA
Safety
stop
Cause: Appears when safety stop function is activated (during output shutoff). (Refer to page 83.)

Check point:

– Check if an emergency stop device is activated.
– Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not using the safety stop function.

Solution:

– An emergency stop device is active when using the safety stop function. Identify the cause of emergency stop, ensure the safety and restart the system.
– When not using the safety stop function, short across terminals S1 and PC and across S2 and PC with shorting wire for the inverter to run.
– If “SA” is indicated when wires across S1 and SIC and across S2 and SIC are both conducted while using the safety stop function (drive enabled), internal failure might be the cause. Check the wiring of terminals S1, S2, and SIC and contact your sales representative if the wiring has no fault.
MT1 to MT3
Maintenance
signal output
Cause: Appears when the inverter’s cumulative energization time reaches or exceeds the parameter set value. Set the time until the MT is displayed using Pr. 504 “Maintenance timer 1 warning output set time” (MT1), Pr. 687 “Maintenance timer 2 warning output set time” (MT2), and Pr. 689 “Maintenance timer 3 warning output set time” (MT3).
– MT does not appear when the settings of Pr. 504, Pr. 687, and Pr. 689 are initial values (9999).

Check point:

– The set time of maintenance timer has been exceeded.

Solution:

– Take appropriate countermeasures according to the purpose of the maintenance timer setting. Setting “0” in Pr.503 Maintenance timer 1, Pr.686 Maintenance timer 2, and Pr.688 Maintenance timer 3 clears the indication.
UF
USB host
error
Cause: Appears when an excessive current flows into the USB A connector.

Check point:

– Check if a USB device other than a USB memory device is connected to the USB A connector.

Solution:

– If a device other than a USB memory device is connected to the USB A connector, remove the device.
– Setting Pr.1049 USB host reset = “1” or inverter reset clears the UF indication.
EV
24 V external
power supply
operation
Cause: Flickers when the main circuit power supply is off and the 24 V external power supply is being input.

Check point: 

– Power is supplied from a 24 V external power supply.

Solution:

– Turning ON the power supply (main circuit) of the inverter clears the indication.
– If the indication is still displayed after turning ON of the power supply (main circuit) of the inverter, the power supply voltage may be low, or the jumper between the terminals P/+ and P1 may be disconnected.
ED
Emergency
drive in
operation
Cause: Appears during emergency drive operation.

Check point:

– Emergency drive operation is performed by turning ON X84 signal.

Solution:

– The display is cleared when the emergency drive operation ends.
LDF
Load fault
warning
Cause: Appears when the load is deviated from the detection width set in Pr.1488 Upper limit warning detection width or Pr.1489 Lower limit warning detection width.

Check point:

– Check if too much load is applied to the equipment, or if the load is too light.
– Check that the load characteristics settings are correct.

Solution:

– Inspect the equipment.
– Set the load characteristics (Pr.1481 to Pr.1487) correctly.
FN
Fan alarm
Cause: For the inverter that contains a cooling fan, FN appears on the operation panel when the cooling fan stops due to a fault, low rotation speed, or different operation from the setting of Pr.244 Cooling fan operation selection.

Check point:

– When the cooling fan is replaced, check that the fan is not installed upside down.
– Check the cooling fan for a failure.

Solution:

– Check for fan fault. Install the fan correctly.
E.OC1
Overcurrent
trip during
acceleration
Cause: When the inverter output current reaches or exceeds approximately 170% (LD rating) / 148% (SLD rating) of the rated current during acceleration, the protection circuit is activated and the inverter trips.

Check point:

– Check for sudden speed acceleration.
– Check if the downward acceleration time is too long in a lift application.
– Check for output short-circuit.
– Check that the Pr.3 Base frequency setting is not 60 Hz when the motor rated frequency is 50 Hz.
– Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.
– Check that the regenerative driving is not performed frequently. (Check if the output voltage becomes larger than the V/F reference voltage at regenerative driving and overcurrent occurs due to increase in the motor current.)
– Check that the power supply for RS-485 terminal is not shorted (under Vector control).
– Check that the encoder wiring and the specifications (encoder power supply, resolution, differential/ complementary) are correct. Check also that the motor wiring (U, V, W) is correct (under Vector control).
– Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to forward) during torque control under Real sensorless vector control.
– Check that the inverter capacity matches with the motor capacity. (PM sensorless vector control)
– Check if a start command is given to the inverter while the motor is coasting. (PM sensorless vector control)
– Check the I/O terminal status (of terminals Y67, MRS, S1, and S2) with FR Configurator2 to check if the inverter has restarted the motor after output shutoff due to power failure, undervoltage, the MRS signal, or the safety stop function.

