Parker DC590+ Plus Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OVERSPEED Motor overspeed – the speed feedback signal has exceeded 125% of rated speed. | Cause: Badly adjusted speed loop (alarm only operates with encoder or armature volts feedback selected). Remedy:
|
| MISSING PULSE A missing pulse from the 6-pulse armature current waveform. | Cause: Firing plug failure or Connection failure. Note: This trip is only enabled when motor loading exceeds 1.5 times the DISCONTINUOUS parameter value. Remedy:
|
| FIELD OVER I The motor field current has exceeded 120% of the calibrated value. | Cause: External field has incorrect supply phases applied. Remedy:
|
| HEATSINK TRIP The Drive heatsink temperature is too high. | Cause: The ambient air temperature is too high; Poor ventilation or spacing between Drives; Blocked ventilation slots; Clogged air filters; Excessive armature current. Remedy:
|
| THERMISTOR The motor temperature is too high. | Cause: Inadequate ventilation; Blower failure; Excessive armature current. Remedy:
|
| OVER VOLTS (VA) Motor armature voltage has exceeded 120% of rated volts. | Cause: Loose armature connection; Badly adjusted field voltage setting; Badly adjusted field current loop; Badly adjusted field-weakening bemf loop; Badly adjusted speed loop. Remedy:
|
| SPEED FEEDBACK Difference between speed feedback and armature voltage feedback is greater than SPDFBK ALM LEVEL. | Cause: Analog tacho feedback polarity incorrect; ENCODER SIGN parameter polarity incorrect; Disconnection of wiring (including fibre optics); Tachogenerator failure/coupling failure. Remedy:
|
| ENCODER FAILED No speed feedback signal. | Cause: SPEED FBK SELECT parameter is set to ENCODER but an optional Encoder board is not fitted; Damaged fibre optic cable. Remedy:
|
| FIELD FAIL Field current is less than 6% (Current Control) or 50mA (Voltage Control). | Cause: Open circuit motor field; Faulty operation of field controller; Missing 3-phase supply for synchronization. Remedy:
|
| 3-PHASE FAILED 3-phase supply failure. | Cause: Total failure of supply or missing phase; Blown fuses (thyristor stack or power chassis). Remedy:
|
| PHASE LOCK Supply frequency is outside limits 45 – 65Hz. | Cause: Supply frequency fault; Synchronization errors caused by distorted supply. Remedy:
|
| 5703 RCV ERROR Invalid data received via P3 port from another Drive. | Cause: Communication error. Remedy:
|
| STALL TRIP Motor stationary, current exceeded STALL THRESHOLD for longer than STALL TRIP DELAY. | Cause: Mechanical stall or load issue. Remedy:
|
| OVER I TRIP Current feedback value has exceeded 280% of rated current. | Cause: Motor armature windings failure; Badly tuned current loop; Faulty Drive. Remedy:
|
| ACCTS FAILED AC current transformer plug connection to Drive power board missing. | Cause: Plug disconnected; Load imbalance (Frame 5). Remedy:
|
| AUTOTUNE ERROR Error encountered during Autotune process. | Cause: Motor shaft rotating; Open-circuit wiring; Discontinuous current boundary too high; Large supply imbalance; Hardware fault. Remedy:
|
| AUTOTUNE ABORT The Autotune sequence has been aborted. | Cause: Coast Stop/Program Stop/Enable disabled; AUTOTUNE parameter reset; Timeout (2 mins). Remedy:
|
| SEQ PRE READY Coding not present. | Cause: Hardware configuration issue. Remedy:
|
| CONTACTOR DELAY The internal auxiliary 3-phase contactor failed to close. | Cause: Calibration issue. Remedy:
|
| EXTERNAL TRIP Customer alarm! Trip operates if input open or high impedance. | Cause: Device not wired to drive or device open circuited. Remedy:
|
| REMOTE TRIP Remote Trip flag set. | Cause: REM. SEQUENCE parameter Remote Trip flag set to zero. Remedy:
|
| ENABLE LOW Local Mode run with Enable input low. | Cause: Enable input is low while trying to run in Local Mode. Remedy:
|
| SEQUENCING Internal sequencing error. | Cause: Internal software/hardware error. Remedy:
|
| COMMS TIMEOUT Remote comms timeout. | Cause: Communication interruption. Remedy:
|
| CONFIG ENABLED The drive was requested to start whilst in Configuration mode. | Cause: Drive is in Configuration mode. Remedy:
|
| CALIBRATION FAIL Signal calibration fault. | Cause: Hardware failure suspected. Remedy:
|
| NO OP STATION Keypad has been disconnected from Drive whilst Drive is running in local control. | Cause: Keypad disconnection. Remedy:
|
| AUX SUPPLY Auxiliary supply failure. | Cause: Missing or unstable supply. Remedy:
|
| COMMS FAULT CODE x Keypad or remote cable fault. | Cause: Keypad faulty; Remote cable to keypad faulty; Drive firmware not running. Remedy:
|
| CRITICAL ERROR System Critical Error. | Cause: Internal failure. Remedy:
|
| (EEPROM) CHECKSUM FAIL Parameters not saved, or are corrupted. | Cause: Corrupted UDP file loaded. Remedy:
|
| LANGUAGE CHECKSUM FAIL Incorrect language selected, or corrupted. | Cause: Corrupted UDP file loaded. Remedy:
|