Nidec & Control Technique Pump Drive F600 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 28 An Input 1 Loss | Cause: Current loss detected in current mode on Analog input 1 (Terminal 5, 6). In 4-20 mA and 20-4 mA modes, loss of input is detected if the current falls below 3 mA. Remedy:
|
| 29 An Input 2 Loss | Cause: Current loss detected in current mode on Analog input 2 (Terminal 7). In 4-20 mA and 20-4 mA modes, loss of input is detected if the current falls below 3 mA. Remedy:
|
| 219 An Output Calib | Cause: The zero offset calibration of one or both of the analogue outputs has failed. Indicates hardware failure or voltage applied via low impedance. Sub-trip 1: Output 1 failed (Terminal 9) Sub-trip 2: Output 2 failed (Terminal 10) Remedy:
|
| 217 App Menu Changed | Cause: The customization table for an application menu has changed (Menu 18, 19, or 20). If more than one menu changed, the lowest menu has priority. Remedy:
|
| 121 Assist 1 Cycle | Cause: Soft Starter Assist 1 started too many times in an hour as defined by Assist Starts Per Hour (29.120). Only active when Assist Over-cycle Mode = Trip and Pump Control Mode = Cascade. Remedy:
|
| 122 Assist 2 Cycle | Cause: Soft Starter Assist 2 started too many times in an hour as defined by Assist Starts Per Hour (29.120). Only active when Assist Over-cycle Mode = Trip and Pump Control Mode = Cascade. Remedy:
|
| 11 Autotune 1 | Cause: Position feedback did not change or required speed could not be reached during autotune. Sub-trip 1: Position feedback did not change. Sub-trip 2: Required speed not reached. Sub-trip 3: Commutation signal edge not found. Sub-trip 4: Required movement angle not produced. Sub-trip 5: Motor flux position not located. Sub-trip 6: Phasing offset angle mismatch. Sub-trip 7: Motor moving on enable. Sub-trip 9: Minimal movement phasing test failed. Remedy:
|
| 12 Autotune 2 | Cause: Position feedback direction incorrect. Sub-trip 1: Direction incorrect during rotating autotune. Sub-trip 2: SINCOS encoder with comms rotating opposite to sine wave. Remedy:
|
| 13 Autotune 3 | Cause: Measured inertia exceeded parameter range or commutation signals changed in wrong direction. Sub-trip 1: Measured inertia exceeded range. Sub-trip 2: Commutation signals changed wrong direction. Sub-trip 3: Mechanical load test unable to identify inertia. Remedy:
|
| 14 Autotune 4 | Cause: U commutation signal did not change during a rotating auto-tune. Remedy:
|
| 15 Autotune 5 | Cause: V commutation signal did not change during a rotating auto-tune. Remedy:
|
| 16 Autotune 6 | Cause: W commutation signal did not change during a rotating auto-tune. Remedy:
|
| 17 Autotune 7 | Cause: Motor number of poles or position feedback resolution set incorrectly. Remedy:
|
| 18 Autotune Stopped | Cause: The drive was prevented from completing an autotune test because the drive enable or drive run were removed. Remedy:
|
| 123 Bkground Watchdg | Cause: Background task taking longer than 15s to execute. Remedy:
|
| 19 Brake R Too Hot | Cause: Braking resistor overload timed out (I2t). The Braking Resistor Thermal Accumulator (10.039) reached 100%. Remedy:
|
| 185 Card File Error | Cause: Information in the card header is out of range, or file system header information is incorrect. Remedy:
|
| 177 Card User Prog | Cause: Attempt to read a write-only user program, or transfer a program from drive to card when no program is present in drive. Remedy:
|
| 178 Card Busy | Cause: NV Media Card cannot be accessed as it is being accessed by an option module. Remedy:
|
| 188 Card Derivative | Cause: A parameter difference file is being written to the drive, but the Drive Derivative value in the file header differs from the drive. Remedy:
|
| 179 Card Data Exists | Cause: An attempt is being made to write to a file that already exists. Remedy:
|
| 187 Card File Data | Cause: The drive mode, required defaults, or product type in a parameter difference file are not compatible with the drive. Remedy:
|
| 182 Card Error | Cause: NV Media Card data structure error. Missing or corrupt folders/files. Sub-trip 1: Required folder structure missing. Sub-trip 2: <000> file corrupted. Sub-trip 3: Duplicate file identification numbers. Remedy:
|
