Parker AC10P Drive

Fault Code and MeaningCause and Remedy
Err0
Prohibition modify function code

Cause: Prohibition modify the function code during running process.



Remedy:

  • Please modify the function code in stopped status.


Err1
Wrong password

Cause: Entered wrong password when password is valid. Do not enter password when modifying function code.



Remedy:

  • Please enter the correct password.


2: O.C.
16: OC1
67: OC2
Over-current (1 & 2)

Cause:
Too short acceleration time; short circuit at output side; locked rotor with motor; too heavy load; parameter tuning is not correct.



Remedy:

  • Prolong acceleration time.

  • Check whether motor cable is broken.

  • Check if motor overloads.

  • Reduce V/F compensation value.

  • Measure parameter correctly.


3: O.E.
DC Over-Voltage

Cause:
Supply voltage too high; load inertia too big; deceleration time too short; motor inertia rise again; bad effect of dynamic braking; parameter of rotary speed loop PID is set abnormally.



Remedy:

  • Check if rated voltage is input.

  • Add braking resistance (optional).

  • Increase deceleration time.

  • Enhancing the dynamic braking effect.

  • Set the parameter of rotary speed loop PID correctly.

  • Change to VF control for centrifugal fan.


4: P.F1.
Input Phase loss

Cause: Phase loss with input power.



Remedy:

  • Check if power input is normal.

  • Check if parameter setting is correct.


5: O.L1
Inverter Overload

Cause: Load too heavy.



Remedy:

  • Reduce load.

  • Check drive ratio.

  • Increase inverter’s capacity.


6: L.U.
Under-Voltage Protection

Cause: Input voltage on the low side.



Remedy:

  • Check if supply voltage is normal.

  • Check if parameter setting is correct.


7: O.H.
Radiator Overheat

Cause:
Environment temperature too high; radiator too dirty; install place not good for ventilation; fan damaged; Carrier wave frequency or compensation curve is too high.



Remedy:

  • Improve ventilation.

  • Clean air inlet, outlet, and radiator.

  • Install as required.

  • Change fan.

  • Decrease carrier wave frequency or compensation curve.


8: O.L2
Motor Overload

Cause: Load too heavy.



Remedy:

  • Reduce load.

  • Check drive ratio.

  • Increase motor’s capacity.


11: ESP
External fault

Cause: External emergency-stop terminal is valid.



Remedy:

  • Check external fault.


12: Err3
Current malfunction before running

Cause: Current alarm signal exists before running.



Remedy:

  • Check if control board is connected with power board well.

  • Ask for help from manufacturer.


13: Err2
Parameters tuning wrong

Cause: Do not connect motor when measuring parameters.



Remedy:

  • Please connect motor correctly.


15: Err4
Current zero excursion malfunction

Cause: Flat cable is loosened; Current detector is broken.



Remedy:

  • Check the flat cable.

  • Ask for help from manufacturer.


17: PF0
Output Phase loss

Cause: Motor is broken; Motor wire is loose; Inverter is broken.



Remedy:

  • Check if wire of motor is loose.

  • Check if motor is broken.


18: AErr
Line disconnected

Cause: Analog signal line disconnected; Signal source is broken.



Remedy:

  • Change the signal line.

  • Change the signal source.


19: EP3
20: EP/EP2
Inverter under-load

Cause: Water pump dries up; Belt is broken; Equipment is broken.



Remedy:

  • Supply water for pump.

  • Change the belt.

  • Repair the equipment.


22: nP
Pressure control

Cause: Pressure is too high when negative feedback; Pressure is too low when positive feedback; Inverter enters into the dormancy status.



Remedy:

  • Decrease the min frequency of PID.

  • Reset inverter to normal status.


23: Err5
PID parameters are set wrong

Cause: PID parameters are set wrong.



Remedy:

  • Set the parameters correctly.


26: GP
Earth fault protection

Cause: Motor cable is damaged, short connected to grounding; Motor isolation is damaged, short connected to grounding; Inverter fault.



Remedy:

  • Change a new cable.

  • Repair the motor.

  • Contact manufacturer.


27: GP
Encoder fault

Cause: Encoder installation error; Encoder fault; Encoder line number fault.



Remedy:

  • Check the installation and connection.

  • Check encoder.

  • Set F851 correctly.


32: PCE
PMSM distuning fault

Cause: Motor parameters measurement is wrong; Load is too heavy.



Remedy:

  • Measure motor parameters correctly.

  • Decrease the load.


35: OH1
PTC overheat protection

Cause: External relay protection.



Remedy:

  • Check external heat protection equipment.


44: Er44
Master loses slave’s response

Cause: Communication fault between master and slave.



Remedy:

  • Check wiring.

  • Check baud rate.

  • Check communication parameters setting.


45: CE
Communication timeout error

Cause: Communication fault.



Remedy:

  • Check if PC/PLC sends command at fixed time.

  • Check whether the communication line is connected reliably.


47: EEEP
EEPROM read/write fault

Cause: Interference around; EEPROM is damaged.



Remedy:

  • Remove interferences.

  • Contact manufacturer.


49: Err6
Watchdog fault

Cause: Watchdog timeout.



Remedy:

  • Please check watchdog signal.