Solutions:

– Set the acceleration time longer. (Shorten the downward acceleration time of the lift.)
– If “E.OC1” always appears at start, disconnect the motor once and restart the inverter.
– Check the wiring to make sure that output short circuit does not occur.
– Set 50 Hz in Pr.3 Base frequency.
– Lower the stall prevention operation level. Activate the fast-response current limit operation.
– Set the base voltage (rated voltage of the motor, etc.) in Pr.19 Base frequency voltage.
– Check RS-485 terminal connection (under Vector control).
– Check the wiring and specifications of the encoder and the motor. Perform the setting according to the specifications of the encoder and the motor (under vector control).
– Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward) during torque control under Real sensorless vector control.
– Choose inverter and motor capacities that match. (PM sensorless vector control)
– Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power failure/flying start function.
– Remove the cause of output shutoff. (Check the power supply, and terminals MRS, S1, and S2.)
E.OC2
Overcurrent
trip during
constant speed
Cause: When the inverter output current reaches or exceeds approximately 170% (LD rating) / 148% (SLD rating) of the rated current during constant-speed operation, the protection circuit is activated and the inverter trips.

Check point:

– Check for sudden load change.
– Check for output short-circuit.
– Check if the stall prevention operation level is set too high. Check if the fast-response current limit operation is disabled.
– Check that the inverter capacity matches with the motor capacity. (PM motor control)
– Check if a start command is given to the inverter while the motor is coasting. (PM motor control)

Solutions:

– Keep the load stable.
– Check the wiring to make sure that output short circuit does not occur.
– Lower the stall prevention operation level. Activate the fast-response current limit operation.
– Choose inverter and motor capacities that match. (PM motor control)
– Input a start command after the motor stops. Alternatively, use the automatic restart after instantaneous power failure/flying start function.
E.OC3
Overcurrent
trip during
deceleration
or stop
Cause: When the inverter output current reaches or exceeds approximately 170% (LD rating) / 148% (SLD rating) of the rated current during deceleration (other than acceleration or constant speed), the protection circuit is activated and the inverter trips.

Check point:

– Check for sudden speed reduction.
– Check for output short-circuit.
– Check for too fast operation of the motor’s mechanical brake.
– Check if the stall prevention operation level is set too high. Check if the fast-responsecurrent limit operation is disabled.
– Check that the inverter capacity matches with the motor capacity.(PM motor control)
– Check if a start command is given to the inverter while the motor is coasting.(PM motor control)

Solutions:

– Set the deceleration time longer.
– Check the wiring to make sure that output short circuit does not occur.
– Check the mechanical brake operation.
– Lower the stall prevention operation level. Activate the fast-response current limitoperation.
– Choose inverter and motor capacities that match. (PM motor control)
– Input a start command after the motor stops. Alternatively, use the automatic restart afterinstantaneous power failure/flying start function.
E.OV1
Regenerative
overvoltage
trip during
acceleration
Cause: If regenerative energy causes the inverter’s internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.

Check point:

– Check for too slow acceleration. (e.g. during descending acceleration in vertical lift load)
– Check that the Pr. 22 Stall prevention operation level is not lower than the no load current.

Solution:

– Set the acceleration time shorter. Use the regeneration avoidance function
– Use the brake unit, multifunction regeneration converter (FR-XC), or power regeneration common converter (FR-CV) as required.
– Set a value larger than the no load current in Pr.22.
– Set Pr.154 Voltage reduction selection during stall prevention operation = “10 or 11”.
– Remove the cause of output shutoff. (Check the power supply, and terminals MRS, S1, and S2.)
E.OV2
Regenerative
overvoltage
trip during
constant speed
Cause: If regenerative energy causes the inverter’s internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.

Check point:

· Check for sudden load change.
· Check that the Pr. 22 Stall prevention operation level is not lower than the no load current.