| 184 Card Full | Cause: Not enough space left on the NV Media Card to create a data block. Remedy:
|
| 183 Card No Data | Cause: Attempt to access non-existent file or block on NV Media Card. Remedy:
|
| 180 Card Option | Cause: Option modules installed are different between source drive and destination drive. Warning that data for option modules will be set to defaults. Remedy:
|
| 175 Card Product | Cause: NV Media Card data blocks are not compatible with the drive derivative. Sub-trips: 1: Drive Derivative different between source and target. 2: Product Type different or corruption detected. 3: Unidrive SP parameter value found with no equivalent. Remedy:
|
| 186 Card Rating | Cause: The voltage and/or current rating of the source and destination drives are different during parameter transfer from NV Media Card. Remedy:
|
| 181 Card Read Only | Cause: An attempt has been made to modify a read-only NV Media Card or a read-only data block. Remedy:
|
| 174 Card Slot | Cause: Option module application program transfer has failed because the option module does not respond correctly. The sub-trip indicates the slot number. Remedy:
|
| 120 Clean Over-cycle | Cause: Pump cleaning cycle running too many times as defined by Clean Per Hour Limit (29.100). Only active if Clean Per Hour Limit Mode (29.101) = Trip. Remedy:
|
| 102 Cloning | Cause: Cloning system backup or restore of drive/option modules failed. The sub-trip value indicates the specific reason. Remedy:
|
| 111 Configuration | Cause: The number of power modules installed is different from the modules expected (11.071), or external rectifiers connected are less than expected (11.096). Remedy:
|
| 35 Control Word | Cause: Trip initiated from the Control Word (06.042) by setting bit 12 when the control word is enabled. Remedy:
|
| 124 Ctrl Wrd Watchdg | Cause: Watchdog bit 15 not being toggled for Watchdog Time (29.150) seconds. Protects system when HMI or PLC disconnects. Remedy:
|
| 225 Current Offset | Cause: The current feedback offset is too large to be trimmed correctly. Sub-trips: 1 (Phase U), 2 (Phase V), 3 (Phase W). Remedy:
|
| 97 Data Changing | Cause: Drive parameters are being changed by a user action or file system write while the drive has been commanded to enable. Remedy:
|
| 247 Derivative ID | Cause: There is a problem with the identifier associated with derivative image which customizes the drive. Sub-trips: 1: Derivative image erased. 2: Identifier out of range. 3: Derivative image changed. Remedy:
|
| 248 Derivative Image | Cause: Error detected in the derivative image. Common Sub-trips: 1: Divide by zero. 30: CRC incorrect / image header error. 53: Customisable menu table changed. 80/81: Image not compatible with control board. Remedy:
|
| 199 Destination | Cause: Two or more parameters are writing to the same destination parameter (Menus 5, 7, 8, 9, 12 or 14). Remedy:
|
| 224 Drive Size | Cause: The control PCB has not recognized the drive size of the power circuit to which it is connected. Remedy:
|
| 115 Dry Well | Cause: Dry Well Low Load detection triggered when Dry Well Low Load Mode (29.059) = Trip. Remedy:
|
| 31 EEPROM Fail | Cause: Default parameters have been loaded. This occurs if saved parameters are corrupted, power down save fails, or checksum fails. Remedy:
|
| 162 Encoder 12 | Cause: Drive is communicating with the encoder but the encoder type is not recognised. Remedy:
|
| 163 Encoder 13: Drive is communicating with the encoder | Cause: Data read from the encoder was out of range during auto-configuration. No parameters will be modified. The tens in the sub-trip indicate the interface (1 for P1, 2 for P2). Sub-trip Reasons: x1: Rotary lines per revolution error x2: Linear comms pitch error x3: Linear line pitch error x4: Rotary turns bits error x5: Communications bits error x6: Calculation time is too long x7: Line delay measured is longer than 5us Remedy:
|
| 164 Encoder 14: Drive is communicating with the encoder | Cause: Data given in the additional configuration parameter for a position feedback interface is out of range. P1 Additional Configuration (03.074) or P2 Additional Configuration (03.174) is out of range. BiSS: Range checking is applied to turns padding (digits 5-3) and position padding (digits 2-0). If padding value is outside +/- 16, trip is initiated. Remedy:
