—- Problem with application firmware |
Cause: Invalid application firmware update using the Multi-Loader tool.
Remedy:
- Re-download application firmware.
|
F001 Precharge |
Cause: Charging relay control fault or charging resistor damaged.
Remedy:
- Turn the drive off and then back on again.
- Check the connections.
- Check the stability of the main supply.
- Contact local Schneider Electric representative.
|
F002 Unknown drive rating |
Cause: Power card and stored card versions different.
Remedy:
- Contact local Schneider Electric representative.
|
F003 Unknown or incompatible power board |
Cause: The power card is incompatible with the control card.
Remedy:
- Contact local Schneider Electric representative.
|
F004 Internal serial link fault |
Cause: Communication interruption between the internal cards.
Remedy:
- Contact local Schneider Electric representative.
|
F005 Invalid industrialization zone |
Cause: Internal data inconsistent.
Remedy:
- Contact local Schneider Electric representative.
|
F006 Current measurement circuit |
Cause: Current measurement is not correct due to hardware circuit fault.
Remedy:
- Contact local Schneider Electric representative.
|
F007 Internal thermal sensor detected fault |
Cause:
- The drive temperature sensor is not operating correctly.
- The drive is in short circuit or open.
Remedy:
- Contact local Schneider Electric representative.
|
F008 Internal CPU |
Cause: Internal microprocessor fault.
Remedy:
- Turn the drive off and then back on again.
- Contact local Schneider Electric representative.
|
F010 Overcurrent |
Cause:
- Parameters in the Motor control menu (300) are not correct.
- Inertia or load too high.
- Mechanical locking.
Remedy:
- Check the parameters.
- Check the size of the motor/drive/load.
- Check the state of the mechanism.
- Connect line motor chokes.
- Reduce the Switching frequency range (315).
- Check the ground connection of drive, motor cable, and motor insulation.
|
F018 Motor short-circuit |
Cause:
- Short-circuit or grounding at the drive output.
- Ground fault while in run state.
- Motor switching while in run state.
- Significant current leakage to ground while several motors are connected in parallel.
Remedy:
- Verify the cables connecting the drive to the motor and the motor insulation.
- Adjust the switching frequency.
- Connect chokes in series with the motor.
- Verify the adjustment of speed loop.
|
F019 Ground short-circuit |
Cause:
- Ground fault while in run state.
- Motor switching while in run state.
- Significant current leakage to ground.
Remedy:
- Verify the cables connecting the drive to the motor and the motor insulation.
- Adjust the switching frequency.
- Connect chokes in series with the motor.
- Verify the adjustment of speed loop.
|
F020 IGBT short circuit |
Cause: Internal power component short circuit detected at power on.
Remedy:
- Contact local Schneider Electric representative.
|
F025 Overspeed |
Cause:
- Instability.
- Overspeed associated with the inertia of the application.
Remedy:
- Check the motor.
- If overspeed is 10% more than Top frequency (308), adjust this parameter if necessary.
- Add a braking resistor.
- Check the size of the motor/drive/load.
- Check parameters of the speed loop (gain and stability).
|
F028 Autotuning fault |
Cause:
- Motor not connected to the drive.
- Motor phase loss.
- Special motor.
- Motor is rotating (being driven by the load, for example).
Remedy:
- Check that the motor/drive are compatible.
- Check that the motor is present during autotuning.
- If an output contactor is being used downstream, close it during auto-tuning.
- Check that the motor is completely stopped.
|
F036 Angle setting fault |
Cause: This occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high.
Remedy:
- Check the motor phases and the maximum current allowed by the drive.
|
F009 Overbraking |
Cause: Sudden braking or load inertia too high.
Remedy:
- Increase the deceleration time.
- Install a module unit with a braking resistor if necessary.
- Check the main supply voltage to ensure it is under the maximum acceptable limit during run status.
|
F011 Drive overheat |
Cause: Drive temperature too high.
Remedy:
- Check the motor load, the drive ventilation and the ambient temperature.
- Wait for the drive to cool down before restarting.
- See Mounting and temperature conditions in manual.
|
F012 Process overload fault |
Cause: Process overload.
Remedy:
- Check that drive parameters and application processes are compatible.
|
F013 Motor overload |
Cause: Triggered by excessive motor current.
Remedy:
- Check configuration of motor thermal protection and motor load.
|
F014 1 Output phase loss |
Cause: Loss of one phase on drive output.
Remedy:
- Check the connections from the drive to the motor.
- If using a downstream contactor, make sure the connection, cable and contactor are right.
|
F015 3 Output phases loss |
Cause:
- Motor not connected.
- Motor power too low, below 6% of the rated drive current.
- Output contactor open.
- Transient instability in the motor current.