Solution:

– Keep the load stable.
– Use the regeneration avoidance function (Pr.882 to Pr.886).
– Use the brake unit, multifunction regeneration converter (FR-XC), or power regeneration common converter (FR-CV) as required.
– Set a value larger than the no load current in Pr.22.
– Set Pr.154 Voltage reduction selection during stall prevention operation = “10 or 11”.
– Set the acceleration/deceleration time longer. (Under Vector control or Advanced magnetic flux vector control, the output torque can be increased. However, sudden acceleration may cause an overshoot in speed, resulting in an occurrence of overvoltage.)
E.OV3
Regenerative
overvoltage
trip during
deceleration
or stop
Cause: If regenerative energy causes the inverter’s internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.

Check point:

– Check for sudden speed reduction.

Solution:

– Set the deceleration time longer. (Set the deceleration time which matches the moment of inertia of the load.)
– Make the brake cycle longer.
– Use the regeneration avoidance function.
– Use the brake unit, multifunction regeneration converter (FR-XC), or power regeneration common converter (FR-CV) as required.
– Set Pr.154 Voltage reduction selection during stall prevention operation = “10 or 11”.
E.THT
Inverter
overload
trip
(electronic
thermal relay
function)
Cause: When the temperature of the output transistor element exceeds the protection level while a current flows at the rated output current level or higher without causing an overcurrent trip (E.OC), the inverter output is stopped. (Permissible overload capacity 120% 60 s)

Check point:

– Check that acceleration/deceleration time is not too short.
– Check that torque boost setting is not too large (small).
– Check that load pattern selection setting is appropriate for the load pattern of the using machine.
– Check the motor for use under overload.

Solutions:

– Increase acceleration/deceleration time.
– Adjust the torque boost setting.
– Set the load pattern selection setting according to the load pattern of the using machine.
– Reduce the load weight.
E.THM
Motor
overload
trip
Cause: The electronic thermal O/L relay function in the inverter detects motor overheat, which is caused by overload or reduced cooling during low-speed operation. When the cumulativeheat value reaches 85% of the Pr. 9 “Electronic thermal O/L relay” setting, pre-alarm (TH) is output. When the accumulated value reaches the specified value, the protection circuit isactivated to stop the inverter output.

Check point:

– Check the motor for use under overload.
– Check that the setting of Pr. 71 Applied motor for motor selection is correct.
– Check that stall prevention operation setting is correct.

Solution:

– Reduce the load weight.
– For a constant-torque motor, set the constant-torque motor in Pr. 71 Applied motor.
– Check that stall prevention operation setting is correct.
E.FIN
Heatsink
overheat
Cause: When the heat sink overheats, the temperature sensor is activated, and the inverter output is stopped.
– The FIN signal can be output when the temperature becomes approximately 85% of the heat sink overheat protection operation temperature.
– For the terminal used for the FIN signal output, assign the function by setting “26 (positive logic) or 126 (negative logic)” from Pr.190 to Pr.196 (Output terminal function selection).

Check point:

– Check for too high surrounding air temperature.
– Check for heatsink clogging.
– Check that the cooling fan is stopped. (Check that “Fn” is displayed on the operation panel.)

Solution:

– Set the surrounding air temperature to within the specifications.
– Clean the heatsink.
– Replace the cooling fan.
E.IPF
Instantaneous
power failure
Cause: If a power failure occurs for longer than 15ms (this also applies to inverter input shut-off), the instantaneous power failure protective function is activated to trip the inverter in order to prevent the control circuit from malfunctioning. If a power failure persists for longer than 100ms, the fault output is not provided, and the inverter restarts if the start signal is ON upon power restoration. (The inverter continues operating if an instantaneous power failure is within 15ms.) In some operating status (load magnitude, acceleration/deceleration time setting, etc.), overcurrent or other protection may be activated upon power restoration.
– When instantaneous power failure protection is activated, the IPF signal is output.

Check point:

– Find the cause of instantaneous power failure occurrence.

Solution:

– Remedy the instantaneous power failure.
– Prepare a backup power supply for instantaneous power failure.
– Set the function of automatic restart after instantaneous power failure (Pr. 57).
E.UVT
Undervoltage
Cause: If the power supply voltage of the inverter decreases, the control circuit will not perform normal functions. In addition, the motor torque will be insufficient and/or heat generation will increase. To prevent this, if the power supply voltage decreases below about 150VAC (300VAC for the 400V class), this function stops the inverter output.
– When a jumper is not connected across P/+ and P1, the undervoltage protective function is activated.
– When undervoltage protection is activated, the IPF signal is output.