|
| 116 Ext Pump Fault: External Pump Fault Input | Cause: This trip is called by the Pump software in the event of the External Pump Fault Input (29.085) being set to On(1). Remedy:
|
| 6 External Trip: An External trip is initiated | Cause: An External Trip has occurred. Can be initiated by writing a value of 6 in Pr 10.038. Sub-trip Reasons: 1: External Trip Mode (08.010) = 1 or 3 and Safe Torque Off input 1 is low 2: External Trip Mode (08.010) = 2 or 3 and Safe Torque Off input 2 is low 3: External Trip (10.032) = 1 Remedy:
|
| HF01 Data processing error: CPU address error | Cause: A CPU address error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF02 Data processing error: DMAC address error | Cause: A DMAC address error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF03 Data processing error: Illegal instruction | Cause: An illegal instruction has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF04 Data processing error: Illegal slot instruction | Cause: An illegal slot instruction has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF05 Data processing error: Undefined exception | Cause: An undefined exception error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF06 Data processing error: Reserved exception | Cause: A reserved exception error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF07 Data processing error: Watchdog failure | Cause: A watchdog failure has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF08 Data processing error: CPU Interrupt crash | Cause: A CPU interrupt crash has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF09 Data processing error: Free store overflow | Cause: A free store overflow has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF10 Data processing error: Parameter routing system error | Cause: A Parameter routing system error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF11 Data processing error: Access to EEPROM failed | Cause: Access to the drive EEPROM has failed. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF12 Data processing error: Main program stack overflow | Cause: The main program stack overflow has occurred. Control PCB has failed. Sub-trip Stack ID: 1: Background tasks 2: Timed tasks 3: Main system interrupts Remedy:
|
| HF13 Data processing error: Firmware incompatible with hardware | Cause: Drive firmware is not compatible with the hardware. The sub-trip number gives the actual ID code of the control board hardware. Remedy:
|
| HF14 Data processing error: CPU register bank error | Cause: A CPU register bank error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF15 Data processing error: CPU divide error | Cause: A CPU divide error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF16 Data processing error: RTOS error | Cause: A RTOS error has occurred. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF17 Data processing error: Clock supplied to the control board is out of specification | Cause: The clock supplied to the control board logic is out of specification. This trip indicates that the control PCB on the drive has failed. Remedy:
|
| HF18 Data processing error: Internal flash memory has failed | Cause: Internal flash memory has failed when writing option module parameter data. Sub-trip Reasons: 1: Programming error while writing menu in flash 2: Erase flash block containing setup menus failed 3: Erase flash block containing application menus failed Remedy:
|
| HF19 Data processing error: CRC check on the firmware has failed | Cause: The CRC check on the drive firmware has failed. Remedy:
|
| HF20 Data processing error: ASIC is not compatible with the hardware | Cause: The ASIC version is not compatible with the drive firmware. The ASIC version can be identified from the sub-trip number. Remedy:
|
| HF23 to HF25 Hardware fault | Cause: Internal hardware fault occurred. Remedy:
|
| 26 I/O Overload: Digital output overload | Cause: Total current drawn from 24 V user supply or from the digital output has exceeded the limit. Conditions:
Remedy:
|
