Atn Autotune active. |
Cause:
- Autotune function is currently running.
Remedy:
- Indication only; no action required.
|
ETN Autotuning error. |
Cause:
- Autotune readings significantly inconsistent with configuration.
- A non-3-phase motor is being used.
- Improper settings at F400 or F410 to F413.
- Motor rating significantly smaller than ASD rating.
- Output cabling too small, too long, or EMF interference.
- Motor is running during Autotune.
Remedy:
- Verify motor wiring and type.
- Check and adjust parameters F400 and F410-F413.
- Ensure motor is stopped before tuning.
|
ETN1 Autotuning error — Torque boost error. |
Cause:
- Improper setting at F410.
Remedy:
|
ETN2 Autotuning error — Leak inductance error. |
Cause:
- Improper setting at F412.
Remedy:
|
ETN3 Autotuning error — Motor rating error. |
Cause:
- Improper setting at F405, F406, or F407.
Remedy:
- Correct settings F405, F406, or F407.
|
ETYP Typeform error. |
Cause:
- Firmware information inconsistent between Application Board and Motor Control board.
- Application Board or Motor Control board is defective.
Remedy:
- Perform a Typeform Reset.
- Replace defective board if reset fails.
|
4-20 mA 4-20 Signal Loss. |
Cause:
- Misconnection, poor connection, or broken wire.
- Improper programming at F201 and associated parameters.
Remedy:
- Check wiring continuity.
- Verify parameter F201.
|
CM1 Internal communications error. |
Cause:
- Improperly programmed ASD.
- Improper communications settings.
Remedy:
- Check communications programming.
|
CM2 External communications error. |
Cause:
- Improperly connected cables.
Remedy:
- Secure and check external cable connections.
|
COFF Under-voltage condition at optional Control power supply. |
Cause:
- Misconnection, poor connection, or broken wire.
- Defective power supply.
Remedy:
- Check wiring.
- Replace power supply if defective.
|
DAMP Damper closed. |
Cause:
- Improper configuration/programming for Damper Control at discrete input terminals.
Remedy:
- Check discrete input terminal configuration.
|
Emergency Off Output signal terminated/Brake applied. |
Cause:
- Stop-Reset pressed twice at the EOI.
- EOFF command received remotely.
Remedy:
|
HLD Heavy load — motor/ASD overloaded. |
Cause:
- Accel setting is too short.
- ASD/Motor not right-sized for application.
- Excessively fluctuating load.
Remedy:
- Increase Accel time.
- Verify motor/drive sizing.
|
LLD Light load. |
Cause:
- ASD/Motor should be right-sized for application.
Remedy:
- Verify load matches drive capacity.
|
LLT Lower-limit time. |
Cause:
- Parameter F256 adjustment required.
Remedy:
|
LTA Part replacement alarm. |
Cause:
- Part Replacement Alarm activation as set at F634.
Remedy:
- Perform scheduled maintenance/replacement.
|
MOFF Main under-voltage condition. |
Cause:
- Low 3-phase commercial power voltage level.
Remedy:
- Check input power supply voltage.
|
OC Over-Current — ASD output > F601. |
Cause:
- Phase-to-phase short (U, V, or W).
- Defective IGBT.
- Output cabling connected incorrectly.
- Restarting into a spinning motor (no catch-spin).
- Motor/machine jammed or brake engaged.
- Accel/Decel too short or Voltage Boost too high.
- Load fluctuations or high temp.
Remedy:
- Check cabling and motor for shorts.
- Check for mechanical jams.
- Adjust Accel/Decel or V/f settings.
|
OH Overheat — ASD ambient temp excessive. |
Cause:
- ASD operating at elevated temperature.
- Cooling fan obstructed or inoperative.
- Internal thermistor disconnected.
Remedy:
- Clean vents and check fans.
- Reduce ambient temperature.
|
OJ User-set run-time counter exceeded. |
Cause:
Remedy:
- Type Reset required; select Clear run timer.
|
OLI ASD overload. |
Cause:
- Carrier frequency too high.
- Excessive load.
- Accel time too short.
- DC damping rate too high.
- Motor starting into spinning load.
Remedy:
- Reduce carrier frequency.
- Increase Accel time.
- Check load conditions.
|
OLM Motor overload. |
Cause:
- V/f parameter improperly set.
- Motor locked or running low speed continuously.
- Motor improperly matched to load.
Remedy:
- Adjust V/f parameters.
- Check for motor locking/jams.
|
OLST Overload soft Stall active. |
Cause:
- Soft Stall Selection adjustment required (F017).
Remedy:
|
OP DC bus voltage exceeds specifications. |
Cause:
- Starting into spinning motor after momentary power loss.
- High input voltage or spikes (install inductive filter).
- Decel time too short.
- Regenerative load (Over-voltage stall turned off).
Remedy:
- Increase Decel time.
- Install input reactor/filter.
- Enable Ridethrough (F302) or Over-voltage stall.
|
OT Over-torque. |
Cause:
- Torque requirement exceeds F616/F617 for time > F618.
- ASD not matched to application.
- Load obstructed.
Remedy:
- Check load for obstructions.
- Adjust torque parameters F616, F617, F618.
|
POFF Under-voltage at 5, 15, or 24 VDC supply. |
Cause:
- Defective Control board.
- Excessive load on power supply.
- Low input voltage.
Remedy:
- Check input voltage.
- Replace Control board if defective.
|
POT Pre-over-torque. |
Cause:
- Torque requirement exceeds F616 or F617.
- Load obstructed.
Remedy:
- Clear load obstruction.
- Adjust F616/F617 if necessary.
|
PTC Optional thermal sensor threshold exceeded. |
Cause:
- User-set thermal threshold (F646) exceeded.