Check point:

– Check for start of large-capacity motor.
– Check that a jumper or DC reactor is connected across terminals P/+ and P1.

Solution:

– Check the power supply system equipment such as the power supply.
– Connect a jumper or DC reactor across terminals P/+ and P1.
E.ILF
Input phase
loss
Cause: When Pr. 872 “Input phase loss protection selection” is enabled (“1”) and one of the three-phase power input is lost, the inverter output is shut off. This protective function is not available when Pr. 872 is set to the initial value (Pr. 872 = “0”).

Check point:

– Check for a break in the cable for the three-phase power supply input.

Solution:

– Wire the cables properly.
– Repair a break portion in the cable.
– Check the Pr. 872 Input phase loss protection selection setting.
E.OLT
Stall
prevention
stop
Cause:

V/F- If the output frequency has fallen to 0.5 Hz by stall prevention operation and remains for 3 s, a fault (E.OLT) appears and the inverter trips. OL appears while stall prevention is being activated.

PM- During speed control, a fault (E.OLT) appears and the inverter trips if the frequency value converted from the motor rotation speed drops to 1.5 Hz or lower by stall prevention operation and the output torque exceeds the Pr. 874 “OLT level setting” (refer to page 5-175) and remains there for 3 s.

Check point:

– Check the motor for the use under overload.
– Check that the Pr. 874 values are correct.
– Check the Pr. 22 “Stall prevention operation level” setting under V/F control and Advanced magnetic flux vector control.)
– Check if a motor is connected under PM motor control.

Solution:

– Reduce the load.
– Change the Pr. 22, and Pr. 874 values. (Check the Pr. 22 setting under V/F control and Advanced magnetic flux vector control.)
– For a test run without connecting a motor, select the PM motor control test operation.
– Also check that the stall prevention (overcurrent) warning (OL) or the stall prevention (overvoltage) warning (oL) countermeasure is taken.
E.SOT
Loss of
synchronism
detection
Cause: The inverter output is shut off when the motor operation is not synchronized. (This function is only available under PM sensorless vector control.)

Check point:

– Check that the PM motor is not driven overloaded.
– Check if a start command is given to the inverter while the PM motor is coasting.
– Check if a motor is connected under PM sensorless vector control.
– Check if a PM motor other than the MM-EFS/MM-THE4 series is driven.

Solution:

– Set the acceleration time longer.
– Reduce the load.
– If the inverter restarts during coasting, set Pr.57 Restart coasting time ≠ “9999”, and select the automatic restart after instantaneous power failure.
– Check the connection of the IPM motor.
– For the test operation without connecting a motor, select the PM sensorless vector control test operation.
– Drive a PM motor (EM-A or MM-CF).
– When driving an IPM motor other than MM-EFS/MM-THE4 series, offline auto tuning must be performed.
E.LUP
Upper limit
fault
detection
Cause: The inverter output is shut off when the load exceeds the upper limit fault detection range. This protective function is not available in the initial setting of Pr.1490 (Pr.1490 = “9999”).

Check point:

– Check if too much load is applied to the equipment.
– Check that the load characteristics settings are correct.

Solution:

– Inspect the equipment.
– Set the load characteristics (Pr.1481 to Pr.1487) correctly.
E.LDN
Lower limit
fault
detection
Cause: The inverter output is shut off when the load falls below the lower limit fault detection range. This protective function is not available in the initial setting of Pr.1491 (Pr.1491 = “9999”).

Check point:

– Check if the equipment load is too light.
– Check that the load characteristics settings are correct.

Solution:

– Inspect the equipment.
– Set the load characteristics (Pr.1481 to Pr.1487) correctly.
E.GF
Output
side earth
ground fault
Cause: Description This function stops the inverter output if an earth (ground) fault overcurrent flows due to an earth (ground) fault that occurred on the inverter’s output (load) side.
– The inverter output is shut off if an earth (ground) fault overcurrent flows due to an earth (ground) fault that occurred on the inverter’s output side (load side).

Check point:

– Check for an earth (ground) fault in the motor and connection cable.

Solution:

– Remedy the earth (ground) fault portion.
E.LF
Output
phase loss
Cause: This function stops the inverter output if one of the three phases (U, V, W) on the inverter’s output side (load side) is lost.