| 8 Inductance | Cause: This trip occurs in RFC-S mode when the drive has detected that the motor inductances are not suitable for the operation being attempted. The trip is either caused because the ratio or difference between Ld and Lq is too small or because the saturation characteristic of the motor cannot be measured. Remedy:
|
| 20 Motor Too Hot | Cause: The Motor Too Hot trip indicates a motor thermal overload based on the rated current (Pr 05.007) and motor thermal time constant (Pr 04.015). Pr 04.019 displays the motor temperature as a percentage of the maximum value. The drive will trip when Pr 04.019 gets to 100%. Remedy:
|
| 21 OHt Inverter | Cause: Inverter over temperature based on thermal model. This trip indicates that an IGBT junction over-temperature has been detected based on a firmware thermal model. Remedy:
|
| 23 OHt Control | Cause: Control stage over temperature. This trip indicates that a control stage over-temperature has been detected (Control board thermistors or I/O board thermistor). Remedy:
|
| 27 OHt dc bus | Cause: DC bus over temperature. The trip indicates a DC bus component over temperature based on a software thermal model, or power stage detection in multi-power module systems. Remedy:
|
| 34 Keypad Mode | Cause: Keypad has been removed when the drive is receiving the speed reference from the keypad. Remedy:
|
| 38 Low Load | Cause: Low load detector is set up to produce a trip on low load detection. This trip is initiated if the low load detector is set up to produce a trip on low load detection and this condition occurs. Remedy:
|
| 39 Line Sync | Cause: Line Sync error. Remedy:
|
| 93 Inductor Too Hot | Cause: Inductor Too Hot. Remedy:
|
| 101 OHt Brake | Cause: Braking IGBT over-temperature. The trip indicates that braking IGBT over-temperature has been detected based on software thermal model. Remedy:
|
| 103 Inter-connect | Cause: Multi-power module drive interconnection cable error. Indicates which power module has detected the fault or if communication fails. Remedy:
|
| 118 Motor Over Temp | Cause: This trip is called by the Pump software in the event of the Motor Thermal Protection Input (29.086) being set to Off(0) when Motor Thermal Protection Enable (29.087) = On(1). Remedy:
|
| 160 Island | Cause: System is connected to an island supply. Remedy:
|
| 176 Name Plate | Cause: Electronic nameplate transfer has failed.
Remedy:
|
| Network Loss Ethernet RTMoE Loss | Cause: Event of a loss Ethernet RTMoE comms from this drive to its Leader in a Multi-leader system. Remedy:
|
| OHt Power (22) Power stage over temperature | Cause: A power stage over-temperature has been detected. The sub-trip “xxyzz” indicates which thermistor is indicating the over-temperature (located on power board or rectifier). Remedy:
|
| OI ac (3) Instantaneous output over current detected | Cause: The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX. This trip cannot be reset until 10 s after the trip was initiated. Remedy:
|
| OI Brake (4) Braking IGBT over current detected | Cause: Over current has been detected in braking IGBT or braking IGBT protection has been activated. This trip cannot be reset until 10 s after the trip was initiated. Remedy:
|
| OI dc (109) Power module over current detected from IGBT on state voltage monitoring | Cause: The short circuit protection for the drive output stage has been activated. This trip cannot be reset until 10 s after the trip was initiated. Remedy:
|
| OI Snubber (92) Snubber over-current detected | Cause: An over-current condition has been detected in the rectifier snubber circuit. Remedy:
|
| Option Disable (215) Option module does not acknowledge during drive mode changeover | Cause: During drive mode changeover option modules must acknowledge that they have stopped accessing the communications system. If an option module does not do this in the allowed time then this trip is produced. Remedy:
|
| Out Phase Loss (98) Output phase loss detected | Cause: A phase loss has been detected at the drive output. Sub-trips indicate specifically which phase (U, V, or W) was detected as disconnected or if an IGBT failure was detected. Remedy:
|
| Over-Cycle (117) Over-cycle | Cause: This trip is called by the Pump software in the event of the over-cycle protection scheme counting too many starts per hour when Over-cycle Mode (29.127) = Trip. Remedy:
