Siemens V70 Drive Fault Codes:
| Fault Code and Meaning | Cause and Remedy |
|---|---|
F1000 Internal software error Reaction: OFF2 Acknowledgement: POWER ON | Cause: An internal software error has occurred. Remedy:
|
F1001 Floating Point exception Reaction: OFF2 Acknowledgement: POWER ON | Cause: An exception occurred during an operation with the Floating Point data type. Remedy:
|
F1002 Internal software error Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause: An internal software error has occurred. Remedy:
|
F1003 Acknowledgement delay when accessing the memory Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause: A memory area was accessed that does not return a “READY”. Remedy:
|
F1015 Internal software error Reaction: OFF2 Acknowledgement: POWER ON | Cause: An internal software error has occurred. Remedy:
|
F1018 Booting has been interrupted several times Reaction: NONE Acknowledgement: POWER ON | Cause: Module booting was interrupted several times. As a consequence, the module boots with the factory setting. Possible reasons for booting being interrupted:
After this fault is output, then the module is booted with the factory settings. Remedy:
Examples:
Note: If the fault situation is repeated, then this fault is again output after several interrupted boots. |
F1030 Sign-of-life failure for master control Reaction: OFF3 Acknowledgement: IMMEDIATELY | Cause: For active PC master control, no sign-of-life was received within the monitoring time. Remedy: Contact the Hotline. |
F1611 SI CU: Defect detected Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause: The drive-integrated “Safety Integrated” (SI) function on the Control Unit (CU) has detected an error and initiated an STO. Remedy:
|
F1910 Drive Bus: Setpoint timeout Reaction: OFF3 Acknowledgement: IMMEDIATELY | Cause: The reception of setpoints from the Drive Bus interface has been interrupted.
Remedy: Restore the bus connection and set the controller to RUN. |
F1911 Drive Bus clock cycle synchronous operation clock cycle failure Reaction: OFF1 Acknowledgement: IMMEDIATELY | Cause: The global control telegram to synchronize the clock cycles has failed – in cyclic operation – for several Drive Bus clock cycles or has violated the time grid specified in the parameterizing telegram over several consecutive Drive Bus clock cycles. Remedy:
|
F1912 Clock cycle synchronous operation sign-of-life failure Reaction: OFF1 Acknowledgement: IMMEDIATELY | Cause: The maximum permissible number of errors in the controller sign-of-life (clock synchronous operation) has been exceeded in cyclic operation. Remedy:
|
F7011 Motor overtemperature Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause:
Remedy:
|
F7085 Open-loop/closed-loop control parameters changed Reaction: NONE Acknowledgement: IMMEDIATELY | Cause: Open-loop/closed-loop control parameters have had to be changed for the following reasons:
Remedy: It is not necessary to change the parameters as they have already been correctly limited. |
F7403 Lower DC link voltage threshold reached Reaction: OFF1 Acknowledgement: IMMEDIATELY | Cause: The DC link voltage monitoring is active and the lower DC link voltage threshold was reached in the “Operation” state. Remedy:
|
F7404 Upper DC link voltage threshold reached Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause: The DC link voltage monitoring is active and the upper DC link voltage threshold was reached in the “Operation” state. Remedy:
|
F7410 Current controller output limited Reaction: OFF2 Acknowledgement: IMMEDIATELY | Cause: The condition “I_act = 0 and Uq_set_1 longer than 16 ms at its limit” is present and can be caused by the following:
Remedy:
|
| F7412 Commutation angle incorrect (motor model) | Cause: An incorrect commutation angle was detected that can result in a positive coupling in the speed controller. Possible causes:
Remedy:
|
| F7414 Encoder serial number changed | Cause:
Remedy: Re causes 1, 2:
Re causes 3, 4:
|
| F7420 Drive: Current setpoint filter natural frequency > Shannon frequency | Cause: One of the filter natural frequencies is greater than the Shannon frequency (2KHz). Filter 1 (p1658, p1660) Filter 2 (p1663, p1665) Filter 3 (p1668, p1670) Filter 4 (p1673, p1675) Remedy:
|
| F7450 Standstill monitoring has responded | Cause: After the standstill monitoring time expired, the drive left the standstill window.
Remedy: Check the causes and resolve. |
| F7452 Following error too high | Cause: The difference between the position setpoint position actual value (following error dynamic model) is greater than the tolerance.