Check point:

– Check the wiring (Check that the motor is normal.)
– Check that the capacity of the motor used is not smaller than that of the inverter.

Solution:

– Wire the cables properly.
E.OHT
External
thermal relay
operation
Cause: If the external thermal relay provided for motor overheat protection, or the internally mounted temperature relay in the motor, etc. switches ON (contacts open), the inverter output is stopped. This function is available when “7” (OH signal) is set in any of Pr. 178 to Pr. 189 (input terminal function selection).
– When the initial value (without OH signal assigned) is set, this protective function is not available.

Check point:

– Check for motor overheating.
– Check that the value of 7 (OH signal) is set correctly in any of Pr. 178 to Pr. 189 (input terminal function selection).

Solution:

– Reduce the load and operating duty.
– Even if the relay contacts are reset automatically, the inverter will not restart unless it is reset.
E.PTC
PTC thermistor
operation
Cause: The inverter output is shut off if resistance of the PTC thermistor connected between terminal 2 and terminal 10 is equal to or higher than the Pr.561 PTC thermistor protection level setting for a continuous time equal to or longer than the setting value in Pr.1016 PTC thermistor protection detection time. When the initial value (Pr.561 = “9999”) is set, this protective function is not available.

Check point:

– Check the connection with the PTC thermistor.
– Check the Pr.561 and Pr.1016 settings.
– Check the motor for operation under overload.

Solution:

– Reduce the load weight.
E.OPT
Option fault
Cause:

– Appears when the AC power supply is connected to the terminal R/L1, S/L2, or T/L3 accidentally when a high power factor converter (FR-HC2) or power regeneration common converter (FR-CV) is connected (when Pr. 30 “Regenerative function selection” = “2”).
– Appears when the switch for manufacturer setting of the plug-in option is changed.
– Appears when a communication option is connected while Pr. 296 “Password lock level” = “0 or 100”.

Check point:

– Check that the AC power supply is not connected to the terminal R/L1, S/L2, or T/L3 when a high power factor converter (FR-HC2) or power regeneration common converter (FR-CV) is connected (when Pr. 30 = “2”).
– Check for the password lock with a setting of Pr. 296 = “0, 100”.

Solution:

– Check the Pr. 30 setting and wiring.
– The inverter may be damaged if the AC power supply is connected to the terminal R/L1, S/L2, or T/L3 when a high power factor converter is connected.
– Set the switch on the plug-in option, which is for manufacturer setting, back to the initial setting. (Refer to the Instruction Manual of each option.)
– To apply the password lock when installing a communication option, set Pr. 296 ≠ “0, 100”.
E.OP1
Communication
option fault
Cause: The inverter trips if a communication line error occurs in the communication option.

Check point:

– Check for an incorrect option function setting and operation.
– Check that the plug-in option is plugged into the connector properly.
– Check for a break in the communication cable.
– Check that the terminating resistor is fitted properly.

Solution:

– Check the option function setting, etc.
– Connect the plug-in option securely.
– Check the connection of communication cable.
E.16 to E.20
Fault 16 to
Fault 20
User
definition
error by the
PLC function
Cause: The protective function is activated by setting “16 to 20” in the special register SD1214 for the PLC function. The inverter trips when the protective function is activated. The protective function is activated when the PLC function is enabled. This protective function is not available in the initial setting (Pr. 414 = “0”). Any character string can be displayed on FR-LU08 or FR-PU07 by sequence programs.

Check point:

– Check if “16 to 20” is set in the special register SD1214.

Solution:

– Set a value other than “16 to 20” in the special register SD1214.
E.PE
Parameter
storage
device fault
(control
circuit
board)
Cause: The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)

Check point:

– Check for too many number of parameter write times.

Solution:

– Set “1” in Pr.342 Communication EEPROM write selection (write to RAM) for the operation which requires frequent parameter writing via communication, etc. Note that writing to RAM goes back to the initial status at power OFF.
E.PUE
PU
disconnection
Cause:

– The inverter output is shut off if communication between the inverter and PU is suspended, e.g. the operation panel or parameter unit is disconnected, when the disconnected PU disconnection function is valid in Pr.75 Reset selection/disconnected PU detection/PU stop selection.
– The inverter output is shut off if communication errors occurred consecutively for more than permissible number of retries when Pr.121 PU communication retry count ≠ “9999” during the RS-485 communication via the PU connector.
– The inverter output is shut off if communication is broken within the period of time set in Pr.122 PU communication check time interval during the RS-485 communication via the PU connector.