Remedy:
- Check temperature or adjust F646.
|
UC Under-current. |
Cause:
- Current below level defined at F611.
Remedy:
- Disable detection at F610 or adjust F611.
|
E-10 Over-voltage at analog input. |
Cause:
- Mis-wire at the ASD input terminals.
Remedy:
- Check input terminal wiring.
|
E-12 Open circuit at shaft-mounted encoder. |
Cause:
Remedy:
- Check encoder connection.
|
E-13 Over-speed error. |
Cause:
- Motor speed > commanded speed.
- Improper encoder connection or setup.
- Defective encoder.
Remedy:
- Check encoder setup and hardware.
|
E-18 Loss of signal at analog input. |
Cause:
- V/I input missing or low.
- Over-current at P24.
Remedy:
- Check analog signal source.
|
E-19 CPU communication error. |
Cause:
- Internal CPU communication failure.
Remedy:
|
E-20 Speed/torque/direction signal error. |
Cause:
- Control signal transfer error.
Remedy:
|
E-21 Stack overflow error. |
Cause:
- Internal processing error.
Remedy:
|
E-22 Improper input voltage at discrete input. |
Cause:
- Input activation voltage out of specification.
Remedy:
- Check discrete input voltage levels.
|
E-23 Expansion card option 1 hardware error. |
Cause:
Remedy:
|
E-24 Expansion card option 2 hardware error. |
Cause:
Remedy:
|
E-26 CPU fault. |
Cause:
Remedy:
|
EEP1 EEPROM write error. |
Cause:
Remedy:
|
EEP2 / EEP3 EEPROM read error. |
Cause:
- Data retrieval failure during initialization.
Remedy:
|
EF1 Software-detected earth fault. |
Cause:
- Mis-wired ground.
- Loose ground connection.
- ASD setup improperly.
Remedy:
|
EF2 Hardware-detected earth fault. |
Cause:
- Mis-wired ground or loose connection.
Remedy:
|
Emergency Off Emergency Off command (Trip). |
Cause:
- Stop-Reset pressed twice.
- EOFF command received.
Remedy:
- ASD reset required.
- Check stopping method at F603.
|
EPHI Input phase loss (R, S, or T). |
Cause:
- Mis-wired input phase.
- Loose input phase connection.
Remedy:
- Check input power wiring.
|
EPHO Output phase loss (U, V, or W). |
Cause:
- Mis-wired output phase.
- Loose output phase connection.
Remedy:
|
ERR2 / ERR3 / ERR4 / ERR5 / ERR6 Internal ROM/RAM/CPU/Comm/Gate Array errors. |
Cause:
- Internal hardware or communication timeouts.
- Improper setup or connections (ERR5/ERR8).
Remedy:
- Service call required (for most hardware errors).
- Check cables and setup (for Comm/Net errors).
|
OC1 / OC1P Over-current during acceleration. |
Cause:
- V/f setting needs adjustment.
- Restart from momentary power outage.
- Starting into rotating motor.
- Phase-to-phase short.
- Accel time too short.
- Voltage Boost too high.
- Motor jammed or brake engaged.
Remedy:
- Adjust V/f or Accel settings.
- Clear jams/brakes.
- Check for shorts.
|
OC2 / OC2P Over-current during deceleration. |
Cause:
- Phase-to-phase short.
- Decel time too short.
- Motor/machine jammed.
Remedy:
- Increase Decel time.
- Check for shorts/jams.
|
OC3 / OC3P Over-current during run. |
Cause:
- ASD/Motor load not matched.
- Load fluctuations.
- Elevated temperature.
Remedy:
- Verify drive sizing.
- Check cooling.
|
OCA1 / OCA2 / OCA3 Over-current at U/V/W phase IGBT. |
Cause:
- Low impedance at the specific phase (U, V, or W).
Remedy:
- Check IGBT and motor phase impedance.
|
OCL Output short circuit at U-V-W. |
Cause:
- Phase-to-phase short.
- Starting into rotating motor.
- Short Circuit Detection adjustment required (F613).
Remedy:
- Check wiring for shorts.
- Adjust F613.
|
OH Over temperature error. |
Cause:
- Cooling fan inoperative.
- Ventilation obstructed.
Remedy:
- Check fans and clear vents.
|
OH2 Over temperature at PTC1/PTC2. |
Cause:
- Over-temperature detected by option board.
- See F637 and F638.
Remedy:
- Check external device temperature.
|
OL1 ASD overload error. |
Cause:
- Accel time too short.
- DC Injection current too high.
- V/f setting needs adjustment.
Remedy:
- Adjust Accel or V/f settings.
|
OL2 Motor overload error. |
Cause:
- Motor locked or continuous low speed.
- Load exceeds motor ability.
Remedy:
- Check for jams.
- Review sizing.
|
OP1 / OP2 / OP3 Over-voltage (Accel/Decel/Run). |
Cause:
- Motor running during restart.
- Decel time too short.
- Stall protection disabled.
- Input voltage out of spec.
Remedy:
- Increase Decel time.
- Check input voltage.
- Install input reactance if needed.
|
OT Over-torque error. |
Cause:
- Torque exceeds F616/F617 settings.
- Load obstructed.
Remedy:
- Clear obstruction.
- Adjust torque parameters.
|
SOUT Permanent magnet motor pull out trip. |
Cause:
Remedy:
|
UC Low-Current error. |
Cause:
- Improper low-current detection level setting.
Remedy:
|
UP1 Main power under-voltage. |
Cause:
- 3-phase input voltage low.
- Defective control board.
- Excessive load on power supply.
- Under-Voltage/Ridethrough settings require adjustment.
Remedy:
- Check input power.
- Adjust Ridethrough settings.
|