Remedy: Check the causes and resolve. |
| F7801 Motor overcurrent | Cause: The permissible motor limit current was exceeded.
Remedy:
|
| F7802 Infeed or power unit not ready | Cause: After an internal power-on command, the infeed or drive does not signal ready because of one of the following reasons:
Remedy:
|
| F7815 Power unit has been changed | Cause: The code number of the actual power unit does not match the saved number. Remedy: Connect the original power unit and power up the Control Unit again (POWER ON). |
| F7900 Motor blocked/speed controller at its limit | Cause: The servo motor has been operating at the torque limit longer than 1s and below the speed threshold of 120 rpm. This signal can also be initiated if the speed actual value is oscillating and the speed controller output repeatedly goes to its limit. Remedy:
|
| F7901 Motor overspeed | Cause: The maximum permissible speed has been exceeded. Remedy: Check and correct the maximum speed (p1082). |
| F7995 Pole position identification not successful | Cause: The pole position identification routine was unsuccessful. Remedy: Contact the Hotline. |
| F30001 Power unit: Overcurrent | Cause: The power unit has detected an overcurrent condition.
Remedy:
|
| F30002 DC link voltage, overvoltage | Cause: The power unit has detected overvoltage in the DC link.
Remedy:
|
| F30003 DC link voltage, undervoltage | Cause: The power unit has detected an undervoltage condition in the DC link.
Remedy:
|
| F30004 Drive heat sink overtemperature | Cause: The temperature of the power unit heat sink has exceeded the permissible limit value.
Remedy:
|
F30005 Power unit: Overload I2t | Cause: The power unit was overloaded.
Remedy:
|
F30011 Line phase failure in main circuit | Cause: At the power unit, the DC link voltage ripple has exceeded the permissible limit value. Possible causes:
Remedy:
|
F30015 Phase failure motor cable | Cause: A phase failure in the motor feeder cable was detected. The signal can also be output in the following case: The motor is correctly connected, however the closed-speed control is instable and therefore an oscillating torque is generated. Remedy:
|
F30021 Ground fault | Cause: Power unit has detected a ground fault.
Remedy:
|
F30027 Precharging DC link time monitoring | Cause: The power unit DC link was not able to be pre-charged within the expected time.
Remedy: Check the line supply voltage at the input terminals. |
F30036 Internal overtemperature | Cause: The temperature inside the drive converter has exceeded the permissible temperature limit.
Remedy:
Notice: This fault can only be acknowledged once the permissible temperature limit minus 5 K has been fallen below. |
F30050 24 V supply overvoltage | Cause: The voltage monitor signals an overvoltage fault on the module. Remedy:
|
F30074 Communication error between the Control Unit and Power Module | Cause: Communications between the Control Unit (CU) and Power Unit (PU) via the interface no longer possible. The CU may have been withdrawn or is incorrectly inserted. Fault value (r0949, interpret hexadecimal):
Remedy: Reinsert the Control Unit (CU) or the Control Unit adapter (CUAxx) onto the original Power Unit (PU) and continue operation. If required, carry out a POWER ON for the CU and/or the CUA. |
F31100 Zero mark distance error | Cause: The measured zero mark distance does not correspond to the parameterized zero mark distance. For distance-coded encoders, the zero mark distance is determined from zero marks detected pairs. If a zero mark is missing, depending on the pair generation, this cannot result in a fault and also has no effect in the system. Remedy:
|
F31110 Serial communications error | Cause: Serial communication protocol transfer error between the encoder and evaluation module. Remedy:
|
F31112 Error bit set in the serial protocol | Cause: The encoder sends a set error bit via the serial protocol. Remedy:
|
| F31117 Inversion error signals A/B/R | Cause: For a square-wave encoder (bipolar, double ended) signals A*, B* and R* are not inverted with respect to signals A, B and R. Remedy:
|
| F31130 Zero mark and position error from the coarse synchronization | Cause: After initializing the pole position using track C/D, Hall signals or pole position identification routine, the zero mark was detected outside the permissible range. For distance-coded encoders, the test is carried out after passing 2 zero marks. Fine synchronization was not carried out. Remedy:
|
| F31150 Initialization error | Cause: Encoder functionality is not operating correctly. Remedy:
|
| F52980 Absolute encoder motor changed | Cause: The servo motor with absolute encoder is changed. Actual motor ID is different from commissioned motor ID. Remedy: The servo motor will be automatically configured after the acknowledgement of this fault. |