Check point:

– Check that the operation panel or the parameter unit is connected properly.
– Check the Pr.75 setting.

Solution:

– Fit the operation panel or the parameter unit securely.
E.RET
Retry count
excess
Cause: The inverter output is shut off if the operation cannot be resumed properly within the number of retries set in Pr.67 Number of retries at fault occurrence. This function is available when Pr.67 is set. This protective function is not available in the initial setting (Pr.67 = “0”).

Check point:

– Find the cause of alarm occurrence.

Solution:

– Eliminate the cause of the error preceding this error indication.
E.PE2
Parameter
storage
device fault
(main circuit
board)
Cause: The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure)

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
E. 5
Fault 5
E. 6 Fault 6
E. 7 Fault 7
E.CPU CPU
Fault
Cause: Stops the inverter output if the communication error of the built-in CPU occurs.

Check point:

– Check for devices producing excess electrical noises around the inverter.

Solution:

· Take measures against noises if there are devices producing excess electrical noises around the inverter.
· After this same fault comes then there is an hardware issue in drive. Need to repair or replace drive.
E.CTE
Operation
panel power
supply short
circuit
Cause: –

– When the power supply for the operation panel (PU connector) is shorted, the power output is shutoff and the inverter trips. The use of the operation panel (parameter unit) and the RS- 485 communication via the PU connector are disabled. To reset, enter the RES signal from the terminal, reset via communication through the RS-485 terminals, or switch power OFF then ON again.
– When the power supply for the RS-485 terminals are short circuited, this function shuts off the power output. At this time, communication from the RS-485 terminals cannot be made. To reset, use STOP/RESET key of the operation panel, enter the RES signal, or switch power OFF then ON again.

Check point:

– Check that the PU connector cable is not shorted.
– Check that the RS-485 terminals are connected correctly.

Solution:

– Check the PU and cable.
– Check the connection of the RS-485 terminals
E.P24
24VDC power
Fault
Cause: When the 24 VDC power output from the PC terminal is shorted, this function shuts off the power output. At this time, all external contact inputs switch OFF. The inverter cannot be reset by entering the RES signal. To reset it, use the operation panel, or switch power OFF, then ON again.

Check point:

– Check for a short circuit in the PC terminal output.

Solution:

– Repair the short-circuited portion.
E.CDO
Output current
detection value
exceeded
Cause: Trips the inverter when the output current exceeds the setting of Pr. 150 Output current detection level.
– This function is available when Pr. 167 Output current detection operation selection is set to “1”. When the initial value (Pr. 167 = “0”) is set, this protective function is not available.

Check point:

– Check the settings of Pr. 150 Output current detection level, Pr. 151 Output current detection signal delay time, Pr. 166 Output current detection signal retention time, Pr. 167 Output current detection operation selection.
E.IOH
Inrush current
limit circuit
fault
Cause: The inverter trips when the resistor of the inrush current limit circuit is overheated. The inrush current limit circuit failure

Check point:

– Check that frequent power ON/OFF is not repeated.
– Check if the input side fuse (5A) in the power supply circuit of the inrush current limit circuit contactor (FR-F840-03250(132K) or higher) is blown.
– Check that the power supply circuit of inrush current limit circuit contactor is not damaged.

Solution:

– Configure a circuit where frequent power ON/OFF is not repeated.
– If the problem still persists after taking the above measure then there is an hardware issue in drive. Need to repair or replace drive.
E.SER
Communication
fault
Cause: The inverter output is shut off when communication error occurs consecutively for the permissible number of retries or more when Pr.335 RS-485 communication retry count ≠ “9999” during RS-485 communication through the RS-485 terminals. The inverter output is also shut off if communication is broken for the period of time set in Pr.336 RS-485 communication check time interval.

Check point:

– Check the RS-485 terminal wiring.

Solution:

– Perform wiring of the RS-485 terminals properly.
E.AIE
Analog
input fault
Cause: Stops the inverter output when a 30mA or higher current or a 7.5V or higher voltage is input to terminal 2 while the current input is selected by Pr. 73 Analog input selection, or to terminal 4 while the current input is selected by Pr. 267 Terminal 4 input selection.