Remedy:
- Check the connections from the drive to the motor.
- Test on a low power motor or without a motor.
- In factory settings, motor phase loss detection is active (605=01). To test without a motor, set 605=00.
- Check and optimize IR compensation (310), Rated motor voltage (304), and Rated motor current (305), then perform Auto-tuning (318).
|
F016 Main overvoltage |
Cause:
- Line voltage too high.
- Drive power supply >10% over max acceptable voltage.
- Power with no run command >20% over max line supply.
- Disturbed mains supply.
Remedy:
- Turn Off the Drive. Check and adjust the line voltage.
- After line comes back to nominal voltage, power On.
- If intermittent F016 codes appear, set R1 assignment (205.0) to 01.
|
F017 Input phase loss |
Cause:
- Drive incorrectly supplied or a fuse blown.
- Failure of one phase.
- 3-phase drive used on a single-phase line supply.
- Unbalanced load.
Remedy:
- Check the power connection and the fuses.
- Use a 3-phase line supply.
- Disable reporting of this fault by setting Input Phase loss detection (606) to 00.
|
F021 Load short circuit |
Cause:
- Short-circuit at drive output.
- Short circuit detection at the run command or DC injection if parameter IGBT Test (608) is set to 01.
Remedy:
- Check the cables connecting the drive to the motor and the condition of motor insulation.
|
F022 Modbus interruption |
Cause: Interrupted communication on the Modbus network.
Remedy:
- Check the connections of communication bus.
- Check the time-out (parameter Modbus time out 704).
- Refer to the Modbus user manual.
|
F024 HMI communication |
Cause: Communication interruption with the external display terminal.
Remedy:
- Check the terminal connection.
|
F026 PI feedback fault |
Cause: PID feedback below lower limit.
Remedy:
- Verify the PID function feedback.
- Verify the PID feedback supervision (parameter 59.25) and time delay setting (parameter 59.23).
|
F027 IGBT overheat |
Cause:
- Drive overheated.
- IGBT internal temperature is too high for the ambient temperature and load.
Remedy:
- Check the size of the load/motor/drive.
- Reduce the Switching frequency (315).
- Wait for the drive to cool down before restarting.
|
F029 Process underload fault |
Cause:
- Process underload.
- Time that motor current is below the Process underload threshold (211) exceeds the delay (210).
Remedy:
- Check that drive parameters and application processes are compatible.
|
F033 AI1 current loss |
Cause:
- Analog input AI1 is configured as current.
- AI1 current scaling parameter (204.1) is greater than 3 mA.
- Analog input current is lower than 2 mA.
Remedy:
- Check the terminal connection.
|
F030 Undervoltage |
Cause:
- Line supply too low.
- Transient voltage dip.
Remedy:
- Check the voltage and parameters on the Undervoltage phase loss menu (607).
|
F031 Incorrect configuration |
Cause:
- HMI block replaced by an HMI block configured on a drive with a different rating.
- The current configuration of customer parameters is inconsistent.
Remedy:
- Return to factory settings or retrieve the backup configuration, if it is valid.
- If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.
|
F032 Invalid configuration |
Cause:
- Invalid configuration.
- The configuration loaded in the drive via the bus/communication network is inconsistent.
- The configuration upload has been interrupted or is not fully finished.
Remedy:
- Check the configuration loaded previously.
- Load a compatible configuration.
|
F034 Download invalid configuration |
Cause: When save parameter setting or restore to factory setting, the drive detects invalid configuration.
Remedy:
- Power cycle drive.
- Restore to factory setting.
- If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.
|
InIt:
Auto-initialization on start
|
Cause:
- Macro controller initialization.
- Searching communication configuration.
Remedy:
|
COM.E (Flashing)
Communication error
|
Cause:
- 50 ms time out error.
- This message appears after 220 retry attempts.
Remedy:
|
A-17 (Flashing)
Key alarm
|
Cause:
- Key pressed down for longer than 10 seconds.
- Membrane switch disconnected.
- Display terminal woken up while a key is being pressed.
Remedy:
|
cLr (Flashing)
Confirm fault reset
|
Cause:
This message appears if the STOP key is pressed while the display terminal is displaying a fault.
Remedy:
|
dEU.E (Flashing)
Drive mismatch
|
Cause:
Drive type (brand) does not match display terminal type (brand).
Remedy:
|
rOM.E (Flashing)
ROM abnormality
|
Cause:
ROM abnormality detected by checksum calculation.
Remedy:
|
rAM.E (Flashing)
RAM abnormality
|
Cause:
Display terminal RAM abnormality detected.
Remedy:
|
CPU.E (Flashing)
Other fault
|
Cause:
The other detected fault.
Remedy:
|