| F52981 Absolute encoder motor mismatched | Cause: Connected absolute encoder motor cannot be operated. The servo drive in use does not support the Motor ID. Remedy: Use a suitable absolute encoder motor. |
| F52983 No encoder detected | Cause: The servo drive in use does not support encoderless operation. Remedy:
|
| F52984 Incremental encoder motor not configured | Cause:
Remedy: Configure the motor ID by setting the parameter p29000. |
| F52985 Absolute encoder motor wrong | Cause:
Remedy:
|
| F52987 Absolute encoder replaced | Cause: Incorrect absolute encoder data. Remedy: Contact the Hotline. |
| A1009 Control module overtemperature | Cause: The temperature of the control module (Control Unit) has exceeded the specified limit value. Remedy:
Note: The alarm automatically disappears after the limit value has been undershot. |
| A1019 Writing to the removable data medium unsuccessful | Cause: The write access to the removable data medium was unsuccessful. Remedy: Remove and check the removable data medium. Then run the data backup again. |
| A1032 All parameters must be saved | Cause: The parameters of an individual drive object were saved, although there is still no backup of all drive system parameters. The saved object-specific parameters are not loaded the next time that the system powers up. Remedy: Save all parameters. |
| A1045 Configuring data invalid | Cause: An error was detected when evaluating the parameter files saved in the non-volatile memory. Remedy: Save the parameterization using the “SAVE” function on the BOP. This overwrites the incorrect parameter files in the non-volatile memory and the alarm is withdrawn. |
| A1920 Drive Bus: Receive setpoints after To | Cause: Output data of Drive Bus master (setpoints) received at the incorrect instant in time within the Drive Bus clock cycle. Remedy:
Note: To: Time of setpoint acceptance, Tdx: Data exchange time. |
| A1932 Drive Bus clock cycle synchronization missing for DSC | Cause: There is no clock synchronization or clock synchronous sign of life and DSC is selected. Remedy: Set clock synchronization across the bus configuration and transfer clock synchronous sign-of-life. |
| A5000 Drive heat sink overtemperature | Cause: The alarm threshold for overtemperature at the inverter heat sink has been reached. If the temperature rises by an additional 5 K, fault F30004 is initiated. Remedy: Check the following:
|
| A7012 Motor temperature model 1/3 overtemperature | Cause: The motor temperature model 1/3 identified that the alarm threshold was exceeded. Remedy:
|
| A7565 Encoder error in encoder interface | Cause: An encoder error was signaled for encoder via the encoder interface (G1_ZSW.15). Remedy: Acknowledge the encoder error using the encoder control word (G1_STW.15 = 1). |
| A7576 Encoderless operation due to a fault active | Cause: Encoderless operation is active due to a fault. Remedy:
|
| A7965 Save required | Cause: The angular commutation offset was re-defined and has still not been saved. Remedy: This alarm automatically disappears after the data has been saved. |
| A7971 Angular commutation offset determination activated | Cause: The automatic determination of the angular commutation offset (encoder adjustment) is activated. The automatic determination is carried out at the next power-on command. Remedy: The alarm automatically disappears after determination. |
| A7991 Motor data identification activated | Cause: The motor data identification routine is activated. The routine is carried out at the next power-on command. Remedy: The alarm automatically disappears after the motor data identification routine has been successfully completed. If a POWER ON or a warm restart is performed with motor data identification selected, the motor data identification request will be lost. If motor data identification is required, it will need to be selected again manually following ramp-up. |
| A30016 Load supply switched off | Cause: The DC link voltage is too low. Remedy:
|
| A30031 Hardware current limiting in phase U | Cause: Hardware current limit for phase U responded. The pulsing in this phase is inhibited for one pulse period.
Remedy: Check the motor data. As an alternative, run a motor data identification.
|
| A31411 Absolute encoder signals internal alarms | Cause: The absolute encoder fault word includes alarm bits that have been set. Remedy: Replace the encoder. |
| A31412 Error bit set in the serial protocol | Cause: The encoder sends a set error bit via the serial protocol. Remedy:
|
| A52900 Failure during data copying | Cause:
Remedy:
|