Check point:

– Check the Pr.73, Pr.267, and the voltage/current input switch settings

Solution:

– Either give a current less than 30 mA, or set Pr.73, Pr.267, and the voltage/current input switch to the voltage input and input a voltage.
E.USB
USB
communication
fault
Cause: The inverter output is shut off when the communication is cut off for the time set in Pr.548 USB communication check time interval.

Check point:

– Check the USB communication cable.

Solution:

– Check the Pr. 548 USB communication check time interval setting.
– Check the USB communication cable.
– Increase the Pr. 548 USB communication check time interval setting. Or, change the setting to 9999.
E.SAF
Safety
circuit fault
Cause:

– The inverter trips when a safety circuit fault occurs.
– The inverter trips if the either of the wire between S1 and SIC or S2 and SIC becomes non- conductive while using the safety stop function.
– When not using the safety stop function, the inverter trips when the shorting wire between terminals S1 and PC or across S2 and PC is disconnected.

Check point:

– Check that the safety relay module or the connection has no fault when using the safety stop function.
– Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when not using the safety stop function.

Solution:

– When using the safety stop function, check that wiring of terminal S1, S2 and SIC is correct and the safety stop input signal source such as a safety relay module is operating properly.
– When not using the safety stop function, short across terminals S1 and PC and across S2 and PC with shorting wires.
E.PBT
E.13
Internal
circuit fault
Cause: The inverter output is shut off when an internal circuit fault occurs.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
E.BE
Brake
transistor
error
Cause: The inverter output is shut off when an internal circuit fault occurs.

Solution: There is an hardware or software issue in drive. Need to repair or replace drive.
E.OS
Overspeed
occurrence
Cause: The inverter trips when the motor speed exceeds the Pr. 374 “Overspeed detection level” under PM motor control. This protective function is not available in the initial status.

Check point:

– Check that the Pr. 374 setting is correct.

Solution:

– Set the Pr. 374 correctly.
E.LCI
4 mA input
fault
Cause: The inverter trips when the analog input current is 2 mA or less for the time set in Pr. 778 “4 mA input check filter”. This function is available when Pr. 573 “4 mA input check selection” = “2 or 3”. This function is not available in the initial status.

Check point:

– Check for a break in the wiring for the analog current input.
– Check that the Pr. 778 setting is not too short.

Solution:

– Check the wiring for the analog current input.
– Set the Pr. 778 setting larger.
E.PCH
Pre-charge
fault
Cause: The inverter output is shut off when the pre-charge time exceeds Pr.764 Pre-charge time limit. The inverter output is shut off when the measured value exceeds Pr.763 Pre-charge upper detection level during pre- charging. This function is available when Pr.764 and Pr.763 are set. This protective function is not available in the initial status.

Check point:

– Check that the Pr.764 setting is not too short.
– Check that the Pr.763 setting is not too small.
– Check that the Pr.127 PID control automatic switchover frequency setting is not too low.
– Check for a break in the connection to the pump.

Solution:

– Set the Pr.764 setting longer.
– Set the Pr.763 setting larger.
– Set the Pr.127 setting higher.
– Check the connection to the pump.
E.PID
PID signal
fault
Cause: The inverter output is shut off if the measured value exceeds the PID upper limit or PID lower limit parameter setting, or the absolute deviation value exceeds the PID deviation parameter setting during PID control. Set this function in Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit, and Pr.554 PID signal operation selection. This protective function is not available in the initial status.

Check point:

– Check the meter for a failure or break.
– Check that the parameter settings are correct.

Solution:

– Check that the meter has no failure or break.
– Set the parameters correctly.
E.1, E. 2
E.3
Fault 1,
Fault 2,
Fault 3
Option fault
Cause: The inverter trips when a contact fault is found between the inverter and the plug-in option, or when the communication option is not connected to the connector 1. Appears when the switch for manufacturer setting of the plug-in option is changed.

Check point:

– Check that the plug-in option is plugged into the connector properly. (1 to 3 indicate connector numbers for connection of options.)
– Check for excessive noise around the inverter.
– Check if the communication option is connected to the connector 2 or 3.

Solution:

– Connect the plug-in option securely.
– Take measures against noises if there are devices producing excess electrical noises around the inverter.
– Connect the communication option to the connector 1.
– Set the switch on the plug-in option, which is for manufacturer setting, back to the initial setting. (Refer to the Instruction Manual of each option.)