|
| Over Speed (7) Motor speed has exceeded the over speed threshold | Cause: In open loop mode, Output Frequency exceeds the threshold set in 03.008. In RFC-A/S mode, Speed Feedback exceeds the threshold. Can also be caused by SSI encoder settings or flux weakening configurations. Remedy:
|
| Over Volts (2) DC bus voltage has exceeded the peak level or maximum continuous level | Cause: The DC bus voltage has exceeded the VM_DC_VOLTAGE[MAX] or VM_DC_VOLTAGE_SET[MAX] for 15 s. The threshold varies depending on the voltage rating of the drive. Remedy:
|
| 32 Phase Loss: Supply phase loss | Cause: Input phase loss, large supply imbalance, or high ripple in the DC bus voltage detected. Remedy:
|
| 198 Phasing error: Phase offset angle is incorrect | Cause: The phase offset angle in Position Feedback Phase Angle (03.025) is incorrect, incorrect encoder wiring, noise, or instability in sensorless control. Remedy:
|
| 113 PID Feedbk High: PID1 feedback above high threshold | Cause: The main process PID1 feedback has gone above the PID Feedback High Trip Threshold (29.041). Remedy:
|
| 112 PID Feedbk Loss: PID1 feedback loss detected | Cause: Loss of main process PID1 feedback when PID Feedback Loss Action (29.048) is set to Trip. Remedy:
|
| 114 PID Feedbk Low: PID1 feedback below low threshold | Cause: The main process PID1 feedback has gone below the PID Feedback Low Threshold (29.044). Remedy:
|
| 90 Power Comms: Communications problem within power system | Cause: Excessive communications errors detected by the rectifier module or between control/power systems. Remedy:
|
| 220 Power Data: Power system configuration data error | Cause: Error in configuration data stored in the power system (e.g., table missing, table too big, CRC error, version mismatch). Remedy:
|
| 37 Power Down Save: Power down save error | Cause: An error has been detected in the power down save parameters saved in non-volatile memory. Remedy:
|
| 5 PSU: Internal power supply fault | Cause: One or more internal power supply rails are outside limits or overloaded. Remedy:
|
| 9 PSU 24V: 24V internal power supply overload | Cause: The total user load of the drive and option modules has exceeded the internal 24V power supply limit. Remedy:
|
| 94 Rectifier Set-up: Rectifier incorrectly set up | Cause: A rectifier has not been set-up correctly in a multi-power module system. Remedy:
|
| 100 Reset | Cause: This is not a valid trip number. Remedy:
|
| 255 Reset Logs | Cause: This is not a valid trip number. Remedy:
|
| 223 Rating Mismatch: Multi module voltage or current rating mismatch | Cause: A mixture of power modules with different voltage or current ratings detected in a parallel system. Remedy:
|
| 33 Resistance: Measured resistance exceeded parameter range | Cause: Stator resistance too high, measurement failed during auto-tune, or motor parameters changed by user. Remedy:
|
| 216 Slot App Menu: Customization conflict error | Cause: More than one option slot has requested to customize the application menus 18, 19, and 20. Remedy:
|
| 204, 209, 214, 254 SlotX Different: Option module in slot X has changed | Cause: The option module in slot X is a different type than what was previously installed and saved. Remedy:
|
| 202, 207, 212, 252 SlotX Error | Cause: The Option module in option slot X on the drive has detected an error. The reason for the error can be identified by the sub-trip number. Remedy:
|
| 200, 205, 210, 250 SlotX HF | Cause: The option module in option slot X on the drive has indicated a hardware fault. Possible causes (Sub-trips): 1: Module category unidentified. 2: Table information corrupt/missing. 3: Insufficient memory for comms buffers. 4-10: Various initialization or communication failures. Remedy:
|
| 203, 208, 213, 253 SlotX Not Fitted | Cause: The option module in option slot X on the drive has been removed since the last power up. Remedy:
|
| 201, 206, 211, 251 SlotX Watchdog | Cause: The option module installed in Slot X has started the option watchdog function and then failed to service the watchdog correctly. Remedy:
|
| 226 Soft Start | Cause: The soft start relay in the drive failed to close or the soft start monitoring circuit has failed. Remedy:
|
| 221 Stored HF | Cause: A hardware trip (HF01 – HF19) has occurred and the drive has been power cycled. The sub-trip number identifies the HF trip (e.g. stored HF.17). Remedy:
|
| 227 Sub-array RAM | Cause: RAM allocation error. An option module, derivative image or user program image has requested more parameter RAM than is allowed. The failure with the highest sub-trip number is given. Remedy:
|
| 218 Temp Feedback | Cause: An internal thermistor has failed. The thermistor location can be identified by the sub-trip number (01: Control board thermistor 1, 02: Control board thermistor 2, 03: I/O board thermistor). Remedy:
|
| 10 Th Brake Res | Cause: Brake resistor over temperature. If hardware based braking resistor thermal monitoring is connected and the resistor overheats. If the resistor is not used, this trip must be disabled (bit 3 of Action On Trip Detection 10.037). Remedy:
|
| 25 Th Short Circuit | Cause: Motor thermistor short circuit. A temperature sensor connected to an analogue input or terminal 15 on the position feedback interface has a low impedance (i.e. < 50 Ω). Remedy:
|
| 24 Thermistor | Cause: Motor thermistor over-temperature. The motor thermistor connected to terminal 8 (analog input 3) or terminal 15 (encoder) has indicated a motor over temperature. Remedy:
|
| 110 Undefined | Cause: The drive has tripped and the cause of the trip is Undefined. The power system generated a trip but did not identify the trip type. Remedy:
|
| 91 User 24V | Cause: User 24 V supply is not present on control terminals (1,2). Initiated if User Supply Select (Pr 06.072) is set to 1 or Low Under Voltage Threshold Select (06.067) = 1. Remedy:
|
| 249 (Cont) User Program | Cause: On board user program error. Sub-trips indicate specifics: 40,41: Enable reset to zero. 51, 6x, 7x: Customization/Module restrictions. 100-104: Pointer/Array access violations or Type conversion errors. 200: Divide by zero. Remedy:
|
| 96 User Prog Trip | Cause: Trip generated by an onboard user program using a function call which defines the sub-trip number. Remedy:
|
| 36 User Save | Cause: User Save error / not completed. Error detected in user save parameters saved in non-volatile memory (e.g. power removed while saving). Remedy:
|
| 40-89, 125-159 User Trip | Cause: User generated trip. These trips are not generated by the drive and are to be used by the user to trip the drive through an application program. Remedy:
|
| 169 Voltage Range | Cause: Not Applicable. Remedy:
|
| 30 Watchdog | Cause: Control word watchdog has timed out. The control word has been enabled and has timed out. Remedy:
|
| HF01 – HF20 Internal / Hardware trips | Cause: The main drive processor has detected an irrecoverable error. Internal faults that do not have trip numbers. Remedy:
|
| Brake Resistor Brake resistor overload | Cause: Braking Resistor Thermal Accumulator (10.039) in the drive has reached 75.0 % of the value at which the drive will trip. Remedy:
|
| Motor Overload Motor protection warning | Cause: Motor Protection Accumulator (04.019) in the drive has reached 75.0 % of the value at which the drive will trip and the load on the drive is > 100 %. Remedy:
|
| Drive Overload Drive over temperature | Cause: Percentage Of Drive Thermal Trip Level (07.036) in the drive is greater than 90 %. Remedy:
|
| Auto Tune Autotune in progress | Cause: The autotune procedure has been initialized. Remedy:
|
| Error 1 Insufficient Memory | Cause: There is not enough drive memory requested by all the option modules. Remedy: Power down drive and remove some of the option modules until the message disappears. |
| Error 2 Module Reset Failure | Cause: At least one option module did not acknowledge the reset request. Remedy: Power cycle drive. |
| Error 3 Flash Erase Failure | Cause: The boot loader failed to erase the processor flash. Remedy: Power cycle drive and try again. If problem persists, return drive. |
| Error 4 Flash Program Failure | Cause: The boot loader failed to program the processor flash. Remedy: Power cycle drive and try again. If problem persists, return drive. |
| Error 5 Module Initialization Failure | Cause: One option module did not initialize correctly. Option module did not set Ready to Run flag. Remedy: Remove faulty option module. |